37
Part name
Check method and criterion
Figure
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12, RT13)
Measure the resistance with a tester.
Refer to 10-7. "Test point diagram and voltage", "Indoor electronic control
P.C. board", for the chart of thermistor.
Indoor fan motor (MF)
Check 10-6. "Check of indoor fan motor".
Vane motor (MV1)
(HORIZONTAL)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - YLW
262 - 328 Ω
YLW
YLW
RED
YLW YLW
ROTOR
Vane motor (MV2)
(VERTICAL)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - YLW
219 - 273 Ω
YLW
YLW
RED
YLW YLW
ROTOR
i-see SENSOR MOTOR
(MT)
Measure the resistance between the terminals with a tester.
(Temperature: 10 - 30°C)
Color of the lead wire
Normal
RED - BRN
262 - 328 Ω
BRN
BRN
RED
BRN BRN
ROTOR
AIR PURIFYING power
Check 10-6. .
OPERATION INDICATOR
(POWER)
(AIR PURIFYING)
No. Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
MXZ type
Operation
mode
setting
• AIR PURIFYING lamp blinks.
2.5-second OFF
• POWER lamp is lit.
Outdoor unit
operates but
indoor unit does
not operate.
The operation mode of the each indoor unit is
differently set to COOL (includes DRY, FAN)
and HEAT at the same time, the operation
mode of the indoor unit that has operated at
first has the priority.
• Unify the operation mode.
Refer to outdoor unit service
manual.
OPERATION INDICATOR
(POWER)
(AIR PURIFYING)
No. Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
AIR
PURIFYING
power
control
AIR PURIFYING lamp blinks.
2.5-second OFF
Indoor unit and
outdoor unit do
not operate.
When AIR PURIFYING power cannot be
turned OFF even if the AIR PURIFYING
operation is turned OFF by remote controller.
• Refer to 10-6. "Check of AIR
PURIFYING power".
Lit
Blinking
Not lit
Lit
Blinking
Not lit
10-5. TROUBLESHOOTING CRITERION OF MAIN PARTS
MSZ-RW25VG
MSZ-RW35VG
MSZ-RW50VG
OBH902A