background image

2

Contents

1. Safety 

precautions 

..................................................................................... 2

2.  Selecting the installation location .............................................................. 3
3. Installation 

diagram 

................................................................................... 3

4.  Installing the indoor unit ............................................................................ 3

5.  Refrigerant pipe and drain pipe ................................................................. 6
6. Electrical 

work 

........................................................................................... 7

7.  Installing the grille .................................................................................... 10
8. Test 

run 

.................................................................................................... 12

1. Safety precautions

1.2.  Before installation or relocation

 Caution:

•  Be extremely careful when transporting the units. Two or more persons are 

needed to handle the unit, as it weighs 20 kg, 44 lbs or more. Do not grasp 
the packaging bands. Wear protective gloves as you can injure your hands 
on the fins or other parts.

•  Be sure to safely dispose of the packaging materials. Packaging materials, 

such as nails and other metal or wooden parts may cause stabs or other 
injuries.

 Warning:

•  Ask a dealer or an authorized technician to install the unit.
•  For installation work, follow the instructions in the Installation Manual and use 

tools and pipe components specifically made for use with refrigerant specified 
in the outdoor unit installation manual.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

• The unit must be securely installed on a structure that can sustain its 

weight. 

•  If the air conditioner is installed in a small room, measures must be taken to 

prevent the refrigerant concentration in the room from exceeding the safety 
limit in the event of refrigerant leakage. Should the refrigerant leak and cause 
the concentration limit to be exceeded, hazards due to lack of oxygen in the 
room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. 

•  Use only specified cables for wiring.
•  The terminal block cover panel of the unit must be firmly attached.
•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them.

•  The user should never attempt to repair the unit or transfer it to another loca-

tion.

•  After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or 
portable cooking range, poisonous gases will be released.

1.1.  Before installation (Environment)

 Caution:

•  Do not use the unit in an unusual environment. If the air conditioner is installed 

in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, 
areas exposed to high salt content such as the seaside, the performance can 
be significantly reduced and the internal parts can be damaged.

•  Do not install the unit where combustible gases may leak, be produced, flow, 

or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.

•  Do not keep food, plants, caged pets, artwork, or precision instruments in the 

direct airflow of the indoor unit or too close to the unit, as these items can be 
damaged by temperature changes or dripping water.

• When the room humidity exceeds 80% or when the drainpipe is clogged, 

water may drip from the indoor unit. Do not install the indoor unit where such 
dripping can cause damage.

•  When installing the unit in a hospital or communications office, be prepared for 

noise and electronic interference. Inverters, home appliances, high-frequency 
medical equipment, and radio communications equipment can cause the air 
conditioner to malfunction or breakdown. The air conditioner may also affect 
medical equipment, disturbing medical care, and communications equipment, 
harming the screen display quality.

•  Thermal insulation of the refrigerant pipe is necessary to prevent condensation. 

If the refrigerant pipe is not properly insulated, condensation will be formed.

•  Place thermal insulation on the pipes to prevent condensation. If the drain-

pipe is installed incorrectly, water leakage and damage to the ceiling, floor, 
furniture, or other possessions may result.

•  Do not clean the air conditioner unit with water. Electric shock may result.
•  Tighten all flare nuts to specification using a torque wrench. If tightened too 

much, the flare nut can break after an extended period.

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.
•  For the power lines, use standard cables of sufficient capacity. Otherwise, a 

short circuit, overheating, or fire may result.

•  When installing the power lines, do not apply tension to the cables.

•  Be sure to ground the unit. If the unit is not properly grounded, electric shock 

may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and 

molded case circuit breaker) with the specified capacity. If the circuit breaker 
capacity is larger than the specified capacity, breakdown or fire may result.

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 12 hours before starting operation. 

Starting operation just after turning on the power switch can severely damage 
the internal parts.

•  Before starting operation, check that all panels, guards and other protective 

parts are correctly installed. Rotating, hot, or high voltage parts can cause 
injuries.

•  Do not operate the air conditioner without the air filter set in place. If the air 

filter is not installed, dust may accumulate and breakdown may result.

