background image

11

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

A
B

D

C

G

E

F

4

1

2

1

3 4

1

2

A

 Pair No. of wireless remote controller

Indoor PC board

0

Factory setting

1

Cut J41

2

Cut J42

3–9

Cut J41, J42

4) Assigning a remote controller to each unit (Fig. 6-7)

Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a remote controller is assigned
to the same pair No.

5) Wireless remote controller pair number setting operation

1

Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.

MODEL SELECT

 blinks and Model No. is lighted.

2

Press the 

min

 button twice continuously.

Pair No. “0” blinks.

3

Press the temp 

 button to set the pair number you want to set.

4

Press the SET button with something sharp at the end.
Set pair number is lighted for three seconds then turned off.

Fig. 6-7

Fig. 6-8

3

CHECK

4

CHECK

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

E

C

,

D

F

A
B

Fig. 6-9

2

CHECK

CHECK

1

6. Electrical work

?

Mode number

?

Setting number

?

Refrigerant address

?

Unit number

1

2

3

4

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL SELECT

1

,

4

3

A

2

6.3. Function settings

6.3.1 Function setting on the unit (Selecting the unit functions)

1) For wired remote controller (Fig. 6-8)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function setting mode.

Switch OFF the remote controller.
Press the 

A

 and 

B

 buttons simultaneously and hold them for at least 2

seconds. FUNCTION will start to flash.

2

Use the 

C

 button to set the refrigerant address (

3

) to 00.

3

Press

D

 and [--] will start to flash in the unit number (

4

) display.

4

Use the 

C

 button to set the unit number (

4

) to 00.

5

Press the 

E

 MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number (

1

) display momentarily.

6

Press the 

F

 buttons to set the mode number (

1

) to 04.

7

Press the 

G

 button and the current set setting number (

2

) will flash.

Use the 

F

 button to switch the setting number in response to the power supply

voltage to be used.
Power supply voltage

230 V : setting number = 1
208 V : setting number = 2

8

Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

2) For wireless remote controller (Fig. 6-9)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function select mode

Press the 

CHECK

 button 

F

 twice continuously.

(Start this operation from the status of remote controller display turned off.)

CHECK

 is lighted and “00” blinks.

Press the temp 

 button 

C

 once to set “50”. Direct the wireless remote controller

toward the receiver of the indoor unit and press the 

h

 button 

A

.

2

Setting the unit number

Press the temp 

 button 

C

 and 

D

 to set the unit number “00”. Direct the wireless

remote controller toward the receiver of the indoor unit and press the 

min

 button 

B

.

3

Selecting a mode

Enter 04 to change the power voltage setting using the 

C

 and 

D

 buttons.

Direct the wireless remote controller toward the receiver of the indoor unit and press

the

h

 button 

A

.

Current setting number:

1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)

4

Selecting the setting number

Use the 

C

 and 

D

 buttons to change the power voltage setting to 01 (240 V).

Direct the wireless remote controller toward the sensor of the indoor unit and press

the

h

 button 

A

.

5

To select multiple functions continuously

Repeat steps 

3

 and 

4

 to change multiple function settings continuously.

6

Complete function selection

Direct the wireless remote controller toward the sensor of the indoor unit and press

the

 button 

E

.

Note:
Whenever changes are made to the function settings after installation or main-
tenance, be sure to record the changes with a mark in the “Setting” column of
the Function table.

6.3.2 Function setting on the remote controller

Refer to the indoor unit operation manual.

9

Summary of Contents for Mr.Slim PKA-AA GA

Page 1: ...he outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR ...

Page 2: ...e unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre q...

Page 3: ...ole in the wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot ø90 mm 3 9 16 inch C Main body K Bottom right pipe slot knockout hole D Slot 6 11 20 L Liquid pipe flare connection position 6P 7 16 25 32 inch M Gas pipe flare connection position E Unit center N Level setting standard F Bolt hole 14 ø14 mm V Ins...

Page 4: ...pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left rear piping Fig 3 7 1...

Page 5: ...iquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut...

Page 6: ...d check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 4 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 2 The drain pipe can be cut midway to meet the on site conditions A Total length of flexible hose D Drain hose B Liquid pipe E Left...

Page 7: ... Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor unit Outdoor unit S1 S2 3 Indoor unit Outdoor unit S2 S3 3 Remote controller Indoor unit 3 PKA 1A 15A 3 AWG16 polar 1 Min AWG16 2 AWG22 Non polar AC 208 230 V DC24 V DC12 V Circuit rating Wiring Wire No size ...

Page 8: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or h...

Page 9: ... 1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230 V setting number 1 208 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Press ...

Page 10: ...10 ...

Page 11: ... P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory err...

Page 12: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displaye...

Page 13: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the ...

Page 14: ...s manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U874H02 BG79U874H02 A ...