En-3

1-5. INSTALLATION DIAGRAM

Units should be installed by licensed contractor according to local code requirements.

After the leak test, apply insulat-

ing material tightly so that there 

is no gap.

When the piping is to be attached to 

a wall containing metals (tin plated) 

or metal netting, use a chemically 

treated  wooden  piece  20  mm  or 

thicker between the wall and the 

piping or wrap 7 to 8 turns of insula-

tion vinyl tape around the piping.

To use existing piping, perform 

COOL  operation  for  30  minutes 

and pump down before removing 

the old air conditioner. Remake flare 

according to the dimension for new 

refrigerant.

ACCESSORIES

Check the following parts before installation.

(1) Drain socket

1

(2) Drain cap

2

PARTS TO BE PROVIDED AT YOUR SITE

(A) Power supply cord*

1

(B) Indoor/outdoor unit connecting wire*

1

(C) Extension pipe

1

(D) Wall hole cover

1

(E) Piping tape

1

(F)

Extension drain hose 

(or soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16)

1

(G) Refrigeration oil

Little 

amount

(H) Putty

1

(I) Pipe fixing band

2 to 7

(J) Fixing screw for (I)

2 to 7

(K) Wall hole sleeve

1

(L)

Soft PVC hose, 25 mm inner 

diameter or hard PVC pipe VP25 

for drain socket (1)

1

* Note:

Place  indoor/outdoor  unit  connecting  wire  (B)  and 

power supply cord (A) at least 1 m away from the 

TV antenna wire.

The “Q’ty” for (B) to (K) in the above table is quantity 

to be used per indoor unit.

More than 

100 mm

Open as a rule

More than 500 mm 

if the front and both 

sides are open

More than 100 mm 

More than 200 mm if there are 

obstacles to both sides

Open as a rule

More than 500 mm if the back, 

both sides and top are open

More than 350 mm

Outdoor unit installation

Air inlet

Air outlet

1-6. DRAIN PIPING FOR OUTDOOR UNIT

Please perform the drain piping work only when draining from one place.

1) Choose one hole to discharge drain and install the drain socket (1) to the hole.

2) Close the rest of the holes with the drain caps (2).

3) Connect the soft PVC hose (L) of 25 mm in the inside diameter on the market with the drain socket (1) and lead drain.

Note:

Install the unit horizontally.

Do not use the drain socket (1) and the drain caps (2) in the cold regions. Drain may freeze and it makes the fan stop. 

The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds from 

being wet by drain water or damaged by frozen drain water.

Air inlet

900 mm
500 mm

200 

mm

2-U-shape notched holes

(Base bolt M10)

320

 mm

2 - 12 mm × 36 mm  

oval holes (Base bolt M10)

355

 mm

387

 mm

JG79A366H03_en.indd   3

2016/03/02   8:49:49

Summary of Contents for MXZ-4C80VA

Page 1: ... Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendør...

Page 2: ...efrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could ...

Page 3: ...oil Salty places such as the seaside Where sulfide gas is generated such as a hot spring Where there is high frequency or wireless equipment Where there is emission of high levels of VOCs including phthalate compounds formaldehyde etc which may cause chemical cracking 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit i...

Page 4: ... 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quantity to be used per indoor unit More than 100 mm Open as a rule More than 500 mm if the front and both sides are open More than 100 mm More than 200 mm if there are obstacles to both sides Open as a rule More than 500 mm if the back bo...

Page 5: ...ng section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC T...

Page 6: ...ted 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared section and do flaring work again 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe The stop valves are fully closed and covered in caps in their initial state 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outd...

Page 7: ...1 on the outdoor controller board to OFF To lock the operation in HEAT mode set the same switch to ON 4 Turn on the main power for the air conditioner Description of the function With this function the operating noise of the outdoor unit can be lowered by reducing the operation load for example during nighttime in COOL mode However please note that the cooling and heating capacity may lower if thi...

Page 8: ... the live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimination before operating this function This function does not operate when the outside temperature is 0 C or below LED indication during detection LED 1 Red 2 Yellow 3 Green Lighted Lighted Blinking Result of piping wiring correction function LED Result 1 Red 2 Yellow 3 Green L...

Page 9: ...работающем компрессоре и открытом стопорном клапане возможно засасывание воздуха и чрезмерное повышение дав ления в контуре охлаждения Это может привести к разрыву труб или нанесению увечий n При установке прибора надежно подсоедините трубы с хладагентом до запуска компрессора Если компрессор запускается до подсоединения труб с хладагентом и при открытом стопорном клапане возможно засасывание возд...

Page 10: ...нтально Производите установку в местах где отсутствует воздействие снегопада ветра и снега В районах с сильным снегопадом уста новите навес опору и или несколько отражательных перегородок Примечание Рекомендуется сделать трубную петлю рядом с наружным прибором для уменьшения передаваемой оттуда вибрации Примечание При эксплуатации кондиционера при низкой температуре наружно го воздуха обязательно ...

Page 11: ... Воздуховыпускное отверстие 1 6 ТРУБОПРОВОДЫ ДРЕНАЖНОЙ СИСТЕМЫ НАРУЖНОГО БЛОКА Воздухозаборное отверстие 900 мм 500 мм 200 мм 2 U образные отверстия с пазом Болт основания M10 320 мм 2 12 мм 36 мм овальные отверстия Болт основания M10 355 мм 387 мм После проверки на отсутствие утечек плотно нанесите изо ляционный материал чтобы обеспечить отсутствие зазоров В случае крепления трубопро водов к стен...

Page 12: ...е винты клеммной колодки для предотвраще ния их ослабления После затяжки винтов слегка потяните за про вода чтобы убедиться в их неподвижности 4 Выполните 2 и 3 для каждого внутреннего прибора 5 Подсоедините шнур электропитания А 6 Закрепите провод соединения внутреннего наружного приборов В и шнур электропитания А с помощью проводных зажимов 7 Надежно закройте сервисную панель Убедитесь что этап ...

Page 13: ... виде запорные клапаны полностью закрыты и прикрыты колпачками 2 Подключите клапан коллектора с измерителем и вакуумный насос к сервисному порту стопорного клапана на стороне трубы для газа наружного прибора 3 Включите вакуумный насос Продолжайте создавать вакуум в течение не менее 15 минут 4 Проверьте вакуум с помощью клапана коллектора с измерителем затем закройте клапан коллектора с измерителем...

Page 14: ... переключатель 1 в SW1 на наружной панели управления в положение ON ВКЛ чтобы включить эту функцию 3 Установите переключатель 2 в SW1 на наружной панели управления в положение OFF ВЫКЛ чтобы заблокировать режим работы COOL DRY ОХЛАЖДЕНИЕ СУШКА Чтобы заблокировать режим работы HEAT ОБОГРЕВ установите тот же переключатель в позиции ON ВКЛ 4 Включите электропитание кондиционера Описание функции С дан...

Page 15: ...атной платы системы электронно го управления обязательно выполните процедуру снятия электростати ческого заряда перед включением данной функции Данная функция не работает при температуре наружного воздуха 0 C или ниже Индикация светодиода во время обнаружения Светодиод 1 Красный 2 Желтый 3 Зеленый Горит Горит Мигает Результат работы функции коррекции труб проводов Светодиод Результат 1 Крас ный 2 ...

Page 16: ...HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A366H03 ...

Reviews: