133
MXZ-3D/4D/5D
LED1(Red) LED2(Yellow)
Lighted
Twice
Outdoor power system
Lighted
3 times
Discharge temperature
thermistor
• Refer to 11-6. "Check of outdoor thermistors".
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lighted
7 times
Nonvolatile memory data
• Replace the outdoor control P.C. board.
Lighted
8 times
Current sensor
• Replace the power P.C. board.
Lighted
11 times
Communication error
between P.C. boards
• Check the connecting wire between the outdoor control
P.C. board and the power P.C. board.
Lighted
12 times
Zero cross detecting
circuit
• Check the connecting wire between the outdoor control P.C.
board, the noise filter P.C. board and the power P.C. board.
Abnormal point / Condition
Remedy
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 5 minutes (in cooling) and 10
minutes (in heating) after compressor start-up.
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 5 minutes after compressor start-up.
• Replace the outdoor control P.C. board.
Indication
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started, or converter protection
or bus-bar voltage protection cut-out operates 3 consecutive times
within 3 minutes after start-up.
A short circuit is detected in the thermistor during operation, or an open
circuit is detected in the thermistor 10 minutes after compressor start-up.
Condition
The nonvolatile memory data cannot be read properly.
Fin temperature
thermistor
P.C board temperature
thermistor
Lighted
4 times
Ambient temperature
thermistor
Current sensor protection cut-out operates 2 consecutive times.
Communication error occurs twice between the outdoor control
P.C. board and the power P.C. board for more than 10 seconds.
The protection cut-out of the zero cross detecting circuit operates 10
consecutive times.
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
5 times
Lighted
IPM protection
Lock protection
3 times
Not lighted
Discharge temperature
protection
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
8 times
Not lighted
Converter protection
• Replace the power P.C. board.
Bus-bar voltage
protection (1)
• Check the voltage of power supply.
• Replace the power P.C. board or the outdoor
control P.C. board.
• Refer to 11-6. "Check of bus-bar voltage".
Bus-bar voltage
protection (2)
13 times
Not lighted
Outdoor fan motor
• Refer to 11-6. "Check of outdoor fan motor".
Lighted
8 times
Current sensor
protection
• Replace the power P.C. board.
Lighted
11 times
Communication protection
between P.C. boards
• Check the connecting wire between the outdoor
control P.C. board and the power P.C. board.
Lighted
12 times
Zero cross detecting circuit
protection
• Check the connecting wire between the outdoor control P.C.
board, the noise filter P.C. board and the power P.C. board.
• Check the amount of gas and the refrigerant circuit.
• Check the stop valve.
• Check the amount of gas and the refrigerant circuit.
• Refer to 11-6. "Check of LEV".
•Check the refrigerant circuit and the refrigerant amount.
•Refer to 11-6. "Check of outdoor fan motor".
• Reconnect compressor connector.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice
Not lighted
4 times
Not lighted
5 times
Not lighted
6 times
Not lighted
9 times
Not lighted
Overcurrent is detected 30 seconds after compressor start-up.
Overcurrent is detected within 30 seconds after compressor start-up.
The bus-bar voltage falls to 200 V or below during compressor
operating.
The bus-bar voltage exceeds 400 V
(MXZ-3D54/3D68/4D72VA,
MXZ-3D54VA2)
/430 V
(MXZ-4D83/5D102VA)
or falls to 50 V or below
while the compressor is operating.
Discharge temperature exceeds 116°C during operation. Compressor can
restart if discharge temperature thermistor reads 100°C or less 3 minutes
later.
The fin temperature exceeds 89°C during operation.
The P.C. board temperature exceeds 73°C (
MXZ-3D54/3D68/4D72VA,
MXZ-3D54VA2)
/87°C
(MXZ-4D83/5D102VA)
during operation.
High-pressure is detected with the high-pressure switch (HPS) during
operation.
(MXZ-3D68/4D72/4D83/5D102VA)
Pre-heat protection
• Replace the power P.C. board.
A failure is detected in the operation of pre-heat.
(MXZ-3D54/3D68/4D72VA, MXZ-3D54VA2)
Failure occurs 3 consecutive times within 30 seconds after the fan
gets started.
A short or open circuit is detected in the current sensor while the
compressor is operating.
Communication error occurs between the outdoor control P.C.
board and the power P.C. board for more than 10 seconds.
Zero cross signal cannot be detected while the compressor is operating.
