13
OCH594B
INDOOR-OUTDOOR CONNECTING CABLE
Cross section of cable
Wire size (mm
2
)
Number of wires
Polarity
L (m)*
5
Round
2.5
3
Clockwise : S1-S2-S3
(Pay attention to stripe of yellow and green.)
(30)*
1
Flat
2.5
3
Not applicable
(Since center wire has no cover finish.)
Not applicable*
4
Flat
1.5
4
From left to right: S1-Open-S2-S3
(18)*
2
Round
2.5
4
Clockwise : S1-S2-S3-Open
(Connect S1 and S3 to the opposite angle.)
(30)*
3
Note: Power supply cords of appliances shall not be lighter than design 60245 IEC or
227 IEC.
*
1
In case that cable with stripe of yellow and green is available.
*
2
In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm
2.
*
3
In case of regular polarity connection (S1-S2-S3).
*
4
In the flat cables are connected as this picture, they can be used up to 30 m.
*
5
Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or
materials, etc.
(3C Flat cable × 2)
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication error if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at
the intermediate connection point.
S1
S3
S2