ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
precharged
900
1,050
14m
270
270
7m
0
0
6m
0
0
5m
0
0
11m
180
180
Model
Refrigerant piping length (one way)
Calculation : Xg=30g/m
o
(Refrigerant piping length(m) - 5)
8m
90
90
9m
120
120
10m
150
150
12m
210
210
13m
240
240
15m
300
300
20m
450
450
MUZ-FA25VA -
E1
MUZ-FA25VAH -
E1
MUZ-FA35VA -
E1
MUZ-FA35VAH -
E1
12
Refrigerant Piping
Max. length
A
w
Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
w
Max. Height
difference 12m
Indoor
unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Max. length : m
A
20
Indoor unit
Gas 0.43
Liquid 0.5
Gas
9.52
Liquid
6.35
Outdoor unit
Piping size O.D : mm
Length of connecting pipe : m
Model
MUZ-FA25VA -
E1
MUZ-FA25VAH -
E1
MUZ-FA35VA -
E1
MUZ-FA35VAH -
E1