5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system following 
the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas 

pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely 

so that it can be easily closed fully when the pressure gauge shows 0 psi [Gauge] 
(0 Mpa).

4) Start the emergency COOL operation.
  To start the emergency operation in COOL mode, disconnect the power supply 

plug and/or turn off the breaker. After 15 seconds, connect the power supply plug 
and/or turn on the breaker, and then press the E.O. SW once. (The emergency 
COOL operation can be performed continuously for up to 30 minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure 

gauge shows (0.1 to 0 psi [Gauge] (0.05 to 0 Mpa)).

6) Stop the emergency COOL operation.
  To stop operation, press the E.O. SW several times until all LED lamps turn off. 

Refer to operating instructions for details.

5.  RELOCATION AND MAINTENANCE

5-1. REMOVING AND INSTALLING THE PANEL  

 

ASSEMBLY

Removal procedure

1) Remove the two screws that attach the panel assembly.
2) Remove the panel assembly. Be sure to remove its bottom end first.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the installation plate.
When releasing the corner part, release both left and right bottom corner part of 
indoor unit and pull it downward and forward as shown in the figure on the right.

Push

Lower

Square hole

Installation procedure

1) Install the panel assembly following the removal procedure in reverse. 
2) Be sure to press the positions as indicated by the arrows in order to attach the 

assembly completely to the unit.

If the above method cannot be used

Remove the panel. Then, insert hexagonal wrenches into the square holes on the 
left and right sides of the unit and push them up as shown in the following figure. 
The bottom of the indoor unit lowers and releases the hooks.

When pumping down the refrigerant, stop the compressor before discon-
necting the refrigerant pipes. The compressor may burst if air etc. get into it.

 WARNING

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, 
TOKYO 100-8310, JAPAN

Summary of Contents for MSZ-HE09NA

Page 1: ...s dust blockage or loose parts on the power supply plug or the outlet it could cause electric shock or fire If loose parts are found on the power supply plug replace it N Securely attach the electrical cover to the indoor unit and the service panel to the outdoor unit If the electrical cover of the indoor unit and or the service panel of the outdoor unit are not attached securely dust water etc cou...

Page 2: ...nlight Do not ex pose to direct sunlight also during the period following unpacking to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with radio or TV reception An amplifier may be re quired for the affected device In a place as far away as possible from fluorescent and incandescent lights so the infr...

Page 3: ...g piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refrigerant Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 3 ft 1 m away from the TV antenna wire 4 in 100 mm or more 14 in 350 mm or more 8 in 200 mm 3 or more 2 4 in 100 mm or more when front and sides of unit are...

Page 4: ...end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are tightly fas tened 9 Reinstall conduit plate condu...

Page 5: ...the section to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall...

Page 6: ...fective cut off the section and repeat procedure Conduit cover Lead wire 3 OUTDOOR UNIT INSTALLATION Power supply cord K Indoor outdoor unit connecting wire A Make earth wire a little longer than oth ers More than 2 3 8 in 60 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its cor respondent terminal when securing the cord and or the wire to the ter...

Page 7: ...r turn on the breaker 2 Press the E O SW once Test run will be performed for 30 minutes If the power lamp blinks every 0 5 seconds inspect the indoor outdoor unit connecting wire A After the test run emergency COOL mode 75ºF 24ºC COOL will start 3 To stop operation press the E O SW several times until all LED lamps turn off Refer to operating instructions for details Checking the remote infrared s...

Page 8: ...veral times until all LED lamps turn off Refer to operating instructions for details 5 RELOCATION AND MAINTENANCE 5 1 REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1 Remove the two screws that attach the panel assembly 2 Remove the panel assembly Be sure to remove its bottom end first 5 2 REMOVING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When r...

Reviews: