background image

4

4. OUTDOOR UNIT INSTALLATION

4-1 INSTALLING THE UNIT

 

 Be sure to 

fi

 x the unit’s legs with bolts when installing it.

 

 Be sure to install the unit 

fi

 rmly to ensure that it does not fall by an earthquake or a gust.

 

 Refer to the 

fi

 gure in the right for concrete foundation.

4-2 MOUNTING ARRANGEMENT OF DRAIN SOCKET

Please perform the drain piping work only when draining from one place.

 CAUTION:

Do not use drain socket and drain cap in the cold region.
Drain may freeze and it makes the fan stop.

1

 Please choose one hole to discharge drain and install the drain socket to the hole.

2

 Please close the rest of the holes with the drain caps.

3

 Please connect a vinyl hose of 25 mm in the inside diameter on the market with the drain socket and lead 

drain.

4-3 INDOOR/OUTDOOR WIRE CONNECTION AND OUTDOOR POWER SUPPLY 

CORD CONNECTION

 

 Be sure to lead in the power supply cord 

A

 to the air conditioner in accordance with the speci

fi

 cation table 

below and “Technical Standards for Electrical Installation”.

 

 Be sure to use special circuits for room air conditioner.

 CAUTION:

Attach an earth leakage breaker according to your installation location. If any breaker is not attached, 
it may cause a risk of electric shock.

 WARNING:

Be sure to comply with “Technical Standards for Electrical Installation”, follow this manual and use
special circuits for electrical work. If there is a lack of circuit capacity or some de

fi

 ciency in installation, 

it may cause a risk of 

fi

 re or electric shock.

Overcurrent that might be produced may include DC substances. Be careful to choose the correct type 
of overcurrent protection switch.

Rated Voltage

Breaker capacity

Connect to the supply terminals and leave a contact separation of 
at least 3 mm at each pole to disconnect the source power pole. 
(When the power switch is shut off, it must disconnect all poles.)

230 V

15A

 

Peel off both ends of the cables as shown in the right.

 

Take care not to let the cables contact the pipes inside the unit.

  

Take enough care to connect the indoor/outdoor unit connecting wire correctly between 
the respective indoor units and the outdoor unit.

 

Make earth wire a little longer than the others. (more than 35 mm)

35 mm

15 mm

}

}

POWER SUPPLY

L

L

~/N 230 V 50 Hz

UNIT

UNIT

 

 For the power supply cord and the indoor/outdoor unit connecting wires, be sure to use the ones in compli-

ance with the standards.

 

  Be sure to push the core until it is hidden and pull each cable to make sure that it is not pulled up. Incomplete 

insertion may cause a risk of burning the terminal blocks.

Power supply cord Speci

fi

 cation

Cable 3-core 2.5 mm

2

, in conformity with Design 245 IEC 57.

Indoor and Outdoor connecting wire Speci

fi

 cation

Cable 4-core 1.0/1.5 mm

2

, in conformity with Design 245 IEC 57.

This installation manual is only for the outdoor unit installation. In installing the indoor units, refer to the 
installation manual attached to each indoor unit.

Indoor/outdoor unit connecting wire

<OUTDOOR UNIT>

1

 Remove the service panel.

2

 Connect the indoor/outdoor wire and power supply cable to the terminal block.

Firmly tighten the indoor/outdoor unit connecting 
wire 

B

 and the power supply cord 

A

.

Route the indoor/outdoor unit connecting wire 

B

 and the power supply cord 

A

 along with the 

unit.

Cable clamp

Power supply cord 

A

Be sure that the indoor/outdoor unit 
connecting wire 

B

 does not contact 

the stop valve.

B

 unit

A

 unit

 WARNING:

  Be sure to attach the service panel of the outdoor unit securely, otherwise it may result in a 

fi

 re or an 

electric shock from dust or water.

  Use the indoor/outdoor unit connecting wire that meets the Standards to connect the indoor and 

outdoor units and 

fi

 x the wire to the terminal block securely so that no external force is conveyed to 

the connecting section of the terminal block. Incomplete connection or 

fi

 xing of the wire could result 

in a 

fi

 re.

  Be sure to attach the terminal block cover on the both indoor and outdoor units. If the terminal block 

cover is incorrectly attached, it may cause a risk of 

fi

 re or electric shock due to dust or water pen-

etration.

SG79Y644H01.indd   4

SG79Y644H01.indd   4

29.11.2005   17:04:12 Uhr

29.11.2005   17:04:12 Uhr

Summary of Contents for MXZ-2A52VA

Page 1: ...LLATION DIAGRAM ACCESSORIES 2 3 SELECTING THE INSTALLATION LOCATION 3 4 OUTDOOR UNIT INSTALLATION 4 5 INDOOR OUTDOOR UNITS CONNECTION FINISHING AND TEST RUN 5 IMPORTANT NOTES TO COMPLY WITH THE REQUIREMENTS OF AUSTRALIAN STANDARD AS 3000 S A A WIRING RULES THE ELECTRICAL WIRING REQUIRED BETWEEN THE INDOOR AND OUTDOOR UNITS MUST BE INSTALLED BY A LICENCED ELECTRICAL CONTRACTOR SG79Y644H01 indd 1 SG...

Page 2: ...tdoor unit are not attached se curely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or specified parts for the installation work The use of defective parts could cause an injury due to a fire an electric shock the unit falling leakage of water etc Be sure to cut off the main power in case of set ting up the indoor electronic control P C board...

Page 3: ...upport is available to prevent the increase of operation sound or vibration Where there is no risk of combustible gas leakage When installing the unit at a high level be sure to fix the unit legs Where it is at least 3 m away from the antenna of TV set or radio Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required fo...

Page 4: ...t Take enough care to connect the indoor outdoor unit connecting wire correctly between the respective indoor units and the outdoor unit Make earth wire a little longer than the others more than 35 mm 35 mm 15 mm POWER SUPPLY LY L N 230 V 50 Hz UNIT UNIT For the power supply cord and the indoor outdoor unit connecting wires be sure to use the ones in compli ance with the standards Be sure to push ...

Page 5: ...A52VA Outdoor unit Indoor unit UNIT Indoor unit UNIT PIPING PREPARATION 1 If you use commercially available copper pipes use the following table for pipe specifications Outside diameter Wall thickness Liquid pipe ø6 35 mm 0 8 mm Gas pipe ø9 52 mm 0 8 mm 2 For insulation material use 8 mm thick heat insulating expended polyethylene with a specific gravity of 0 045 3 Ensure that the 2 refrigerant pi...

Page 6: ...n for prevention of condensation A Die Copper pipe Flare nut Die Copper pipe Smooth all around Even length all around Inside is shining without any scratches Y ork Flaring tool Wing nut type Clutch type 5 4 PURGING PROCEDURES LEAK TEST Perform the manifold valve work securely according to the installation manual of the manifold valve PURGING PROCEDURES Connect the refrigerant pipes both liquid pip...

Page 7: ... can lower the operating noise of the outdoor unit when the operation load is small for example during nighttime in COOL mode However please note that the cooling and heating capacity can also be lowered if this function is acti vated Initial setting is required to activate this function Please explain about this function to your custom ers and ask them whether they want to use it How to lower the...

Page 8: ... cannot detect any erroneous connection if any of the refrigerant pipes and the indoor outdoor unit connecting wires About the restart protective mechanism Once the compressor stops the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner 5 11 EXPLANATION TO THE CUSTOMER Recommend the customer to read the OPERATING INSTRUCTIONS carefull...

Page 9: ......

Page 10: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SG79Y644H01 SG79Y644H01 indd 9 SG79Y644H01 indd 9 29 11 2005 17 04 16 Uhr 29 11 2005 17 04 16 Uhr ...

Reviews: