147
OPERATING PROCEDURE
PHOTOS
Photo 5
Defrost
thermistor
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel
(Refer to 1).
(2) Disconnect the power supply and indoor/outdoor
connecting
wire.
(3) Disconnect the connectors for outdoor fan motor.
(4) Remove the propeller nut.
(5) Remove the propeller.
(6) Remove the screws fixing the fan motor (Photo 6).
(7) Remove the fan motor.
Photo 7
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel
(Refer to 1).
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel (Refer to 1).
(3) Remove the inverter assembly (Refer to 2).
(4) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
2
(0 MPa).
(5) Detach the welded part of the suction and the discharge pipe
connected with compressor.
(6) Remove the nuts of compressor legs.
(7) Remove the compressor.
(8) Detach the welded part of pipes connected with 4-way valve
(Photo
7).
Photo 6
Screws of the outdoor fan motor
Outdoor heat
exchanger
temperature
thermistor
Propeller
Welded parts of 4-way valve
Propeller nut
Summary of Contents for MXZ-2A30VA
Page 79: ...79 MXZ 3A54VA E7 ...
Page 83: ...83 MXZ 4A71VA E7 ...