•  Do not touch any switch with wet hands. Electric shock may result.
•  Do not touch the refrigerant pipes with bare hands during operation.
•  After stopping operation, be sure to wait at least five minutes before turning off 

the main power switch. Otherwise, water leakage or breakdown may result.

► Before installing the unit, make sure you read all the “Safety precau-

tions”.

► Please report to your supply authority or obtain their consent before 

connecting this equipment to the power supply system. 

 Warning:

Describes precautions that must be observed to prevent danger of injury or 
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety precautions,” use, and 
maintenance of the unit to the customer according to the information in the Operation 
Manual and perform the test run to ensure normal operation. Both the Installation 
Manual and Operation Manual must be given to the user for keeping. These manuals 
must be passed on to subsequent users.

  : Indicates a part which must be grounded.

 

 Warning:

Carefully read the labels affixed to the main unit.

Summary of Contents for Mr.Slim SLZ-KA09

Page 1: ...horoughly before installing the air conditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil extérieur pour une utilisation sûre et correct MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado Français Español Engl...

Page 2: ...ed water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high frequency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also...

Page 3: ...he unit 3 Installation diagram 3 1 Indoor unit Fig 3 1 Ceiling Grille Obstacle Min 1000 mm 40 inch Min 500 mm 20 inch Entire periphery If setting the maintenance space for be sure to leave is a minimum of 700 mm 28 inch Warning Mount the indoor unit on a ceiling strong enough to withstand the weight of the unit 3 2 Outdoor unit Refer to the outdoor unit installation manual 4 1 Check the indoor uni...

Page 4: ... mm ø3 16 inch hole Duct flange Prepared locally Detail drawing of fresh air intake 4 10 mm ø4 1 2 inch Tapping screw Prepared locally Indoor unit Ceiling surface Duct Fig 4 3 inch 4 2 Ceiling openings and suspension bolt installation locations Fig 4 2 Using the installation template top of the package and the gauge supplied as an accessory with the grille make an opening in the ceiling so that the...

Page 5: ...ssory Fig 4 5 Main unit Ceiling Installation template Accessory Screw with washer Accessory Fig 4 7 Fig 4 6 B Suspension bolt pitch see Fig 4 2 for details Mounting plate Washer without insulation Accessory Check using the Installation gauge Main unit Ceiling Gauge Grille accessory Ceiling opening dimensions inch 4 5 Unit suspension procedures Fig 4 5 Suspend the main unit as shown in the diagram ...

Page 6: ...apt to loosen Be certain to use the flare nuts that are attached to the main unit Use of commercially available products may result in cracking Apply refrigerating machine oil over the entire flare seat surface 5 3 Indoor unit Fig 5 4 Heat insulation for refrigerant pipes Wrap the enclosed large sized pipe cover around the gas pipe making sure that the end of the pipe cover touches the side of the u...

Page 7: ...utside the electric component box 5 Attach the electric component cover as it was Do not allow slackening of the terminal screws Always install earth Earth cable dia Thicker than 1 6 mm 5 8 inch AWG14 Fix power supply cable and control cable to electric component box by using buffer bushing for tensile force PG connection or the like Tape is affixed over the conduit hole used for connecting the ele...

Page 8: ... Radio frequency interface for RF thermostat For Power supply 6 Electrical work 6 2 Remote controller 6 2 1 Wired remote controller 1 2 remote controllers setting If 2 remote controllers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the opera tion manual for the indoor unit Fig 6 3 Mode number Setting number Refrigeran...

Page 9: ...uipped with outdoor air intake 3 Power voltage 230 V 04 104 1 208 V 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller Mode Settings Mode No Setting no Initial setting Setting Wired remote controller RF thermostat Filter sign 100 Hr 07 107 1 2500 Hr 2 No filter sign indicator 3 Fan speed Standard PLH PLA Silent PCH PCA 08 108 1 High ceiling PLH PLA ...

