En-7

4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.

Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 

a malfunction.

Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 

power supply.

•  Correction completes in 10 to 15 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When  the  result  was  “cannot  be  corrected”,  press  the  piping/wiring  correction  switch 

(SW871) again to cancel this function. Then, confirm the wiring and piping combination in 

a conventional manner by operating the indoor units one by one.

•  The operation is done while the power is supplied. Make sure not to contact parts other 

than the switch, including the P.C. board. This may cause electric shock or burn by hot 

parts and live parts around the switch. Contacting the live parts may cause P.C. board 

damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED

1 (Red)

2 (Yellow)

3 (Green)

Lighted

Lighted

Blinking

Result of piping/wiring correction function

LED

Result

1 (Red)

2 (Yellow) 3 (Green)

Lighted Not lighted Lighted Completed

(Corrected successfully)

Blinking

Blinking

Blinking Cannot be corrected

Other indications

Refer to “SAFETY PRE-

CAUTIONS WHEN LED 

FLASHES” located behind 

the service panel.

5-1. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa 

[Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation on all the indoor units.

  To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply 

plug and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.

  Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details .

When pumping down the refrigerant, stop the compressor before disconnecting 

the refrigerant pipes. The compressor may burst if air etc. get into it.

 

WARNING

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

5.  RELOCATION AND MAINTENANCE

JG79A366H03_en.indd   7

2016/03/02   8:49:50

Summary of Contents for MXZ-4C80VA

Page 1: ... Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendør...

Page 2: ...efrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could ...

Page 3: ...oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wireless equipment Where there is emission of high levels of VOCs including phthalate compounds formaldehyde etc which may cause chemical cracking 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit i...

Page 4: ... 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quantity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the back bo...

Page 5: ...ng section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC T...

Page 6: ...ted 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps in their initial state 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outd...

Page 7: ...1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if thi...

Page 8: ... the live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green L...

Page 9: ...работающем компрессоре и открытом стопорном клапане возможно засасывание воздуха и чрезмерное повышение дав ления в контуре охлаждения Это может привести к разрыву труб или нанесению увечий n При установке прибора надежно подсоедините трубы с хладагентом до запуска компрессора Если компрессор запускается до подсоединения труб с хладагентом и при открытом стопорном клапане возможно засасывание возд...

Page 10: ...нтально Производите установку в местах где отсутствует воздействие снегопада ветра и снега В районах с сильным снегопадом уста новите навес опору и или несколько отражательных перегородок Примечание Рекомендуется сделать трубную петлю рядом с наружным прибором для уменьшения передаваемой оттуда вибрации Примечание При эксплуатации кондиционера при низкой температуре наружно го воздуха обязательно ...

Page 11: ... Воздуховыпускное отверстие 1 6 ТРУБОПРОВОДЫ ДРЕНАЖНОЙ СИСТЕМЫ НАРУЖНОГО БЛОКА Воздухозаборное отверстие 900 мм 500 мм 200 мм 2 U образные отверстия с пазом Болт основания M10 320 мм 2 12 мм 36 мм овальные отверстия Болт основания M10 355 мм 387 мм После проверки на отсутствие утечек плотно нанесите изо ляционный материал чтобы обеспечить отсутствие зазоров В случае крепления трубопро водов к стен...

Page 12: ...е винты клеммной колодки для предотвраще ния их ослабления После затяжки винтов слегка потяните за про вода чтобы убедиться в их неподвижности 4 Выполните 2 и 3 для каждого внутреннего прибора 5 Подсоедините шнур электропитания А 6 Закрепите провод соединения внутреннего наружного приборов В и шнур электропитания А с помощью проводных зажимов 7 Надежно закройте сервисную панель Убедитесь что этап ...

Page 13: ... виде запорные клапаны полностью закрыты и прикрыты колпачками 2 Подключите клапан коллектора с измерителем и вакуумный насос к сервисному порту стопорного клапана на стороне трубы для газа наружного прибора 3 Включите вакуумный насос Продолжайте создавать вакуум в течение не менее 15 минут 4 Проверьте вакуум с помощью клапана коллектора с измерителем затем закройте клапан коллектора с измерителем...

Page 14: ... переключатель 1 в SW1 на наружной панели управления в положение ON ВКЛ чтобы включить эту функцию 3 Установите переключатель 2 в SW1 на наружной панели управления в положение OFF ВЫКЛ чтобы заблокировать режим работы COOL DRY ОХЛАЖДЕНИЕ СУШКА Чтобы заблокировать режим работы HEAT ОБОГРЕВ установите тот же переключатель в позиции ON ВКЛ 4 Включите электропитание кондиционера Описание функции С дан...

Page 15: ...атной платы системы электронно го управления обязательно выполните процедуру снятия электростати ческого заряда перед включением данной функции Данная функция не работает при температуре наружного воздуха 0 C или ниже Индикация светодиода во время обнаружения Светодиод 1 Красный 2 Желтый 3 Зеленый Горит Горит Мигает Результат работы функции коррекции труб проводов Светодиод Результат 1 Крас ный 2 ...

Page 16: ...HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A366H03 ...

Reviews: