29
3. Table of outdoor unit failure mode recall function
MUZ-WR09NA MUZ-WR12NA
OPERATION
INDICATOR
upper lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/
outdoor unit
failure mode
recall function
Outdoor unit
failure mode
recall function
OFF None
(Normal)
—
—
—
—
—
2-time blink
2.5 seconds
OFF
Outdoor power system
—
Overcurrent protection cut-out operates
3 consecutive times within 1 minute
after the compressor gets started.
• Reconnect connectors.
• Refer to 10-5. "How
to check inverter/
compressor".
• Check the stop valve.
○
○
3-time blink
2.5 seconds
OFF
Discharge temperature
thermistor
1-time blink every
2.5 seconds
Thermistor shorts or opens during
compressor running.
• Refer to 10-5. "Check
of outdoor thermistors".
Defective outdoor
thermistors can be
identi
fi
ed by checking
the blinking pattern of
LED.
○
○
Defrost thermistor
Fin temperature thermistor
3-time blink
2.5 seconds OFF
P.C. board temperature
thermistor
4-time blink
2.5 seconds OFF
Ambient temperature
thermistor
2-time blink
2.5 seconds OFF
4-time blink
2.5 seconds
OFF
Overcurrent 11-time
blink
2.5 seconds OFF
Large current
fl
ows into intelligent
power module/ power module 1.
• Reconnect compressor
connector.
• Refer to 10-5. "How
to check inverter/
compressor".
• Check the stop valve.
—
○
Compressor synchronous
abnormality (Compressor start-
up failure protection)
12-time blink
2.5 seconds OFF
Waveform of compressor current is
distorted.
• Reconnect compressor
connector.
• Refer to 10-5. "How
to check inverter/
compressor".
—
○
5-time blink
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads 212°F
(100°C) or less 3 minutes later.
• Check the refrigerant
circuit and the
refrigerant amount.
• Refer to 10-5. "Check
of LEV".
—
○
6-time blink
2.5 seconds
OFF
High pressure
—
Temperature of indoor coil thermistor
exceeds 158°F (70°C) in HEAT mode.
Temperature of outdoor heat exchanger
temperature thermistor exceeds 158°F
(70°C) in COOL mode.
• Check the refrigerant
circuit and the
refrigerant amount.
• Check the stop valve.
—
○
7-time blink
2.5 seconds
OFF
Fin temperature/ P.C. board
temperature
7-time blink
2.5 seconds OFF
Temperature of
fi
n temperature
thermistor on the inverter P.C. board
exceeds 167 - 176°F (75 - 80°C), or
temperature of P.C. board temperature
thermistor on the inverter P.C. board
exceeds 158 - 167°F (70 - 75°C).
• Check around the
outdoor unit.
• Check the outdoor unit
air passage.
• Refer to 10-5. "Check
of outdoor fan motor".
—
○
8-time blink
2.5 seconds
OFF
Outdoor fan motor
—
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor fan
start-up.
• Refer to 10-5. "Check
of outdoor fan motor".
Refer to 10-5. "Check
of inverter P.C. board".
—
○
9-time blink
2.5 seconds
OFF
Nonvolatile memory data
5-time blink
2.5 seconds OFF
Nonvolatile memory data cannot be
read properly.
• Replace the inverter
P.C. board.
○
○
10-time blink
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor has been 122°F (50°C) or
less for 20 minutes.
• Refer to 10-5. "Check
of LEV".
• Check the refrigerant
circuit and the
refrigerant amount.
—
○
NOTE:
Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
OBH819A