TROUBLESHOOTING
Unit conditions at service
Check code
Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action
according to “9-3. SELF-DIAGNOSIS ACTION TABLE”.
Conduct troubleshooting and ascertain the cause of the
trouble according to “9-4. TROUBLESHOOTING BY
INFERIOR PHENOMENA”.
The trouble is not reoccurring.
Logged
Not logged
1
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise, etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring, etc.
2
Reset check code logs and restart the unit after finishing
service.
3
There is no abnormality in electrical component,
controller board, remote controller, etc.
1
Re-check the abnormal symptom.
2
Conduct troubleshooting and ascertain the cause of the
trouble according to “9-4. TROUBLESHOOTING BY
INFERIOR PHENOMENA”.
3
Continue to operate unit for the time being if the cause
is not ascertained.
4
There is no abnormality concerning of parts such as
electrical component, controller board, remote controller,
etc.
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller and control board of out-
door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa-
rized in the table below. Check the contents below before investigating details.
9-1. TROUBLESHOOTING
TCH070A.indd 22
TCH070A.indd 22
7/2/2565 16:46:49
7/2/2565 16:46:49