3. Installation diagram

Fig. 3-1

3.1. Outdoor unit (Fig. 3-1)

Ventilation and service space

  

SUZ-SA71VA

A

 100 mm or more

B

 350 mm or more

C

 500 mm or more

When the piping is to be attached to a wall containing metals (tin plated) or metal 

netting, use a chemically treated wooden piece 0 mm or thicker between the wall 

and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.

Units should be installed by licensed contractor accordingly to local code re-

quirement.

Note:

When operating the air conditioner in low outside temperature, be sure to fol-

low the instructions described below.

•   Never install the outdoor unit in a place where its air inlet/outlet side may be ex-

posed directly to wind.

•   To prevent exposure to wind, install the outdoor unit with its air inlet side facing 

the wall.

•   To prevent exposure to wind, it is recommended to install a baffle board on the 

air outlet side of the outdoor unit.

 

SUZ-SA71VA

Drainage hole 

(

W

42)

Air inlet

Air outlet

417.5

50

360

500

175

Air inlet

330

40

2-10 mm × 21 mm slot

81

840

4. Refrigerant piping work

Fig. 4-2

Fig. 4-1

(C)

(B)

(A)

A

 Indoor unit

B

 Outdoor unit

A

 Indoor unit

B

 Outdoor unit

ø9.5

ø15.88

4.1. Refrigerant pipe (Fig. 4-1)

► Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe 

are within the limits shown below.

Models

(A) Pipe length

(one way)

(B) Height 

difference

(C) Number of 

bends (one way)

SUZ-SA71

Max. 30 m

Max. 30 m 

Max. of 10

•  Height difference limitations are binding regardless of which unit, indoor or out-

door, is positioned higher.

•  Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant 

(R410A) charge is required.

(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)

Pipe length

Up to 7 m

No additional charge is required.

Exceeding 7 m

Additional charge is required.

(Refer to the table below.)

Refrigerant 

to be added

SUZ-SA71

55 g × (refrigerant piping length (m) -7)

Piping preparation

•  Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.

(1) Table below shows the specifications of pipes commercially available.

Model

Pipe

Outside diameter Min. wall

thickness

Insulation

thickness

Insulation

material

mm

inch

SUZ-SA71

For liquid

9.5

3/8

0.8 mm

8 mm

Heat resisting 

foam plastic 

0.045 specific 

gravity

For gas

15.88

5/8

1.0 mm

8 mm

() Ensure that the  refrigerant pipes are well insulated to prevent condensation.

(3) Refrigerant pipe bending radius must be 100 mm or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents 

storage behind the indoor unit and smaller thickness causes dew drippage.

(mm)

01_RG79Y622H02_EN.indd   3

2014/03/27   11:02:15

Summary of Contents for Mr.SLIM SUZ-SA71VA

Page 1: ...nt MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓΧEIPIΔIO OΔHΓIΩN EΓKATAΣ...

Page 2: ... the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the...

Page 3: ...indoor and outdoor units the length of refrigerant pipe and the number of bends in the pipe are within the limits shown below Models A Pipe length one way B Height difference C Number of bends one way SUZ SA71 Max 30 m Max 30 m Max of 10 Height difference limitations are binding regardless of which unit indoor or out door is positioned higher Refrigerant adjustment If pipe length exceeds 7 m addit...

Page 4: ... flaring work again a Smooth all around f Scratch on flared plane b Inside is shining without any scratches g Cracked c Even length all around h Uneven d Too much i Bad examples e Tilted Apply a thin coat of refrigeration oil on the seat surface of pipe Fig 4 8 For connection first align the center then tighten the first 3 to 4 turns of flare nut Use tightening torque table below as a guideline fo...

Page 5: ...n close the gage manifold valve and stop the vacuum pump Leave it as is for one or two minutes Make sure the pointer of the gage mani fold valve remains in the same position Confirm that the pressure gage show 0 101 MPa 760 mmHg Remove the gage manifold valve quickly from the service port of the stop valve After refrigerant pipes are connected and evacuated fully open all stop valves on gas and li...

Page 6: ...he size given in the figure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Fig 5 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the outdoor unit securely If it is not attached correctly it could result in a fire ...

Page 7: ...t S2 S3 2 DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect ope...

Page 8: ...0 5 to 0 kgf cm2 and quickly stop the air conditioner Push the ON OFF button on the remote controller to stop the air conditioner Note that when the extension piping is very long with a large refrigerant amount it may not be possible to perform a pump down operation In this case use refrigerant recovery equipment to collect all of the refrigerant in the system 7 Turn off the power supply circuit b...

Page 9: ... и на предприятиях легкой промышленности erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer MITSUBISHI ELECTRIC SUZ SA71VA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve ...

Page 10: ...talingen van het origi neel VOORZICHTIG Het lekken van koelvloeistof kan verstikking veroorzaken Zorg voor ventilatie in overeen stemming met EN378 1 Isoleer de leidingen met isolatiemateriaal Direct contact met de onbedekte leidingen kan leiden tot brandwonden of bevriezing Stop nooit batterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging ver...

Page 11: ...ng it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC Regulation EU No 206 2012 RoHS Directive 2011 ...

Page 12: ...umber SUZ SA71VA Mr Slim Inverter Cassette Range Brochure SUZ SA71VA_Parts_Catalog_ OCB561 SUZ SA71VA_Installation_Manual_ RG79Y622H02 SUZ SA71VA_Declaration_of_Conformity_ CE2014B01 B03 SUZ SA71VA_ _Service_Manual_ OCH561 ...

Reviews: