14
Model
Piping size O.D : mm
Length of connecting pipe : m
Refrigerant piping
Max. length : m
A
15
Indoor unit
Gas 0.43
Liquid 0.5
Gas
15.88
Liquid
6.35
9.52
Outdoor unit
Gas 0
Liquid 0
MSH-C18TV -
E1
MUH-C18TV -
E1
MSH-C24TV -
E1
MUH-C24TV -
E1
Indoor
unit
w
Max. Height
difference: 5m
A
Refrigerant Piping
Max. Length
w
Height difference should be within 5m
regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Model
MSH-C18TV -
E1
MUH-C18TV -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
1600
15m
280
7m
0
10m
105
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R407C : g)
MAX. REFRIGERANT PIPING LENGTH
Calculation : Xg=35g/m
✕
(Refrigerant piping length (m)–7)
Model
MSH-C24TV -
E1
MUH-C24TV -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
2000
15m
360
7m
0
10m
135
Calculation : Xg=45g/m
✕
(Refrigerant piping length (m)–7)
OB279-1.qxp 2/15/01 10:44 AM Page 14