Page 10: ...h the hook for the intake grille With the intake grille in the open position remove the hinge of the intake grille from the grille as indicated by the arrow Fig 7 2 7 3 Installing the grille Please pay attention because there is a restriction in the attachment position of the grille 7 3 1 Preparations Fig 7 5 Install the 2 enclosed screws with washer in the main unit at the corner refriger ant pip...

Page 11: ...rm on and drop from the ceiling or the unit could malfunction Fig 7 9 Button Vane motor Up down vanes Connector Fig 7 10 7 3 4 Wire connection Fig 7 8 Be sure to connect the unit to the connector white 10 pole red 9 pole Next attach the white glass tube that comes with the main unit so that the tube covers the connector Close the opening of the glass tube with the band Make sure that there is no s...

Page 12: ...nstallation manual that comes with each remote controller for de tails RF thermostat is not established Errors detected by indoor unit Wired remote controller RF thermostat Symptom Remark Check code P1 Intake sensor error P2 Pipe TH2 sensor error P9 Pipe TH5 sensor error E6 E7 Indoor outdoor unit communication error P4 Drain sensor error P5 Drain pump error PA Forced compressor error P6 Freezing O...

Page 13: ...t run has been performed refer to the following table to remove the cause Note Operation is not possible for about 30 seconds after cancellation of function selection Correct operation For description of each LED LED1 2 3 provided on the indoor controller refer to the following table LED1 power for microcomputer Indicates whether control power is supplied Make sure that this LED is always lit LED2...

Page 14: ... ou des gouttes d eau Si l humidité ambiante dépasse 80 ou si le tuyau d écoulement est bouché des gouttes d eau peuvent tomber de l appareil intérieur Ne pas installer l appareil intérieur dans un endroit où ces gouttes peuvent provoquer des dommages Lors de l installation de l appareil dans un hôpital ou un centre de communica tions se préparer au bruit et aux interférences électroniques Les inv...

Page 15: ...érieur dans un plafond suffisamment résistant pour sup porter son poids 3 Schéma d installation 3 1 Appareil intérieure Fig 3 1 Plafond Grille Obstacle Min 1000 mm 40 pouce Min 500 mm 20 pouce Toute la périphérie Lors de la définition de l espace de maintenance pour veiller à laisser au moins 700 mm 28 pouce Avertissement Fixer l appareil intérieur à un plafond suffisamment résistant pour supporter s...

Page 16: ...er sur place Schéma détaillé de la prise d air extérieur Vis 4 10 mm ø4 1 2 pouce Appareil intérieur à se procurer sur place Surface du plafond Conduit Fig 4 3 pouce 4 2 Ouvertures dans le plafond et emplacement des boulons de suspension Fig 4 2 Utiliser le schéma d installation dans le haut du colis et le gabarit fourni comme accessoire avec la grille pour créer une ouverture dans le plafond de s...

Page 17: ...sion Construire une structure ren forcée à l endroit de suspension de l appareil Fig 4 4 Les travaux à effectuer au plafond varient en fonction du type d édifice Il convient de consulter les constructeurs et les décorateurs du bâtiment pour plus de détails 1 Etendue de la découpe dans le plafond Le plafond doit être parfaitement à l horizontale et ses fondations encadrement linteaux de bois ou supp...

Page 18: ...que de desserrage des écrous évasés Veiller à utiliser les écrous évasés fournis avec l unité principale Les produits du commerce risquent de se fissurer Appliquer de l huile pour machine frigorifique sur toute la surface d appui évasée 5 3 Appareil intérieur Fig 5 4 Isolation des tuyaux de réfrigérant contre la chaleur Enrouler le cache tuyaux de grande dimension fourni autour du tuyau de gaz en s ...

Page 19: ...r l interface radiofréquence Connecter correctement le cordon électrique de l interface radiofréquence au connecteur CN105 ROUGE situé sur le panneau du contrôleur intérieur Pour le contrôleur de la télécommande à fil Raccorder solidement les câbles d alimentation et de commande aux blocs de raccordement 4 Fixer les câbles à l aide de crampons à l extérieur du boîtier de composants électriques 5 Re...

