10-3. INSTRUCTION OF TROUBLESHOOTING
Indoor unit operates.
Outdoor unit does
not operate.
If blinking of OPERATION
INDICATOR lamp cannot be
checked, it can be checked
with failure mode recall
function.
Indoor unit operates.
Outdoor unit does
not operate normally.
Indoor unit does
not receive
the signal from
remote controller.
OPERATION INDICATOR
lamp on indoor unit is
blinking ON and OFF.
Outdoor unit
operates only
in Test Run
operation.
Outdoor unit
does not
operate even
in Test Run
operation.
Unit does not
operate nor-
mal operation
in COOL or
HEAT mode.
Indoor unit does
not operate, when
EMERGENCY
OPERATION
switch is pressed.
Indoor unit
operates, when
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to 10-
7. "Test point
diagram and
voltage".
Refer to "How
to check
inverter/com-
pressor".
Refer to
"Check of R.V.
coil".
Refer to 10-6.
"Check of remote
controller and
indoor electronic
control P.C. board".
1. Check indoor/outdoor connect-
ing wire.
2. Check if the power is supplied to
indoor unit.
•
If power supply voltage is detected,
refer to 10-6. "Check of indoor
P.C. board and indoor fan motor".
•
If power supply voltage is not
detected, refer to outdoor unit
service manual.
Left/Upper
lamp*1 blink
on and off at
0.5-second
intervals
Cause:
Indoor/Outdoor
unit
• Miswiring or
trouble of serial
signal
Left/Upper
lamp *1
2-time blink
Cause:
Indoor unit
• Trouble
of room
temperature
/ indoor coil
thermistor
Left/Upper
lamp *1
3-time blink
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Left/Upper
lamp *1
4-time blink
Cause:
Indoor unit
• Trouble
of indoor
unit control
system
Left/Upper
lamp *1
5-time blink
Cause:
Outdoor unit
• Outdoor
power sys-
tem abnor-
mality
Left/Upper
lamp *1
6-time blink
Cause:
Outdoor unit
• Trouble of
thermistor in
outdoor unit
Left/Upper
lamp *1
7-time blink
Cause:
Outdoor unit
• Trouble
of outdoor
control
system
Left/Upper
lamp *1
14-time blink
or more
Cause:
Outdoor unit
• Other ab-
normality
Start
Refer to 10-
6. "How to
check mis-
wiring and
serial signal
error".
Check room
temperature
thermistor
and indoor
coil thermis-
tor. Refer to
10-7."Test
point diagram
and voltage".
Refer to 10-
6. "Check
of indoor fan
motor".
Replace the
indoor elec-
tronic control
P.C. board.
Refer to
"How to
check
inverter/com-
pressor".
Refer to
"Check of
outdoor ther-
mistors".
Replace the
inverter P.C.
board or
the outdoor
electronic
control P.C.
board.
Check "Flow
chart of the
detailed
outdoor unit
failure mode
recall func-
tion."
"Test Run operation"
means the operation
within 30 minutes after
EMERGENCY OPERA-
TION switch is pressed.
Refer to outdoor unit
service manual.
*1 Left lamp:
HR25/35/42/50VF
Upper lamp:
HR60/71VF