background image

En-4

4-1. PURGING PROCEDURES AND LEAK TEST

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and the pipe connections of the out

-

door unit. Do not apply refrigeration oil on screw threads. Excessive tightening torque will result in damage 
on the screw.

2) Align the center of the pipe with that of the pipe connections of the outdoor unit, then hand tighten the flare 

nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

• Over-tightening may cause damage to the flare nut, resulting in refrigerant leakage.

• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or 

frostbite.

3-3. INSULATION AND TAPING

) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).
•  When piping have to be arranged through above ceiling, closet or where the temperature and humidity 

are high, wind additional commercially sold insulation to prevent condensation.

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

) Remove  service  port  cap  of  stop  valve  on  the  side  of  the  outdoor 

unit gas pipe. (The stop valves are fully closed and covered in caps 
in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 5 minutes.)
4) Check  the  vacuum  with  gauge  manifold  valve,  then  close  gauge 

manifold valve, and stop the vacuum pump.

5) Leave  as  it  is  for  one  or  two  minutes.  Make  sure  the  pointer  of 

gauge  manifold  valve  remains  in  the  same  position.  Confirm  that 

pressure gauge shows -0.0 MPa [Gauge] (-760 mmHg).

6) Remove  gauge  manifold  valve  quickly  from  service  port  of  stop 

valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Oper-

ating without fully opening lowers the performance and this causes 
trouble.

8) Refer  to  -2.,  and  charge  the  prescribed  amount  of  refrigerant  if 

needed. Be sure to charge slowly with liquid refrigerant. Otherwise, 
composition  of  the  refrigerant  in  the  system  may  be  changed  and 
affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.
0) Leak test

 

WARNING

When  installing  the  unit,  securely 
connect  the  refrigerant  pipes  before 
starting the compressor.

 

CAUTION

When  there  are  the  ports  which  are 
not  used,  make  sure  their  nuts  are 
tightened securely.

Stop valve 
for GAS

Stop valve 
cap (Torque 
9.6 to 29.4 
N•m, 200 to 
300 kgf•cm)

Gauge manifold 
valve (for R40A)

Compound pressure 
gauge (for R40A)

–0.0 MPa  
(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump
(for R40A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 
for LIQUID

Pressure gauge
(for R40A)

Precautions when using 
the control valve

When attaching the control valve to 
the service port, valve core may de-
form or loosen if excess pressure is 
applied. This may cause gas leak.

Service 
port

Charge hose 
(for R40A)

Body

Close

Open

Control 
valve

A

When attaching the control valve to 
the service port, make sure that the 
valve core is in closed position, and 
then  tighten  part A.  Do  not  tighten 
part A  or  turn  the  body  when  valve 
core is in open position.

Service port cap
(Torque 3.7 to 7.7 N•m, 
40 to 80 kgf•cm)

Charge hose 
(for R40A)

4-2. GAS CHARGE

Perform gas charge to unit.
) Connect gas cylinder to the service port of stop valve.
2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air condi

-

tioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 
liquid  refrigerant. Adding  gas  refrigerant  may  change  the  composition  of  the 
refrigerant in the system and affect normal operation of the air conditioner. Also, 
charge the liquid refrigerant slowly, otherwise the compressor will be locked.
To  maintain  the  high  pressure  of  the  gas  cylinder,  warm  the  gas  cylinder  with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

Refrigerant gas            
cylinder  
operating valve
(for R40A)

Indoor 

unit

Charge hose (for R40A)

Refrigerant gas cylinder 
for R40A with siphon

Electronic scale for 
refrigerant charging

Refrigerant (liquid)

Indoor 

unit

Union

Union

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Stop valve

Service port

Outdoor 

unit

Gauge manifold 
valve (for R40A)

JG79A641H01_en.indd   4

2013/09/06   15:47:06

Summary of Contents for MXZ-2D52VA

Page 1: ... 2D52VA English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit JG79A641H01_en indd 1 2013 09 06 15 47 04 ...

Page 2: ... n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete...

Page 3: ...wer supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use ...

Page 4: ...unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT UNI...

Page 5: ...e system may be changed and affect performance of the air conditioner 9 Tighten cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 2...

Page 6: ...by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 4 6 EXPLANATION TO THE USER Using the OPERATING INSTRUCTIONS explain to the user how to use the air conditioner how to us...

Page 7: ...A4 tombo blank indd 1 12 18 2006 9 45 16 AM ...

Page 8: ...JG79A641H01 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A641H01_en_cover indd 2 2013 08 22 13 30 01 ...

Reviews: