121
13. Removing the reactors (ACL1, ACL2, ACL3)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the 6 screws, screw
8
and
9
(5
✕
10), that fix
the front panel and remove the front panel. (See photo 3.)
(4) Remove the 2 screws, screw
0
and
1
(both 4
✕
10),
that fix the separator, screw
0
from the valve bed and
screw
1
from the bottom of the separator, and tilt the
separator to the side of the fan motor slightly.
(See photo 17.)
(5) Disconnect the lead wires from the reactor and remove the
4 screws, screw
2
, that fix the reactor to remove the
reactor. (See photo 18 and 19.)
Note 1: The reactor is very heavy (4kg)! Be careful when
handling it.
Note 2: The reactor box is also removable.
OPERATING PROCEDURE
PHOTOS
Photo 17
Electrical parts box
Screw
0
Valve
bed
Screw
1
Separator
Reactor box
Photo 18
Reactors
Reactor box
Electrical
parts box
Four-way
valve
Photo 19
Screw
2
Reactor box
Propeller
OC344-5.qxp 05.5.26 5:54 PM Page 121