25
10-3. TROUBLESHOOTING CHECK TABLE
No.
Symptom
LED indication
Abnormal point/
Condition
Condition
Remedy
1
Outdoor unit
does not op-
erate.
1-time blink every
2.5 seconds
Outdoor power sys-
tem
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
• Reconnect connector of compres-
sor.
• Refer to 10-5. "How to check
inverter/compressor".
• Check stop valve.
2
Outdoor thermistors
Discharge temperature thermistor, fin temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor
heat exchanger temperature thermistor or ambient tempera-
ture thermistor shorts or opens during compressor running.
• Refer to 10-5. "Check of outdoor
thermistors".
3
Outdoor control sys-
tem
Nonvolatile memory data cannot be read properly.
(The left lamp of the OPERATION INDICATOR lamp on the
indoor unit lights up or blinks 7-time.)
• Replace inverter P.C. board.
4
6-time blink
2.5 seconds OFF
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
• Refer to 10-5. "How to check
miswiring and serial signal error.
5
11-time blink
2.5 seconds OFF
Stop valve/
Closed valve
Closed valve is detected by compressor current.
• Check stop valve.
6
16-time blink
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly.
The indoor coil thermistor detects an abnormal temperature.
• Refer to 10-5. "Check of R.V.
coil".
• Replace the inverter P.C. board.
7
17-time blink
2.5 seconds OFF
Outdoor refrigerant
system abnormality
A closed valve and air trapped in the refrigerant circuit are
detected based on the temperature sensed by the indoor and
outdoor thermistors and the current of the compressor.
• Check for a gas leak in a
connecting piping etc.
• Check the stop valve.
• Refer to 10-5. “Check of outdoor
refrigerant circuit”.
8
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated.
2-time blink
2.5 seconds OFF
Overcurrent protec-
tion
Large current flows into the power module (IC700).
• Reconnect connector of compressor.
• Refer to 10-5. "How to check
inverter/compressor".
• Check stop valve.
9
3-time blink
2.5 seconds OFF
Discharge tem-
perature overheat
protection
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart if
discharge temperature thermistor reads 212°F (100°C) or less
3 minutes later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 10-5. "Check of LEV".
10
4-time blink
2.5 seconds OFF
Fin temperature
/P.C. board tem-
perature thermistor
overheat protection
Temperature of the fin temperature thermistor on the heat sink
exceeds 167 - 176°F (75 - 80°C) or temperature of P.C. board
temperature thermistor on the inverter P.C.board exceeds 158
- 167°F (70 - 75°C).
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 10-5. "Check of outdoor
fan motor".
11
5-time blink
2.5 seconds OFF
High pressure pro-
tection
Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.
Defrost thermistor exceeds 158°F (70°C) in COOL mode.
• Check refrigerant circuit and refrig-
erant amount.
• Check stop valve.
12
8-time blink
2.5 seconds OFF
Compressor syn-
chronous abnormal-
ity
The waveform of compressor current is distorted.
• Reconnect connector of compressor.
• Refer to 10-5. "How to check
inverter/compressor".
13
10-time blink
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
• Refer to 10-5. "Check of outdoor
fan motor.
• Refer to 10-5. "Check of inverter
P.C. board.
14
12-time blink
2.5 seconds OFF
Each phase current
of compressor
Each phase current of compressor cannot be detected nor-
mally.
• Refer to 10-5. "How to check
inverter/compressor".
15
13-time blink
2.5 seconds OFF
Bus-bar voltage
(DC)
Bus-bar voltage of inverter cannot be detected normally.
• It occurs with following case.
Instantaneous power voltage drop.
(Short time power failure)
• Refer to 10-5. "Check of power
supply".
• Refer to 10-5. "How to check in-
verter/compressor".
NOTE:
1. The location of LED is illustrated at the right figure. Refer to 10-6.1.
2. LED is lit during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
Inverter P.C. board
MUZ-GS30/36NA(H)
MUY-GS30/36NA
LED
→
Blinking
OBH875