21
ACTUATOR CONTROL
9
MUZ-A09YV -
MUZ-A12YV -
MUZ-A09YVH -
MUZ-A12YVH -
E1
E1
E1
E1
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Purpose
Protection
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting
Protection
Cooling : Low ambient temperature operation
Heating : Defrosting (Heater)
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
R.V.coil
Sensor
Actuator
9-3. Relation between main sensor and actuator
9-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling. . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. Outdoor fan motor control
The AC fan motor turns ON/OFF, interlocking with the compressor.
[ON] The AC fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The AC fan motor turns OFF 15 seconds after the compressor has stopped running.
OB328 A--1qxp 04.4.26 4:49 PM Page 21