10-5. PRE-HEAT CONTROL
If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and collected in the compressor,
it may interfere the start-up of the compressor. To improve start-up condition, the compressor is energized even while it is
not operating to generate heat at the winding.
The compressor uses about 50 W when pre-heat control is turned ON. Pre-heat control is OFF(
MXZ-2D33VA/2D40VA/2
D42VA/2D42VA2/2D53VA/2D53VA2/2D53VAH/2D53VAH2
)/ON (
MXZ-3D54VA/3D54VA2/3D68VA/4D72VA/4D83VA/5D1
02VA/6D122VA
) at the default setting.
[How to activate pre-heat control]
MXZ-2D33VA/2D40VA/2D42VA/2D42VA2/2D53VA/2D53VA2/2D53VAH/2D53VAH2/3D54VA/3D54VA2/3D68VA/4D72VA/
4D83VA/5D102VA
(1) Turn OFF the power supply and make sure that the LED goes off.
(2) Set the “4” of SW2 as shown figure below to ON to activate pre-heat control function.
(3) Turn ON the power supply.
SW2
SW2
MXZ-2D33VA/2D40VA/2D42VA/2D42VA2
MXZ-2D53VA/2D53VA2/2D53VAH/2D53VAH2
SW2 on the outdoor display P.C. board
MXZ-6D122VA
SW2 on the outdoor control P.C. board
MXZ-3D54VA/3D54VA2/3D68VA/4D72VA
MXZ-4D83VA/5D102VA
SW2 on the outdoor control P.C. board
MXZ-6D122VA
(1) Turn OFF the power supply for the air conditioner before making the setting.
(2) Set the "4" of SW2 as shown figure below to OFF to activate pre-heat control function.
(3) Turn ON the power supply for the air conditioner.
NOTE
: Pre-heat control will be turned OFF when the power supply is turned OFF.
OBH626K
Summary of Contents for MXZ-2D33VA
Page 26: ...26 MXZ 2D33VA E2 MXZ 2D42VA E2 MXZ 2D53VA E2 OBH626K ...
Page 27: ...27 MXZ 2D33VA E3 MXZ 2D42VA E3 MXZ 2D53VA E3 OBH626K ...
Page 28: ...28 MXZ 2D33VA ER2 MXZ 2D40VA ER2 MXZ 2D53VA ER2 OBH626K ...
Page 29: ...29 MXZ 2D33VA ER3 MXZ 2D42VA ER3 MXZ 2D53VA ER3 OBH626K ...
Page 30: ...30 MXZ 2D33VA ET2 MXZ 2D42VA ET2 MXZ 2D53VA ET2 OBH626K ...
Page 31: ...31 MXZ 2D33VA ET3 MXZ 2D42VA ET3 MXZ 2D53VA ET3 OBH626K ...
Page 33: ...33 MXZ 2D53VAH E1 OUTDOOR DISPLAY P C BOARD OBH626K ...
Page 34: ...34 MXZ 2D53VAH E2 OBH626K ...
Page 35: ...35 MXZ 2D53VAH E3 OBH626K ...
Page 36: ...36 MXZ 2D53VAH ER2 OBH626K ...
Page 37: ...37 MXZ 2D53VAH ER3 OBH626K ...
Page 39: ...39 MXZ 3D54VA E1 OBH626K ...
Page 40: ...40 MXZ 3D54VA2 E2 OBH626K ...
Page 41: ...41 MXZ 3D54VA2 E3 OBH626K ...
Page 42: ...42 MXZ 3D54VA2 ER2 OBH626K ...
Page 43: ...43 MXZ 3D54VA2 ER3 OBH626K ...
Page 44: ...44 MXZ 3D54VA2 ET2 OBH626K ...
Page 45: ...45 MXZ 3D54VA2 ET3 OBH626K ...
Page 46: ...46 MXZ 3D68VA E1 OBH626K ...
Page 47: ...47 MXZ 3D68VA E2 OBH626K ...
Page 48: ...48 MXZ 3D68VA E3 OBH626K ...
Page 49: ...49 MXZ 3D68VA ER2 OBH626K ...
Page 50: ...50 MXZ 3D68VA ER3 OBH626K ...
Page 51: ...51 MXZ 3D68VA ET2 OBH626K ...
Page 52: ...52 MXZ 3D68VA ET3 OBH626K ...
Page 53: ...53 MXZ 4D72VA E1 OBH626K ...
Page 54: ...54 MXZ 4D72VA E2 OBH626K ...
Page 55: ...55 MXZ 4D72VA E3 OBH626K ...
Page 56: ...56 MXZ 4D72VA ER2 OBH626K ...
Page 57: ...57 MXZ 4D72VA ER3 OBH626K ...
Page 58: ...58 MXZ 4D72VA ET2 OBH626K ...
Page 59: ...59 MXZ 4D72VA ET3 OBH626K ...
Page 60: ...60 MXZ 4D83VA E1 OBH626K ...
Page 61: ...61 MXZ 4D83VA E2 OBH626K ...
Page 62: ...62 MXZ 4D83VA ER1 OBH626K ...
Page 63: ...63 MXZ 4D83VA ER2 OBH626K ...
Page 64: ...64 MXZ 4D83VA ET2 OBH626K ...
Page 65: ...65 MXZ 5D102VA E1 OBH626K ...
Page 66: ...66 MXZ 5D102VA E2 OBH626K ...
Page 67: ...67 MXZ 5D102VA ER1 OBH626K ...
Page 68: ...68 MXZ 5D102VA ER2 OBH626K ...
Page 69: ...69 MXZ 5D102VA ET2 OBH626K ...