Page 20: ... à fil Commutateur fusible principal Mise à la terre Panneau du contrôleur intérieur Interface radiofréquence pour le thermostat RF Pour alimentation PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF Fig 6 3 Numéro de mode Numéro de réglage Adresse de réfrigérant Numéro d appareil 6 2 Télécommande 6 2 1 Télécommande à fil 1 Réglage des 2 commandes à dista...

Page 21: ...l intérieur est équipé d une prise d air extérieure 3 Tension d alimentation 230 V 04 104 1 208 V 2 Sélectionner les appareils numéro 01 à 03 ou tous les appareils AL télécommande avec fil 07 télécommande sans fil Mode Paramètre No de Mode No de réglage Réglage initial Réglage Télécommande à fil Thermostat radiofréquence RF Signe du filtre 100 heures 07 107 1 2500 heures 2 Pas d indicateur de signe du...

Page 22: ... crochet qui sert à fixer la grille Ne pas décrocher le crochet de la grille d admission Lorsque la grille se trouve en position ouverte retirer la charnière de la grille d admission comme indiqué par la flèche 7 3 Installer la grille Faire très attention aux restrictions concernant la position de fixation de la grille 7 3 1 Préparatifs Fig 7 5 Installer les 2 vis livrées munies des rondelles d étanc...

Page 23: ...age indi quée De la condensation pourrait apparaître et provoquer l apparition de gouttes au plafond ou l appareil risquerait de mal fonctionner Fig 7 9 Fig 7 10 7 3 4 Câblage Fig 7 8 Toujours veiller à raccorder l appareil au connecteur blanc 10 broches rouge 9 broches Fixer ensuite le tuyau en verre blanc livré avec l appareil principal de sorte qu il recouvre le connecteur Refermer l ouverture ...

Page 24: ...stat radiofréquence RF Symptôme Remarque Code de vérification P1 Erreur du capteur d admission P2 Erreur du capteur sur tuyaux TH2 P9 Erreur du capteur sur tuyaux TH5 E6 E7 Erreur de communication de l appareil intérieur extérieur P4 Erreur du capteur d écoulement P5 Erreur de la pompe d écoulement PA Erreur du compresseur à circulation forcée P6 Fonctionnement du dispositif de protection en cas de...

Page 25: ...ai indiqué ci dessus consulter le tableau suivant pour en trou ver la cause éventuelle Remarque Son utilisation n est pas possible pendant 30 secondes après l annulation de la sélection de fonction Fonctionnement correct Pour la description de chacun des témoins LED 1 2 3 repris sur le contrôleur de l appareil intérieur se reporter au tableau suivant LED1 alimentation du micro ordinateur Indique s...

Page 26: ... el tubo de drenaje esté obstruido puede gotear agua de la unidad interior No instale la unidad interior en lugares donde el goteo pueda causar daños Si instala la unidad en un hospital o en un centro de comunicaciones re cuerde que la unidad produce ruidos e interferencias electrónicas Los con mutadores aparatos domésticos equipos médicos de alta frecuencia y las comunicaciones de radio pueden pr...

Page 27: ...ación 3 1 Unidad interior Fig 3 1 Techo Rejilla Obstáculo Mín 1000 mm 40 pulg Mín 500 mm 20 pulg Toda la periferia Si ajusta el espacio de mantenimiento para asegúrese de dejar un mínimo de 700 mm 28 pulg Atención Instale la unidad interior en un techo suficientemente fuerte para soportar el peso de la unidad 3 2 Unidad exterior Consulte el manual de instalación de la unidad exterior 4 1 Comprobaci...

Page 28: ...lg Reborde de conducto preparado localmente Vista detallada de la entrada de aire fresco Tornillos roscados de 4 10 mm ø4 1 2 pulg preparados localmente Unidad interior Superficie del techo Conducto Fig 4 3 pulg 4 2 Apertura del techo y ubicación de los tornillos de suspensión Fig 4 2 Mediante la plantilla de instalación parte superior del paquete y el calibre sumi nistrado como un accesorio junto ...

