background image

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor
and the outdoor unit.

Remove the service port cap of the stop valve on the side of the outdoor unit gas
pipe. (The stop valve will not work in it initial state fresh out of the factory (totally
closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the
stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold
valve, and stop the vacuum pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve
remains in the same position. Confirm that the pressure gauge shows–0.101 Mpa
[Gauge] (–760 mmHg).

Pipe length exceeding 7 m

Charge the prescribed amount

of gas. (refer to 3)

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on
both sides of gas pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

*Close

*Open

Hexagonal wrench

Stop valve

*4 to 5 turns

Stop valve

(or the vacuum
pump with the
function to
prevent the
back flow)

Gauge manifold
valve (for R410A)

Pressure gauge
    (for R410A)

Compound pressure
gauge (for R410A)

-0.101MPa
(-760 mmHg)

Handle
Low

Handle High

Window

Charge hose
(for R410A)

Vacuum
pump

Adapter for
preventing
the back flow

Charge hose
(for R410A)

Service port

Stop
valve

EMERGENCY
OPERATION switch

Mode Operation Indicator lamp

1

COOL

(Light)

(Off)

2

HEAT

(Off)

(Light)

3

STOP

(Off)

(Off)

6-4 PURGING PROCEDURES·LEAK TEST

PROCEDURE

Press the EMERGENCY OPERATION switch.

1

Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.

If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect the
indoor/outdoor unit connecting wire 

 for mis-wiring.

2

Press it once more, and the EMERGENCY HEAT MODE starts.

3

Press it once more, and the operation stops.
(The operation mode changes in order of 

1

 ~ 

3

 every time the EMERGENCY

OPERATION switch is pressed.)

In starting the heating operation, indoor unit fan may not operate to prevent blowing
cool air. Please wait for a few minutes until the temperature of heat exchanger rises and
warm air blows out.

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller and check that an electronic sound is
heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.

If the indoor unit is operated with the remote controller, both the test
run and the emergency operation are released by commands from
the remote controller.

Once the compressor stops, the restart preventive device operates so the compressor
will not operate for three minutes to protect the air conditioner.

6-6 EXPLANATION TO THE CUSTOMER

Using the OPERATING INSTRUCTIONS, explain the following to the customer, how to
control temperature, how to remove the air filters, how to remove or put the remote
controller in the remote controller holder, how to clean, precautions for operation, etc.

Recommend the customer to read the OPERATING INSTRUCTIONS carefully.

6-7 CHECKING AFTER INSTALLATION

After finishing the installation, check the following items and mark the 

 next to each item.

Is the specified power supply voltage used?

Is the power line equipped with the circuit breaker?

Have the ends of the indoor/outdoor connecting wire been properly inserted into the
terminal blocks?

Has the indoor/outdoor connecting wire been secured firmly?

Are the power supply cord and indoor/outdoor connecting wire connected directly to
the units (no intermediate connections)?

Is the earth wire longer than the other wires so that it will not become disconnected
when tension is applied?

Is the earth wire connected properly?

Are the pipes designed for use with R410A or do they have the specified thickness?

Has the leak test been carried out for the pipe connections?

Has air purging been carried out?

Are the stop valves open fully?

Is the drain hose properly installed?

Has water been poured through the drain hose to confirm proper drainage?

Are the pipes at the rear of the unit bundled with felt tape (for left and left-rear piping
only)?

Can the installation location bear the weight of the unit and not amplify its vibration or
noise?

Is the area under the unit free of objects that block the air outlet?

Are the vertical and horizontal vanes closed securely?

Is the front panel installed securely?

Has the test run been carried out?

Has the drain work been performed properly and are there no bubbling sounds?

Have all of the 

 WARNING and 

 CAUTION items in “1. THE FOLLOWING

SHOULD ALWAYS BE OBSERVED FOR SAFETY” been checked?

6-8 EXPLANATION TO THE CUSTOMER

Using the OPERATING INSTRUCTIONS, explain the following to the customer, how to
control temperature, how to remove the air filters, how to remove or put the remote
controller in the remote controller holder, how to clean, precautions for operation, etc.

Recommend the customer to read the OPERATING INSTRUCTIONS carefully.

6-5 TEST RUN

Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation.

The test run can be started by pressing EMERGENCY OPERATION switch. When the
EMERGENCY OPERATION switch is once pressed, the unit will start the test run
(continuous operation) for 30 minutes.
A thermostat does not work during this time. After 30 minutes the unit will start the
EMERGENCY OPERATION at a fixed temperature setting of 24°C in COOL MODE or
HEAT MODE.

Perform test run in the following procedure.

140 to 180

200 to 300

Tightening torque

N·m

kgf·cm

Cap for service port

Cap for stop valve

13.7 to 17.7

19.6 to 29.4

Pipe length up to 7 m

No gas charge is needed.

Summary of Contents for MSZ-GA50VA

Page 1: ...r or wall and set the wireless remote controller In rooms where inverter type fluorescent lamps are used the signal from the wireless remote controller may not be received 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY before installing the air conditioner Be sure to observe the cautions specified here as they include importa...

Page 2: ...D CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the outdoor units valve cover then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or bend the pipe in pipe bending Limits MSZ GA50 60 71 80 Pipe length 30 m max Height difference 15 m max No of bends 10 max Refrigerant adjustment If pipe length exceeds...

Page 3: ... 3 CONNECTING WIRE SPECIFICATIONS Use special room air conditioning circuit 4 4 INDOOR AND OUTDOOR CONNECTING WIRE CON NECTION You can connect indoor outdoor lead wire without removing the front panel 1 Open the front panel 2 Remove one screw holding the electrical cover then remove the cover 3 Remove the VA clamp and the cord clamp 4 Pass the indoor outdoor unit connecting wire from the back of t...

Page 4: ... is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 6 PIPE FORMING Place the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtain able at a store around it Wr...

Page 5: ...ow Connect the refrigerant piping with the extension pipe Thrust the lower part of the indoor unit into the installation plate 4 7 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with commercially sold insulation The drain hose should point downward for easy drain flow Fig 1 Do not make drain piping as shown in Fig 2 to 5 Spacer assembly Securely attach the s...

Page 6: ... substituted for R410A tools The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit Cap size has been changed from 7 16 UNF with 20 threads to 1 2 UNF with 20 threads R410A tools Can R22 tools be used Description R410A has high pressures beyond the meas urement range of existing gauges Gauge manifold No Port ...

Page 7: ...perates so the compressor will not operate for three minutes to protect the air conditioner 6 6 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control temperature how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the customer to read...

Page 8: ...e top of the front panel 4 Fit in the bottom of the front panel and tighten it using screws 5 Push the section of the front panel marked by the arrow and fit the panel into the air conditioner 7 2 PUMPING DOWN When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant is released into the atmosphere 1 Connect the gauge manifold val...

Reviews: