71
OCH670
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Discharge temperature (TH4)
−20 to 217
Output step of outdoor FAN
0 to 16
The number of ON / OFF times of com-
pressor
0 to 9999
Compressor integrating operation times
0 to 9999
−20 to 217
(When the discharge thermistor detects 100
:
or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105
:
;
0.5 s 0.5 s 2 s
:
Step
100 times
10 hours
0 to 16
0 to 9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 ×100 times);
0.5 s 0.5 s 2 s
0 to 9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 ×10 hours);
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Compressor operating current
0 to 50
0 to 50
Note: Omit the figures after the decimal fractions.
A
Error postponement code history (1)
of outdoor unit
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
“00” is displayed in case of no postponement.
Code
display
Code
display
Operation mode on error occurring
Operation mode of when operation stops due to
error is displayed by setting SW2 like below.
1
ON
2 3 4 5 6
(SW2)
1
ON
2 3 4 5 6
Compressor operating frequency
0 to 255
0 to 9999
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125 Hz;
0.5 s 0.5 s 2 s
0.1 Hz
1
05
4
25
2
45
12
50
1
ON
2 3 4 5 6
The black square ( ) indicates a switch position.