MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-HJ25VA
MUZ-HJ35VA
20
12
9.52
6.35
MUZ-HJ50VA
12.7
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
5 m
6 m
7 m
8 m
9 m
10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-HJ25VA
MUZ-HJ35VA
MUZ-HJ50VA
700
0
0
0
20
40
60
80
100
120
140
160
260
720
1,150
Calculation: X g = 20 g/m (Refrigerant piping length (m) - 7)
NOTE :
Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH648A