background image

EN-7

4-2. TEST RUN

1) Insert power supply plug into the power outlet 

and/or turn on the breaker.

2) Press the E.O. SW once for COOL, and twice 

for HEAT operation. Test run will be performed 

for 30 minutes. If the left lamp of the operation 

indicator blinks every 0.5 seconds, inspect the 

indoor/outdoor unit connecting wire (A) for mis-

wiring.  After the test run, emergency mode (set 

temperature 24ºC) will start.

3) To stop operation, press the E.O. SW several 

times until all LED lamps turn off. Refer to operat

-

ing instructions for details. 

Checking the remote (infrared) signal reception

Press the OFF/ON button on the remote controller (3) and check that an 

electronic sound is heard from the indoor unit. Press the OFF/ON button again 

to turn the air conditioner off.

•  Once the compressor stops, the restart preventive device operates so the 

compressor will not operate for 3 minutes to protect the air conditioner.

4-4. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the 

air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, 

how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

5-1. REMOVING AND INSTALLING THE PANEL 

 

ASSEMBLY

5-3. PUMPING DOWN

When relocating or disposing of the air conditioner, pump down the system 

following the procedure below so that no refrigerant is released into the 

atmosphere.

1) Connect the gauge manifold valve to the service port of the stop valve on the 

gas pipe side of the outdoor unit.

2) Fully close the stop valve on the liquid pipe side of the outdoor unit.

3) Close the stop valve on the gas pipe side of the outdoor unit almost completely 

so that it can be easily closed fully when the pressure gauge shows 0 MPa 

[Gauge] (0 kgf/cm

2

).

4) Start the emergency COOL operation.

  To start the emergency operation in COOL mode, disconnect the power 

supply plug and/or turn off the breaker. After 15 seconds, connect the power 

supply plug and/or turn on the breaker, and then press the E.O. SW once. 

(The emergency COOL operation can be performed continuously for up to 30 

minutes.)

5) Fully close the stop valve on the gas pipe side of the outdoor unit when the 

pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

).

6) Stop the emergency COOL operation.

 

Press the E.O. SW several times until all LED lamps turn off. Refer to operating 

instructions for details.

5-2. REMOVING THE INDOOR UNIT

Remove the bottom of the indoor unit from the 

installation plate.

When releasing the corner part, release both left 

and right bottom corner part of indoor unit and pull 

it downward and forward as shown in the figure on 

the right.

Removal procedure

1) Remove  the  2  screws  which  fix  the  panel 

assembly.

2) Remove the panel assembly. Be sure to 

remove its bottom end first.

Installation procedure

1) Install the panel assembly following the re-

moval procedure in reverse. 

2) Be sure to press the positions as indicated 

by the arrows in order to attach the assembly 

completely to the unit.

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. 

SW or the remote controller before turning off the power supply. Not doing 

so will cause the unit to start operation automatically when power supply is 

resumed.

To the user

•  After installing the unit, make sure to explain the user about auto restart 

function. 

•  If auto restart function is unnecessary, it can be deactivated. Consult the 

service representative to deactivate the function. Refer to the service manual 

for details.

Note: 

When power (circuit breaker) is turned on, the horizontal vanes automatically 

move to the normal position.

When pumping down the refrigerant, stop the compressor before 

disconnecting the refrigerant pipes. The compressor may burst if air 

etc. get into it.

 WARNING

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power 

supply is stopped during operation, such as during blackouts, the function 

automatically starts operation in the previous setting once the power supply is 

resumed. (Refer to the operating instructions for details.) 

5.  RELOCATION AND MAINTENANCE

Emergency operation 

switch (E.O. SW)

VG79J830H01.indd   7

2020/03/09   10:50:43

Summary of Contents for MSZ-AP15VGD

Page 1: ... MSZ AP20VGD English INSTALLATION MANUAL For INSTALLER This manual only describes the installation of indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit VG79J830H01_Cover indd 1 2020 02 20 13 53 25 ...

Page 2: ...diate connection of the power cord or the extension cord and do not connect many devices to one AC outlet It could cause a fire or an electric shock due to defective contact defective insulation exceeding the permissible current etc n Be sure to use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an ...

Page 3: ... Where sulfide gas is generated such as hot spring sewage waste water Where there is high frequency or wireless equip ment Where there is emission of high levels of VOCs including phthalate compounds formaldehyde etc which may cause chemical cracking The appliance shall be stored so as to prevent mechanical damage from occurring 1 3 SPECIFICATIONS Model Power supply 1 Wire specifications Pipe size...

Page 4: ...ion Make sure to provide drain piping with a downhill grade for easy drain flow Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 1 m away from the TV antenna wire IMPORTANT NOTES Units should be installed by licensed contractor according to local code requirements To comply with the requirements of Australian standard AS NZS 3000 electrical installations wiring r...

Page 5: ... cord and or the wire to the terminal block Note Do not place the wires between the indoor unit and the installation plate 1 Damaged wire could cause heat generation or fire Wall Outdoor side ø65 mm 5 7 mm Terminal block Fixing screw Indoor outdoor unit connecting wire A VA clamp Lead wire 15 mm 35 mm Installation plate 1 Center of ø65 mm hole 108 mm or more 81 mm or more 66 mm or more 142 mm or m...

Page 6: ...ith a torque wrench as specified in the table When fastened too tight flare nut may break after a long period and cause refrigerant leakage Be sure to wrap insulation around the piping Direct contact with the bare piping may result in burns or frostbite Indoor unit connection Connect both liquid and gas pipings to indoor unit Apply a thin coat of refrigeration oil J on the flared ends of the pipes...

Page 7: ...0A 0 101 MPa 760 mmHg Handle Low Handle High Adapter for preventing the back flow Charge hose for R32 R410A Close Open Hexagonal wrench Precautions when using the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pressure is applied This may cause gas leak Service port Body Close R32 Open Control valve A When attaching the control valve to...

Page 8: ...supply plug and or turn on the breaker and then press the E O SW once The emergency COOL operation can be performed continuously for up to 30 minutes 5 Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0 05 to 0 MPa Gauge approx 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW several times until all LED lamps turn off Refer to o...