MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-HM09NA(H)
MUZ-HM09NA2
MUZ-HM12NA(H)
MUZ-HM12NA2
65
40
3/8
1/4
MUZ-HM15NA(H)
MUZ-HM15NA2
MUZ-HM18NA(H)
MUZ-HM18NA2
1/2
MUZ-HM24NA(H)
MUZ-HM24NA2
100
50
5/8
3/8
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
65
MUZ-HM09NA(H)
MUZ-HM09NA2
MUZ-HM12NA
-
U1
,
U2
MUZ-HM12NAH
-
U1
MUZ-HM12NA2
-
U1
1 lb. 12 oz.
0
1.08
3.24
5.40
7.56
8.64
MUZ-HM12NA
-
U8
MUZ-HM12NA2
-
U8
MUZ-HM15NA(H)
MUZ-HM15NA2
2 lb. 9 oz.
MUZ-HM18NA(H)
MUZ-HM18NA2
2 lb. 10 oz.
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
70
80
90
100
MUZ-HM24NA(H)
MUZ-HM24NA2
3 lb. 9 oz.
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)