92
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Pulse
LEV-C opening pulse 0~480
0 – 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs. 0.5secs. 2 secs.
:
Indoor room temperature (TH1) on error
occurring
8 – 39
8 – 39
:
Indoor pipe temperature / Liquid (TH2)
on error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 secs. 0.5secs. 2 secs.
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor pipe temperature / 2-phase
(TH6) on error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor ambient temperature (TH7) on
error occurring
-39 – 88
-39 – 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor heatsink temperature (TH8) on
error occurring
-40 – 200
-40 – 200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
30
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
:
:
:
:
The black square ( ) indicates a switch position.
OCH527B