30
11-4. TROUBLE CRITERION OF MAIN PARTS
MUZ-HJ25VA MUZ-HJ35VA MUZ-HJ50VA
Part name
Check method and criterion
Figure
Defrost thermistor
(RT61)
Measure the resistance with a tester.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Discharge temperature
thermistor (RT62)
Fin temperature thermistor
(RT64)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C.
board”, for the chart of thermistor.
Compressor (MC)
Measure the resistance between the terminals with a tester.
(Part temperature -10 ~ 40°C)
Normal
U-V
U-W
V-W
MUZ-HJ25VA
MUZ-HJ35VA
MUZ-HJ50VA
2.01 ~ 2.86
Ω
1.20 ~ 1.72
Ω
0.78 ~ 1.11
Ω
MUZ-HJ25VA
MUZ-HJ35VA
Outdoor fan motor (MF)
INNER FUSE
RA6V21-AB
152
+0
-5
°C CUT OFF
RA6V21-BB
126 ± 2: CUT OFF
Measure the resistance between the terminals with a tester.
(Part temperature -10 ~ 40°C)
MUZ-HJ25VA MUZ-HJ35VA
Color of lead wire
Normal
RA6V21-AB
RA6V21-BB, BD
WHT – BLK
305 ~ 374
Ω
222 ~ 272
Ω
BLK – RED
247 ~ 304
Ω
245 ~ 300
Ω
MUZ-HJ50VA
Outdoor fan motor (MF)
MUZ-HJ50VA
Color of lead wire
Normal
RED – BLK
BLK – WHT
WHT – RED
30 ~ 43
Ω
R.V. coil (21S4)
Measure the resistance between the terminals with a tester.
(Part temperature -10
˚
C ~ 40°C)
Normal
MUZ-HJ25VA/35VA
MUZ-HJ50VA
1.19 ~ 1.78 k
Ω
1.41 ~ 2.00 k
Ω
MUZ-HJ25VA
MUZ-HJ50VA
Expansion valve coil (LEV)
Measure the resistance using a tester.
(Temperature: -10 ~ 40°C)
Color of lead wire
Normal (
Ω
)
RED – ORN
37 ~ 54
RED – WHT
RED – BLU
RED – YLW
MUZ-HJ35VA
Expansion valve coil (LEV)
Measure the resistance using a tester.
(Part temperature: -10 ~ 40°C)
Color of lead wire
Normal
WHT – RED
37 ~ 54
Ω
RED – ORN
YLW – BRN
BRN – BLU
WHT
RED
BLK
FUSE
2
3
W
U
V
1
WHT
RED BLK
LEV
WHT
RED
ORN
YL
W
BRN
BLU
RED
(+12V)
YLW
BLU
WHT
ORN
LEV
W
U
V
WHT
RED BLK
OBH648A