<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press
w
button to select AUTO STOP or AUTO START.
3. Press
q
button to set desired time.
Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour.
When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON/OFF button.
2-7 Test run
<Before test run>
●
After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or
control wiring, and mistaken polarity.
●
Use a 500-volt megger to check the resistance between the power supply terminal block and ground to make sure that it is
at least 1.0M
Ω
.
Attention:
Do not use the air conditioner if resistance is less than 1.0M
Ω
.
This setting will stop the air conditioner in 8 hours.
With the lapse of time, time display changes in 1 hour units, showing remaining time.
<Timer setting example>
2-6 TIMER operation
OFF
FILTER
CHECK MODE
CHECK
TEST RUN
FILTER
CHECK MODE
CHECK
TEST RUN
TEST RUN button
TEST RUN
Indoor coil temperature code
Display
Display
1
2
4
5
6
3
Turn on main switch. 12 hours before proceeding to step 2
to allow for crankcase heater operation.
Push the TEST RUN button twice and indication of TEST
RUN will be shown on the liquid crystal display.
Push button LOW/HIGH to check that the fan speed
changes properly.
Check the operation of outdoor unit fans. This unit controls
the rotation speed and performance capacity of fans. In
some cases, it may rotate at low speed as the condition of
outside air requires and the speed will be kept unless the
performance has become deficient.
Therefore, when the condition of outside air demands,
there may be such cases as the fan stops or rotates
reversely.
Please note that these symptoms are not malfunction.
After the check is finished leave the test run mode, push
the power ON/OFF button.
It can also be stopped by pushing the timer MODE button.
Press the
button to display
f
, COOL/DRY
(or HEAT ) to confirm that cool (or warm ) air is blown out.
(AT heating operation, there may be a short delay before
warm air begins to be out.)
The above figure shows the state of TEST RUN at
cooling operation.
●
When a TEST RUN is started, the timer shall be set to hours. The unit will automatically turn off after 2 hours.
Remote controller