38
J Check of power supply
Is there voltage 208/230 VAC
between the indoor terminal
block S1 and S2?
No
Yes
Replace the indoor
electronic control P.C.
board.
Rectify indoor/outdoor
connecting wire.
Yes
If lights up, OK.
If blinks, refer to 10-3.
Does the left lamp of the
OPERATION INDICATOR lamp on
the indoor unit light up?
Does LED on the inverter P.C.
board light up or blink?
(Refer to 10-6.1.)
No
Replace the inverter
P.C. board.
Is there bus-bar voltage 260 - 370
VDC between DB61 (+) and DB61 (–)
(
MUZ-FS06/09/12
)/294 - 370 VDC
between IC700 (P) and (N)
(
MUZ-FS15/18
) on the inverter P.C.
board? (Refer to 10-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the
compressor and the power module
(IC700).
Turn ON power supply and press
EMERGENCY OPERATION switch.
Inverter P.C. board
(Solder side)
DB61
260 - 370 VDC
MUZ-FS06/09/12
MUZ-FS15/18
IC700
N
P
Inverter P.C board
(Solder side)
IC932
294 -370 V DC
OBH873