62
Outdoor model
Indoor units number
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity [Rated (Min.-Max.) Hz]
Dehumidification
Outdoor air flow
Breaker capacity
Running current
Power input
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at 20 °C)
Model
Winding
resistance(at 20 °C)
Dimensions W x H x D
Weight
Sound level (High/Low)
Fan speed (High/Low)
Fan speed regulator
Refrigerant filling
capacity(R410A)
Refrigeration oil (Model)
m
m
m
m
kW
/h
m
3
/h
A
A
W
%
A
A
A
W
Ω
Ω
mm
kg
dB
rpm
kg
cc
Compressor
2 Electrical
data
Fan
motor
Special
remarks
Capacity
System
Coefficient of performance(C.O.P) 2
MXZ-2A40VA -
Single phase
230 V, 50 Hz
2
Max. 30
Max. 20
Refer to 9
Refer to 9
15
95
4.78
0.2
SNB130FKCH
1,100
U-V 0.64
V-W 0.64 W-U 0.64
RC0J50-CF
BLK-WHT 14.2
WHT-RED 14.2 RED-BLK 14.2
800 x 550 x 285
40
2
1.3
450 (NEO22)
Heating
4.5 (1.0 - 5.0)
—
1,860
4.32
945
4.12
4.76
48/47
850/490
MXZ-2A40VA -
Single phase
230 V, 50 Hz
2
Max. 30
Max. 20
Refer to 9
Refer to 9
15
95
4.78
0.2
KNB092FEDH
1,100
U-V 1.70
V-W 1.70 W-U 1.70
RC0J50-CF
BLK-WHT 14.2
WHT-RED 14.2 RED-BLK 14.2
800 x 550 x 285
34
2
1.15
320 (NEO22)
Cooling
4.0 (1.1 - 4.5)
—
1,950
4.78
1,045
4.58
3.83
47/44
850/650
Heating
4.5 (1.0 - 5.0)
—
1,950
4.32
945
4.12
4.76
48/47
850/650
Cooling
4.0 (1.1 - 4.5)
—
1,860
4.78
1,045
4.58
3.83
47/44
850/530
E1
E2
Outdoor unit power supply
TEST CONDITIONS COOLING INDOOR
Dry-bulb temperature 27.0°C Wet-bulb temperature 19.0°C
OUTDOOR Dry-bulb temperature 35.0°C Wet-bulb temperature 24.0°C
HEATING INDOOR
Dry-bulb temperature 20.0°C
OUTDOOR Dry-bulb temperature 7.0°C Wet-bulb temperature 6.0°C
NOTE: •Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
•Refer to 3 “INDOOR/OUTDOOR CORRESPONDENCE TABLE” for the combination.
1 Measured under rated operating frequency.
2 Electrical data is for only outdoor unit.
3 These specifications are when all indoor units are operating.
Summary of Contents for MXZ-2A30VA