The outdoor heat exchanger temperature exceeds 70°C during cooling
or indoor gas pipe temperature exceeds 70°C during heating.
A failure is detected in the operation of the converter during operation.
Outdoor unit
does not
operate.
Lighted
Once
LEV and drain pump
• Check the connection of the compressor connecting
wire.
• Refer to 11-6.
"How to check inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of LEV".
• Check the drain pump of the indoor unit.
The indoor unit detects an abnormality in the LEV and drain pump.
No.
1
2
3
4
5
6
7
9
8
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit
stops and
restarts 3
minutes
later' is
repeated.
OBH626K
Summary of Contents for MXZ-2D33VA
Page 26: ...26 MXZ 2D33VA E2 MXZ 2D42VA E2 MXZ 2D53VA E2 OBH626K ...
Page 27: ...27 MXZ 2D33VA E3 MXZ 2D42VA E3 MXZ 2D53VA E3 OBH626K ...
Page 28: ...28 MXZ 2D33VA ER2 MXZ 2D40VA ER2 MXZ 2D53VA ER2 OBH626K ...
Page 29: ...29 MXZ 2D33VA ER3 MXZ 2D42VA ER3 MXZ 2D53VA ER3 OBH626K ...
Page 30: ...30 MXZ 2D33VA ET2 MXZ 2D42VA ET2 MXZ 2D53VA ET2 OBH626K ...
Page 31: ...31 MXZ 2D33VA ET3 MXZ 2D42VA ET3 MXZ 2D53VA ET3 OBH626K ...
Page 33: ...33 MXZ 2D53VAH E1 OUTDOOR DISPLAY P C BOARD OBH626K ...
Page 34: ...34 MXZ 2D53VAH E2 OBH626K ...
Page 35: ...35 MXZ 2D53VAH E3 OBH626K ...
Page 36: ...36 MXZ 2D53VAH ER2 OBH626K ...
Page 37: ...37 MXZ 2D53VAH ER3 OBH626K ...
Page 39: ...39 MXZ 3D54VA E1 OBH626K ...
Page 40: ...40 MXZ 3D54VA2 E2 OBH626K ...
Page 41: ...41 MXZ 3D54VA2 E3 OBH626K ...
Page 42: ...42 MXZ 3D54VA2 ER2 OBH626K ...
Page 43: ...43 MXZ 3D54VA2 ER3 OBH626K ...
Page 44: ...44 MXZ 3D54VA2 ET2 OBH626K ...
Page 45: ...45 MXZ 3D54VA2 ET3 OBH626K ...
Page 46: ...46 MXZ 3D68VA E1 OBH626K ...
Page 47: ...47 MXZ 3D68VA E2 OBH626K ...
Page 48: ...48 MXZ 3D68VA E3 OBH626K ...
Page 49: ...49 MXZ 3D68VA ER2 OBH626K ...
Page 50: ...50 MXZ 3D68VA ER3 OBH626K ...
Page 51: ...51 MXZ 3D68VA ET2 OBH626K ...
Page 52: ...52 MXZ 3D68VA ET3 OBH626K ...
Page 53: ...53 MXZ 4D72VA E1 OBH626K ...
Page 54: ...54 MXZ 4D72VA E2 OBH626K ...
Page 55: ...55 MXZ 4D72VA E3 OBH626K ...
Page 56: ...56 MXZ 4D72VA ER2 OBH626K ...
Page 57: ...57 MXZ 4D72VA ER3 OBH626K ...
Page 58: ...58 MXZ 4D72VA ET2 OBH626K ...
Page 59: ...59 MXZ 4D72VA ET3 OBH626K ...
Page 60: ...60 MXZ 4D83VA E1 OBH626K ...
Page 61: ...61 MXZ 4D83VA E2 OBH626K ...
Page 62: ...62 MXZ 4D83VA ER1 OBH626K ...
Page 63: ...63 MXZ 4D83VA ER2 OBH626K ...
Page 64: ...64 MXZ 4D83VA ET2 OBH626K ...
Page 65: ...65 MXZ 5D102VA E1 OBH626K ...
Page 66: ...66 MXZ 5D102VA E2 OBH626K ...
Page 67: ...67 MXZ 5D102VA ER1 OBH626K ...
Page 68: ...68 MXZ 5D102VA ER2 OBH626K ...
Page 69: ...69 MXZ 5D102VA ET2 OBH626K ...