1-6. DRAIN PIPING FOR OUTDOOR UNIT

Please perform the drain piping work only when draining from one place.
) Provide drain piping before indoor and outdoor piping connection. 
2) Connect the soft PVC hose (L) I.D.5 mm as shown in the illustration.

3) Make sure to provide drain piping with a downhill grade for easy drain flow.

Note:

Install the unit horizontally.
Do not use the drain socket () in the cold regions. Drain may freeze and it makes 
the fan stop. 
The outdoor unit produces condensate during the heating operation. Select the in-
stallation place to ensure to prevent the outdoor unit and/or the grounds from being 
wet by drain water or damaged by frozen drain water.

() Drain socket

(L) Soft PVC hose

2.  OUTDOOR UNIT INSTALLATION

2-1. CONNECTING  WIRES FOR OUTDOOR UNIT

•  Be  sure  to  attach  each  screw  to  its 

correspondent  terminal  when  secur-
ing  the  cord  and/or  the  wire  to  the 
terminal block.

•  Make  earth  wire  a  little  longer  than 

others. (More than 35 mm)

•  For future servicing, give extra length 

to the connecting wires.

Terminal block for power supply

) Remove the service panel.
2) Loosen  terminal  screw,  and  connect  indoor/outdoor  unit  connecting 

wire (B) from the indoor unit correctly on the terminal block. Be careful 
not to make mis-wiring. Fix the wire to the terminal block securely so 
that no part of its core is appeared, and no external force is conveyed 
to the connecting section of the terminal block. 

3) Firmly tighten the terminal screws to prevent them from loosening. Af-

ter tightening, pull the wires lightly to confirm that they do not move.

4) Perform 2) and 3) for each indoor unit.
5) Connect power supply cord (A).
6) Fix indoor/outdoor unit connecting wire (B) and power supply cord (A) 

with the cable clamps.

7) Close the service panel securely. Make sure that 3-2. PIPE CONNEC-

TION is completed.

•  After  making  connections  between  both  power  supply  cord  (A)  and 

indoor/outdoor unit connecting wire (B), be sure to fix both cable and 

wire with cable clamps.

Indoor/outdoor unit connecting wire

<OUTDOOR UNIT>

35 mm

5 mm

Lead wire

Terminal block

UNIT

UNIT

Terminal block for 
power supply

<INDOOR UNIT>

POWER SUPPLY
~/N 230 V 50 Hz

Service panel

Fig. 

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

Pipe diameter 

(mm)

Nut 

(mm)

A (mm)

Tightening torque

Clutch 

type tool  

for R40A

Clutch 

type tool  

for R22

Wing nut 

type tool  

for R22

N•m

kgf•cm

ø6.35 (/4”)

7

0 to 0.5

.0 to .5

.5 to 2.0

3.7 to 7.7 40 to 80

ø9.52 (3/8”)

22

34.3 to 4.2 350 to 420

ø2.7 (/2”)

26

2.0 to 2.5

49.0 to 56.4 500 to 575

ø5.88 (5/8”)

29

73.5 to 78.4 750 to 800

Tilted Uneven Burred

Good

No good

Burr

Copper pipe

Spare reamer

Pipe cutter

Smooth all 
around

Even length 
all around

Inside is shin-
ing without any 
scratches.

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 
pipe

) Cut the copper pipe correctly with pipe cutter. (Fig. , 2)
2) Completely remove all burrs from the cut cross section of pipe. (Fig. 3)

•  Aim  the  copper  pipe  downward  while  removing  burrs  to  prevent 

burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, then put them 

on pipe having completed burr removal. (Not possible to put them on 

after flaring work.) 

4) Flaring  work  (Fig.  4,  5).  Firmly  hold  copper  pipe  in  the  dimension 

shown  in  the  table.  Select  A  mm  from  the  table  according  to  the  tool 
selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared section and do flar

-

ing work again.

JG79A641H01_en.indd   3

2013/09/06   15:47:06

Summary of Contents for MXZ-2D52VA

Page 1: ... 2D52VA English Installation Manual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit JG79A641H01_en indd 1 2013 09 06 15 47 04 ...

Page 2: ... n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropri ate tools or materials and incomplete...

Page 3: ...wer supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units should be installed by licensed contractor according to local code requirements After the leak test apply insulat ing material tightly so that there is no gap When the piping is to be at tached to a wall containing metals tin plated or metal netting use ...

Page 4: ...unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Indoor outdoor unit connecting wire OUTDOOR UNIT 35 mm 15 mm Lead wire Terminal block UNIT UNI...

Page 5: ...e system may be changed and affect performance of the air conditioner 9 Tighten cap of service port to obtain the initial status 10 Leak test WARNING When installing the unit securely connect the refrigerant pipes before starting the compressor CAUTION When there are the ports which are not used make sure their nuts are tightened securely Stop valve for GAS Stop valve cap Torque 19 6 to 29 4 N m 2...

Page 6: ...by one Make sure that the following is done Power is supplied to the unit Stop valves are open About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 4 6 EXPLANATION TO THE USER Using the OPERATING INSTRUCTIONS explain to the user how to use the air conditioner how to us...

Page 7: ...A4 tombo blank indd 1 12 18 2006 9 45 16 AM ...

Page 8: ...JG79A641H01 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JG79A641H01_en_cover indd 2 2013 08 22 13 30 01 ...

Reviews: