The other cases
• When the operation frequency does not go up from the lowest frequency.
Check of bus-bar voltage
•Check the voltage of power supply.
•Confi rm outdoor unit failure mode
recall function. (Refer to 12-2.2.)
Blink 5 times
Confi rm LED1 indication lamp on the
outdoor control P.C. board.
Replace the outdoor power
P.C. board.
Blink 9 times
Replace the outdoor control
P.C. board.
Turn OFF power supply before removing P.C. board.
Confi rm LED1 indication lamp
on the outdoor control P.C.
board.
Turn ON power supply. Start
operation.
Lighting
Replace the outdoor control
P.C. board.
Blink 9 times
Replace the outdoor power
P.C. board.
Confi rm LED1 indication lamp
on the outdoor control P.C.
board.
Turn ON power supply. Start
operation.
Normal
Lighting
Lighting
Check of HPS
Infinity
No
Yes
1. Disconnect the connector CN63H in the outdoor control P.C. board.
2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned OFF.
Check the resistance between each terminal.
Reconnect CN63H.
Turn ON the power supply to the indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed immediately
after compressor starts?
Replace HPS.
Replace the outdoor control P.C. board.
Normal
Connector
MXZ-3F, 4F
CN63H
Outdoor control
P.C. board
Indoor unit does not operate. (different operating models in multi system)
• When you try to run 2 indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal to
the outdoor units fi rst decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back
ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas
continuously fl ows into the indoor unit even while it is not operating.
MXZ-3F54VF/3F68VF/4F72VF
MXZ-3F54VF/3F68VF/4F72VF
OBH790
Summary of Contents for MXZ-2F33VF
Page 22: ...22 OUTLINES AND DIMENSIONS 6 MXZ 2F33VF MXZ 2F42VF MXZ 2F53VF MXZ 2F53VFH Unit mm OBH790 ...
Page 25: ...25 WIRING DIAGRAM 7 MXZ 2F33VF E1 ET1 MXZ 2F42VF E1 ET1 MXZ 2F53VF E1 ET1 OBH790 ...
Page 26: ...26 MXZ 2F53VFH E1 OBH790 ...
Page 27: ...27 MXZ 3F54VF E1 ET1 MXZ 3F68VF E1 ET1 OBH790 ...
Page 28: ...28 MXZ 4F72VF E1 ET1 OBH790 ...
Page 93: ...93 OBH790 ...