11-5. Trouble criterion of main parts
Part name
Figure
Check method and criterion
Outdoor fan motor(MF)
R.V. coil(21S4)
LEV(Expansion valve coil)
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
WHT – BLK
BLK – RED
RED – WHT
Abnormal
Open or
short-circuit
Normal
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Normal
1.20 k
"
~ 1.55 k
"
Abnormal
Open or short-circuit
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
Abnormal
Open or
short-circuit
Normal
38
"
~ 50
"
Measure the resistance with a tester.
(Part temperature : –20˚C ~ 40˚C)
Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C)
Color of the lead wire
Color of the lead wire
Discharge temperature
thermistor(RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
Normal
150 k
"
~ 600 k
"
30 k
"
~ 180 k
"
Abnormal
Open or short-circuit
Normal
5 k
"
~ 55 k
"
Abnormal
Open or short-circuit
Defrost thermistor
(RT61)
Fin temperature
thermistor(RT64)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
Normal
Abnormal
Open or short-circuit
Ambient temperature
thermistor(RT65)
31
"
~ 41
"
31
"
~ 41
"
31
"
~ 41
"
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Compressor(MC)
Defrost heater(H)
Measure the resistance with a tester.
(Part temperature -20˚C ~ 40˚C)
Normal
333
"
~ 428
"
Abnormal
Open or short-circuit
U-V
U-W
V-W
Abnormal
Open or
short-circuit
Normal
MUZ-FA35VA
MUZ-FA35VAH
0.41
"
~ 0.53
"
MUZ-FA25VA
MUZ-FA25VAH
1.28
"
~ 1.66
"
2
3
W
U
V
1
WHT
RED BLK
2
3
W
U
V
1
WHT
RED BLK
LEV
WHT
6
RED
1
ORN
4
YL
W
5
BRN
2
BLU
3
MUZ-FA25VA -
MUZ-FA35VA -
MUZ-FA25VAH -
MUZ-FA35VAH -
E1
E1
E1
E1