15
OCH708
4-4. STANDARD OPERATION DATA
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)
Representative matching
PUZ-SM100
PUZ-SM125
PUZ-SM140
Mode
COOLING
HEATING
COOLING
HEATING
COOLING
HEATING
Total
Capacity
W
9.5
11.2
12.1
13.5
13.4
15.0
input
kW
2.79
3.1
4.17
3.73
5.13
4.54
Electrical
circuit
Indoor
PLA-SM100EA
PLA-SM125EA
PLA-SM140EA
Phase, Hz
1, 50
1, 50
1, 50
Voltage
V
230
230
230
Current
A
0.46
0.44
0.66
0.64
0.66
0.64
Outdoor
PUZ-SM100VKA
PUZ-SM100YKA
PUZ-SM125VKA
PUZ-SM125YKA
PUZ-SM140VKA
PUZ-SM140YKA
Phase, Hz
1, 50
3, 50
1, 50
3, 50
1, 50
3, 50
Voltage
V
230
400
230
400
230
400
Current
A
12.1/4.3
13.4/4.8
17.4/6.3
15.6/5.6
22.3/8.1
19.0/6.9
Refrigerant
circuit
Discharge Pressure
MPa
2.93
2.70
3.12
2.62
3.28
2.79
Suction pressure
MPa
0.96
0.70
0.89
0.69
0.84
0.66
Discharge temperature
:
90.2
88.7
89.4
81.7
91.0
88.7
Condensing temperature
:
38.0
44.7
39.8
43.5
40.3
45.9
Suction temperature
:
14.1
1.3
7.9
0.0
5.6
−0.9
Ref. pipe length
m
7.5
7.5
7.5
Indoor
side
Intake air
temperature
DB
:
27
20
27
20
27
20
WB
:
19
14
19
14
19
14
Discharge air
temperature
DB
:
13.6
40.1
11.9
41.7
11.3
44.5
Outdoor
side
Intake air
DB
:
35
7
35
7
35
7
temperature
WB
:
24
6
24
6
24
6
SHF
0.77
—
0.72
—
0.70
—
BF
0.16
—
0.10
—
0.10
—
PUZ-SM100VKA.TH PUZ-SM100YKA.TH
PUZ-SM125VKA.TH PUZ-SM125YKA.TH
PUZ-SM140VKA.TH PUZ-SM140YKA.TH