39
Press OFF/ON (stop/operate) button of the remote con-
troller (the set temperature is displayed) with the remote
controller headed towards the indoor unit.
*
1
Expansion valve operates in full-opening direction.
OK
NOTE
: After check of LEV, take the following steps.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
*
1. Regardless of normal or abnormal condition, a short beep is
emitted once the signal is received.
Measure each voltage between connector
pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+)
Is there about 3 - 5 VAC between each?
NOTE:
Measure the voltage by an analog
tester.
Properly fix the LEV coil to the expansion valve.
Replace the inverter P.C.
board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fixed to
the expansion valve?
Does the resistance of LEV
coil have the characteristics?
(Refer to 10-4.)
Do you hear the expansion valve "click,
click·······"?
Do you feel the expansion valve vibrate
when touching it ?
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both Operation select button and
TEMP button on the remote controller at the same
time, press RESET button.
First, release RESET button.
Hold down the other 2 buttons for another 3 seconds.
Make sure that the indicators on the LCD screen
shown in the right figure are all displayed. Then re
-
lease the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
OBH873