Page 29: ...d principal las arandelas inferiores con aislamiento y las tuercas dobles se colocarán más tarde 2 Levante la unidad hasta la altura adecuada de los tornillos de sujeción para insertar la placa de montaje entre arandelas y apretar luego las tuercas 3 Cuando la unidad principal no pueda ser alineada contra los orificios de monta je en el techo se puede ajustar posteriormente gracias a la ranura prev...

Page 30: ...ar las tuercas abocardadas que se suministran con la uni dad principal El uso de productos de otros fabricantes puede provocar grietas Aplique aceite refrigerante para máquinas sobre toda la superficie abocardada 5 3 Unidad interior Fig 5 4 Aislamiento del calor para los tubos refrigerantes Envuelva la cubierta adjunta del tubo de mayor tamaño alrededor del tubo de gas asegurándose de que el extrem...

Page 31: ... a colocar la tapa de los componentes eléctricos como estaba No permita que se aflojen los tornillos terminales Instale siempre una toma de tierra Diámetro del cable de toma de tierra más grueso de 1 6 mm 5 8 pulg AWG14 Coloque el cable de alimentación y el de control en la caja de los componentes eléctricos utilizando manguitos aisladores separadores para fuerza tractiva Conexión PG o similar La c...

Page 32: ...lador interior Interfaz de radiofrecuencia para el termostato por infrarrojos Para la Alimentación 6 Trabajo eléctrico Fig 6 3 Mode number Setting number Refrigerant address Unit number 6 3 Ajuste de funciones Para el controlador remoto cableado Fig 6 3 Cambio del ajuste de voltaje de alimentación Asegúrese de cambiar el ajuste de voltaje de alimentación dependiendo del vol taje utilizado Paso al ...

Page 33: ...el exterior 3 Voltaje de alimentación 230 V 04 104 1 208 V 2 Seleccione los números de unidad 01 a 03 o todas las unidades AL controlador remoto alámbrico 07 controlador remoto inalámbrico Modo Ajustes Núm de modo Núm de ajuste Configuración inicial Ajuste Controlador remoto cableado Termostato de radiofrecuencia Señalización de filtro 100 horas 07 107 1 2500 horas 2 Sin indicador de señalización de...

Page 34: ...agra de la rejilla de admisión de la rejilla tal y como se indica mediante la flecha Fig 7 2 7 3 Instalación de la rejilla Preste especial atención debido a la restricción existente en la colocación de la posición de la rejilla 7 3 1 Preparación Fig 7 5 Instale los 2 tornillos con arandelas que se adjuntan en la unidad principal en el área del tubo de refrigerante de uno de los extremos y en el ext...

Page 35: ...formar condensación y gotear desde el techo o podría produ cirse un funcionamiento incorrecto de la unidad Fig 7 9 Botón Motor de la paleta Conector Conector Fig 7 10 7 3 4 Conexión de cables Fig 7 8 Asegúrese de conectar la unidad al conector blanco polo 10 rojo polo 9 A continuación coloque el tubo de cristal blanco que viene junto con la unidad principal de forma que cubra al conector Cierre la...

Page 36: ...5 Error de la bomba de drenaje PA Error del compresor forzado P6 Funcionamiento de seguridad por helada sobrecalentamiento EE Error de comunicación entre unidades interior y exterior P8 Error de temperatura del tubo E4 Error de recepción de señal del controlador remoto Fb Error del sistema de control de la unidad interior error de memoria etc Errors detected by unit other than indoor unit outdoor ...

Page 37: ...s de haberse llevado a cabo la ejecución de prueba consulte la tabla siguiente para suprimir la causa Nota No se puede utilizar durante aproximadamente 30 segundos después de cancelar la selección de funciones Funcionamiento correcto Para la descripción de cada uno de los LED LED 1 2 3 de los controladores interiores consulte la tabla siguiente LED1 alimentación para microordenador Indica si se su...

Page 38: ......

Page 39: ......

Page 40: ...0 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79D589H01 Printed in Thailand ...

Reviews: