EN-4

Left or left-rear piping

Note:

Be sure to reattach the drain hose and the drain cap in case of left or left-

rear piping.

Otherwise, it could cause drops of water to drip down from the drain hose.

1) Put the refrigerant piping and the drain hose together, then firmly apply felt 

tape (4) from the end. 

  Felt tape (4) overlap 

width should be 1/3 

the tape width. Use 

a bandage stopper 

at the end of felt tape 

(4).

2) Pull out the drain cap 

at the rear right of the 

indoor unit. (Fig. 1)

•  Hold the convex section at the end and pull 

the drain cap.

3) Pull out the drain hose at the rear left of the 

indoor unit. (Fig. 2)

•  Hold the claw marked by the arrows and 

pull out the drain hose forward.

4) Put the drain cap into the section to which the 

drain hose is to be attached at the rear of the 

indoor unit. (Fig. 3)

•  Insert not sharp-edged tools such as screw-

drivers into the hole at the end of the cap 

and insert the cap fully into the drain pan.

5) Insert the drain hose fully into the drain pan at 

the rear right of the indoor unit. (Fig. 4)

•  Check if the hose is hooked securely to the 

projection of its inserting part at the drain 

pan.

6) Insert the drain hose into wall hole sleeve (C), 

and hook the upper part of indoor unit on instal-

lation plate (1). Then, move the indoor unit 

completely to the left in order to make placing 

the piping in the back space of the unit easier.

7) Cut out a piece of cardboard from the shipping 

box, roll it up, hook it onto the back rib, and use 

it as a spacer to lift the indoor unit. (Fig. 5)

8) Connect the refrigerant piping with the extension 

pipe (B).

9) Thrust the lower part of the indoor unit into the 

installation plate (1).

Drain cap

Drain cap

Drain hose

Cut off in case of left 

piping.

Drain cap

Piping tape (G)

Drain hose

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Felt tape (4)

2-1. FIXING OF INSTALLATION PLATE

•  Find a structural material (such as a stud) in the wall and fix installation plate 

(1) horizontally by tightening the fixing screws (2) firmly.

•  To prevent installation plate (1) from vibrating, be sure to install the fixing screws 

in the holes indicated in the illustration. For added support, fixing screws may 

also be installed in other holes.

•  When the knockout is removed, apply vinyl tape to the knockout edges to 

prevent damaging the wires.

•  When bolts recessed in the concrete wall are to be utilized, secure installation 

plate (1) using 11 × 20 · 11 × 26 oval hole (450 mm pitch).

•  If the recessed bolt is too long, change it for a shorter one available in the 

market.

2-2. WALL HOLE DRILLING

1) Determine the wall hole position.

2) Drill a ø65 mm hole. The outdoor side should 

be 5 to 7 mm lower than the indoor side.

3) Insert wall hole sleeve (C).

Indoor terminal block

Indoor/outdoor unit 

connecting wire (A)

Outdoor terminal block

Earth wire (green/yellow)

•  For future servicing, give extra length to the connecting wires.

•  Make earth wire a little longer than others. (More than 60 mm)

•  Do not fold the excess wire, or cram it into small space. Take caution not 

to damage the wires.

•  Be sure to attach each screw to its correspondent terminal when securing 

the cord and/or the wire to the terminal block.

Note: 

Do not place the wires between the indoor unit and the installation 

plate (1). Damaged wire could cause heat generation or fire. 

Wall

Outdoor side

ø65 mm

5-7 mm

Terminal block

Fixing screw

Indoor/outdoor unit  

connecting wire (A)

VA clamp

Lead wire

15 mm

35 mm

Installation plate (1)

Center of  

ø65 mm hole

108 mm  

or more

81 mm  

or more 

66 mm or more/

142 mm or more for left/left 

rear piping (using spacer)

Ceiling

Wall

Wall

Fixing screw (2)

* Same for left hole.

Insert 

the 

scale. *

Align the 

scale with 

the line. *

100 mm

Level 

Do not make drain piping as shown below.

Do not 

raise

Accumulated 

drain water

Air

Waving

Water 

leakage

Water 

leakage

Water 

leakage

Tip of drain 

hose dipped 

in water

Ditch

At least 50 mm 

gap

Down-

ward 

slope

Drain hose

Soft hose 

I.D. 15 mm

Drain hose
Hard vinyl chloride 

pipe I.D. 30 mm

Insert  

securely

Different 

 

diameter joint

70 cm  

or more

Fig. 1

Fig. 2

Fig. 3

2-4. PIPE FORMING AND DRAIN PIPING

Pipe Forming

•  Place the drain hose below the refrigerant piping.

•  Make sure that the drain hose is not heaved or 

snaked.

•  Do not pull the hose when applying the tape.

•  When the drain hose passes the room, be sure 

to wrap insulation material (obtainable at a store) 

around it.

Drain Piping

•  If the extension drain hose has to pass through a room, be sure to wrap it with 

commercially sold insulation. 

•  The drain hose should point downward for easy drain flow. (Fig. 1)

•  If the drain hose provided with the indoor unit is too short, connect it with drain 

hose (I) that should be provided at your site. (Fig. 2)

•  When connecting the drain hose to the hard vinyl chloride pipe, be sure to 

insert it securely into the pipe. (Fig. 3)

Rear, right, or downward piping

1) Put the refrigerant piping and the drain 

hose together, then firmly apply piping 

tape (G) from the end.

2) Insert the piping and the drain hose 

into the wall hole sleeve (C), and hook 

the upper part of the indoor unit on the 

installation plate (1).

3) Check if the indoor unit is hooked securely on the installation plate (1) by 

moving the unit to left and right.

4) Thrust the lower part of the indoor unit into the installation plate (1).

Cut off in case of 

right piping.

Cut off in case of 

downward piping.

2-3. CONNECTING WIRES FOR INDOOR UNIT

You can connect indoor/outdoor lead wire without removing the front panel.

1) Open the front panel.

2) Remove VA clamp.

3) Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit 

and process the end of the wire.

4) Loosen terminal screw, and connect first the earth wire, then indoor/outdoor 

unit connecting wire (A) to the terminal block. Be careful not to make mis-

wiring. Fix the wire to the terminal block securely so that no part of its core is 

appeared, and no external force is conveyed to the connecting section of the 

terminal block. 

5) Firmly tighten the terminal screws to prevent them from loosening. After 

tightening, pull the wires lightly to confirm that they do not move.

6) Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA 

clamp. Never fail to hook the left claw of the VA clamp. Attach the VA clamp 

securely.

Liquid pipe

Gas pipe

Indoor/outdoor unit 

connecting wire (A)

Felt tape (4) 

Piping tape (G)

2.  INDOOR UNIT INSTALLATION

VG79J830H01.indd   4

2020/03/09   10:50:42

Summary of Contents for MSZ-AP15VGD

Page 1: ... MSZ AP20VGD English INSTALLATION MANUAL For INSTALLER This manual only describes the installation of indoor unit When installing the outdoor unit refer to the installation manual of outdoor unit VG79J830H01_Cover indd 1 2020 02 20 13 53 25 ...

Page 2: ...diate connection of the power cord or the extension cord and do not connect many devices to one AC outlet It could cause a fire or an electric shock due to defective contact defective insulation exceeding the permissible current etc n Be sure to use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an ...

Page 3: ... Where sulfide gas is generated such as hot spring sewage waste water Where there is high frequency or wireless equip ment Where there is emission of high levels of VOCs including phthalate compounds formaldehyde etc which may cause chemical cracking The appliance shall be stored so as to prevent mechanical damage from occurring 1 3 SPECIFICATIONS Model Power supply 1 Wire specifications Pipe size...

Page 4: ...ion Make sure to provide drain piping with a downhill grade for easy drain flow Note 1 Place indoor outdoor unit connecting wire A and power supply cord K at least 1 m away from the TV antenna wire IMPORTANT NOTES Units should be installed by licensed contractor according to local code requirements To comply with the requirements of Australian standard AS NZS 3000 electrical installations wiring r...

Page 5: ... cord and or the wire to the terminal block Note Do not place the wires between the indoor unit and the installation plate 1 Damaged wire could cause heat generation or fire Wall Outdoor side ø65 mm 5 7 mm Terminal block Fixing screw Indoor outdoor unit connecting wire A VA clamp Lead wire 15 mm 35 mm Installation plate 1 Center of ø65 mm hole 108 mm or more 81 mm or more 66 mm or more 142 mm or m...

Page 6: ...ith a torque wrench as specified in the table When fastened too tight flare nut may break after a long period and cause refrigerant leakage Be sure to wrap insulation around the piping Direct contact with the bare piping may result in burns or frostbite Indoor unit connection Connect both liquid and gas pipings to indoor unit Apply a thin coat of refrigeration oil J on the flared ends of the pipes...

Page 7: ...0A 0 101 MPa 760 mmHg Handle Low Handle High Adapter for preventing the back flow Charge hose for R32 R410A Close Open Hexagonal wrench Precautions when using the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pressure is applied This may cause gas leak Service port Body Close R32 Open Control valve A When attaching the control valve to...

Page 8: ...supply plug and or turn on the breaker and then press the E O SW once The emergency COOL operation can be performed continuously for up to 30 minutes 5 Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0 05 to 0 MPa Gauge approx 0 5 to 0 kgf cm2 6 Stop the emergency COOL operation Press the E O SW several times until all LED lamps turn off Refer to o...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...FICE TOKYOBUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO100 8310 JAPAN This product is designed and intended for use in the residential commercial and light industrial environment VG79J830H01_Cover indd 2 2020 02 20 13 53 25 ...

Reviews: