9
MUH-GE50VB
MU-GE50VB
11.6
10.6
9.6
8.6
7.7
6.9
Outdoor intake air Dry-bulb temperature
Indoor air W
e
t-bulb temperature
dif
ference(degree)
Indoor intake air W
et-bulb temperature
Outdoor intake air Dry-bulb temperature
Indoor intake air
Wet-b
ulb temperatur
e
MUH-GE50VB
26.6
24.5
22.5
20.4
18.4
16.3
14.3
12.3
Outdoor intake air Wet-bulb temperature
Indoor air Dry-bulb temperature
dif
ference(degree)
Ind
oor intake air Dry-bu
lb temperature
Indoor
intake air Dry-bulb temperature
Outdoor intake air Wet-bulb temperature
NOTE: The above curves are for the heating operation without any frost.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL
[HEAT (
MUH-GE50VB
)]
MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
Wet and dry-bulb
thermometers
Wet and dry-bulb
thermometers
8-1. CAPACITY AND THE INPUT CURVES