10 m or less

15 m or less

25 m or less

Power supply cord
Specification

Indoor and Outdoor
connecting wire
Specification

5. OUTDOOR UNIT INSTALLATION

INDOOR/OUTDOOR UNIT CONNECTING WIRE CON-
NECTION AND OUTDOOR POWER SUPPLY CORD
CONNECTION

Connect the indoor/outdoor unit connecting wire 

 from the indoor unit correctly

on the terminal block.

For future servicing, give extra length to connecting wire.

Rated Voltage Breaker capacity

230 V

20 A

Peel off both ends of connecting wire (extension wire).
When too long, or connected by cutting off the middle,
peel off power supply wire to the size as shown in the
right.

Be careful not to contact connecting wire with piping.

Make earth wire a little longer than the others.
(more than 35 mm)

For the indoor/outdoor unit connecting wires, be sure to use the ones in compliance
with the standards.

Be sure to push the core until it is hidden and pull each cable to make sure that it
is not pulled up incomplete insertion may cause a risk of burning the terminal
blocks.

 CAUTION

Use care not to make mis-wiring.

Firmly tighten the terminal screws to prevent them from loosening.

After tightening, pull the wires lightly to confirm that they do not move.

If the connecting wire is incorrectly connected to the terminal block, the unit
does not operate normally.

Connect to the supply terminals and leave a contact
separation of at least 3 mm at each pole to discon-
nect the source power pole. (When the power switch
is shut off, it must disconnect all poles.)

Drain hose

4 Insert the drain hose into the section to which the drain hose is

to be attached at the rear right of the indoor unit.

Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to
the projection of its inserting part at the drain pan.

INDOOR UNIT INSTALLATION

Insert the drain hose into the wall hole sleeve 

, and hook the upper part of

indoor unit on the installation plate 

. Then, move the unit to the very edge of the

left side for putting the piping easily in the back space of the indoor unit. After that,
cut the part of packing material (spacer assembly) to hook it on the back rib and
lift the indoor unit as shown in the figure below.

Connect the refrigerant piping with the extension pipe 

.

Thrust the lower part of the indoor unit into the installation plate 

.

4-7 DRAIN PIPING

If the extension drain hose has to pass through a room, be sure to wrap it with
commercially sold insulation.

The drain hose should point downward for easy drain flow. (Fig. 1)
Do not make drain piping as shown in Fig. 2 to 5.

Spacer assembly

Securely attach the spacer
assembly in the concave part
of the rib, taking care its
direction is correct as shown in
the right.

Spacer

Cut part of packing material (spacer assembly) to
hook it on the back rib.

 WARNING

A means for disconnection of the supply with an isolation switch, or similar
device, in all active conductors shall be incorporated in the fixed wiring.

Never cut the power cord and connect it to other wires.
It may cause a fire.

Loosen terminal screw.

Terminal block

Lead wire

<Connection details>

 WARNING

Be sure to attach the service panel of the outdoor unit securely. If it is not attached
correctly, it could result in a fire or an electric shock due to dust, water, etc.

Remove two fixing
screws to open the
service panel.

Service panel

Fixing screws

Be sure to put the left
portion into the square
hole of the service panel.

Be sure to fix the indoor/outdoor unit
connecting wire 

 and power supply

cord

 using this cord clamp.

Valve cover

35 mm

15 mm

3-core 2.5 mm

2

 or more, in conformity with

Design 245 IEC 57.

3-core 4.0 mm

2

 or more, in conformity with

Design 245 IEC 57.

Cable 4-core 1.0 mm

2

, in conformity with

Design 245 IEC 57.

3-core 6.0 mm

2

 or more, in conformity with

Design 245 IEC 57.

Power supply cord 

3-core

Indoor terminal block

Outdoor terminal block

Indoor/outdoor unit
connecting wire 
4-core 1.0 mm

2

L N

Earth wire
(green/yellow)

Downward slope

Water
leakage

Do not raise.

Water
leakage

Accumulated
drain water

Waving

(Fig. 1)

(Fig. 2)

Water
leakage

Tip of drain
hose dipped
in water.

Ditch

Soft hose
I.D.
15 mm

Drain hose

Less than
50 mm gap

(Fig. 3)

If the drain hose provided with the indoor unit is too short, connect it with drain hose

 that should be provided at your site. (Fig.6)

When connecting the drain hose to the hard vinyi chloride pipe, be sure to insert it
securely into the pipe. (Fig.7)

Air

(Fig. 4)

(Fig. 5)

(Fig. 6)

(Fig. 7)

70 cm
or more

Different-
diameter joint

Drain hose

Hard vinyl chloride pipe
I.D.  30 mm

Be sure to insert the
drain hose securely
into the pipe.

Summary of Contents for MSZ-GA50VA

Page 1: ...r or wall and set the wireless remote controller In rooms where inverter type fluorescent lamps are used the signal from the wireless remote controller may not be received 1 THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY Be sure to read THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY before installing the air conditioner Be sure to observe the cautions specified here as they include importa...

Page 2: ...D CONNECTIONS This unit has flared connections on both indoor and outdoor sides Remove the outdoor units valve cover then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or bend the pipe in pipe bending Limits MSZ GA50 60 71 80 Pipe length 30 m max Height difference 15 m max No of bends 10 max Refrigerant adjustment If pipe length exceeds...

Page 3: ... 3 CONNECTING WIRE SPECIFICATIONS Use special room air conditioning circuit 4 4 INDOOR AND OUTDOOR CONNECTING WIRE CON NECTION You can connect indoor outdoor lead wire without removing the front panel 1 Open the front panel 2 Remove one screw holding the electrical cover then remove the cover 3 Remove the VA clamp and the cord clamp 4 Pass the indoor outdoor unit connecting wire from the back of t...

Page 4: ... is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 6 PIPE FORMING Place the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtain able at a store around it Wr...

Page 5: ...ow Connect the refrigerant piping with the extension pipe Thrust the lower part of the indoor unit into the installation plate 4 7 DRAIN PIPING If the extension drain hose has to pass through a room be sure to wrap it with commercially sold insulation The drain hose should point downward for easy drain flow Fig 1 Do not make drain piping as shown in Fig 2 to 5 Spacer assembly Securely attach the s...

Page 6: ... substituted for R410A tools The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit Cap size has been changed from 7 16 UNF with 20 threads to 1 2 UNF with 20 threads R410A tools Can R22 tools be used Description R410A has high pressures beyond the meas urement range of existing gauges Gauge manifold No Port ...

Page 7: ...perates so the compressor will not operate for three minutes to protect the air conditioner 6 6 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control temperature how to remove the air filters how to remove or put the remote controller in the remote controller holder how to clean precautions for operation etc Recommend the customer to read...

Page 8: ...e top of the front panel 4 Fit in the bottom of the front panel and tighten it using screws 5 Push the section of the front panel marked by the arrow and fit the panel into the air conditioner 7 2 PUMPING DOWN When relocating or disposing of the air conditioner pump down the system following the procedure below so that no refrigerant is released into the atmosphere 1 Connect the gauge manifold val...

Reviews: