Before installing the unit, make sure you read all the “Safety precau-
tions”.

s

Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or
death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

1.2. Before installation or relocation

 Caution:

• Be extremely careful when transporting the units. Two or more persons are

needed to handle the unit as it weighs 20 kg, 44 lbs or more. Do not grasp the
packaging bands. Wear protective gloves as you can injure your hands on
the fins or other parts.

• Be sure to safely dispose of the packaging materials. Packaging materials,

such as nails and other metal or wooden parts may cause stabs or other
injuries.

Contents

 Warning:

• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use

tools and pipe components specifically made for use with refrigerant specified
in the outdoor unit installation manual.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

• The unit must be securely installed on a structure that can sustain its weight.
• If the air conditioner is installed in a small room, measures must be taken to

prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Should the refrigerant leak and cause
the concentration limit to be exceeded, hazards due to lack of oxygen in the
room may result.

• Ventilate the room if refrigerant leaks during operation. If refrigerant comes

into contact with a flame, poisonous gases will be released.

• All electric work must be performed by a qualified technician according to

local regulations and the instructions given in this manual.

• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or

an authorized technician to install them.

• The user should never attempt to repair the unit or transfer it to another loca-

tion.

• After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.

1.1. Before installation (Environment)

 Caution:

• Do not use the unit in an unusual environment. If the air conditioner is in-

stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, the performance
can be significantly reduced and the internal parts can be damaged.

• Do not install the unit where combustible gases may leak, be produced, flow,

or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.

• Do not keep food, plants, caged pets, artwork, or precision instruments in the

direct airflow of the indoor unit or too close to the unit as these items can be
damaged by temperature changes or dripping water.

• When the room humidity exceeds 80% or when the drainpipe is clogged, wa-

ter may drip from the indoor unit. Do not install the indoor unit where such
dripping can cause damage.

• When installing the unit in a hospital or communications office, be prepared

for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown. The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.

• Thermal insulation of the refrigerant pipe is necessary to prevent condensa-

tion. If the refrigerant pipe is not properly insulated, condensation will be formed.

• Place thermal insulation on the pipes to prevent condensation. If the drain-

pipe is installed incorrectly, water leakage and damage to the ceiling, floor,
furniture, or other possessions may result.

• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too

much, the flare nut can break after an extended period.

1.3. Before electric work

 Caution:

• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a

short circuit, overheating, or fire may result.

• When installing the power lines, do not apply tension to the cables.

• Be sure to ground the unit. If the unit is not properly grounded, electric shock

may result.

• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and

molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.

1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 3
3. Installing the indoor unit ........................................................................... 3
4. Installing the refrigerant piping ................................................................. 5

5. Drainage piping work ............................................................................... 6
6. Electrical work .......................................................................................... 7
7. Test run .................................................................................................. 12
8. Easy maintenance function (Option) ...................................................... 15

1. Safety precautions

After installation work has been completed, explain the “Safety precautions,” use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.

: Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

1.4. Before starting the test run

 Caution:

• Turn on the main power switch more than 12 hours before starting operation.

Starting operation just after turning on the power switch can severely dam-
age the internal parts.

• Before starting operation, check that all panels, guards and other protective

parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.

• Do not operate the air conditioner without the air filter set in place. If the air

filter is not installed, dust may accumulate and breakdown may result.

• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning off

the main power switch. Otherwise, water leakage or breakdown may result.

Summary of Contents for Mr.Slim PKA-AA GA

Page 1: ...he outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Español MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad exterior antes de instalar la unidad de aire acondicionado PARA EL INSTALADOR ...

Page 2: ...e unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre q...

Page 3: ...ole in the wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot ø90 mm 3 9 16 inch C Main body K Bottom right pipe slot knockout hole D Slot 6 11 20 L Liquid pipe flare connection position 6P 7 16 25 32 inch M Gas pipe flare connection position E Unit center N Level setting standard F Bolt hole 14 ø14 mm V Ins...

Page 4: ...pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left rear piping Fig 3 7 1...

Page 5: ...iquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 9 mm 23 64 inch or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut...

Page 6: ...d check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refrigerant piping A B C D E F G Fig 4 4 4 3 Positioning refrigerant and drain piping 1 Position of refrigerant and drain piping Fig 4 2 The drain pipe can be cut midway to meet the on site conditions A Total length of flexible hose D Drain hose B Liquid pipe E Left...

Page 7: ... Indoor unit Outdoor unit 1 Indoor unit earth Remote controller Indoor unit 2 Indoor unit Outdoor unit S1 S2 3 Indoor unit Outdoor unit S2 S3 3 Remote controller Indoor unit 3 PKA 1A 15A 3 AWG16 polar 1 Min AWG16 2 AWG22 Non polar AC 208 230 V DC24 V DC12 V Circuit rating Wiring Wire No size ...

Page 8: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1 Installation area Area in which the remote controller is not exposed to direct sunshine Area in which there is no nearby heating source Area in which the remote controller is not exposed to cold or h...

Page 9: ... 1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230 V setting number 1 208 V setting number 2 8 Press the MODE button E and mode and the setting number 1 and 2 will change to being on constantly and the contents of the setting can be confirmed 9 Press ...

Page 10: ...10 ...

Page 11: ... P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safeguard operation 7 EE Communication error between indoor and outdoor units 8 P8 Pipe temperature error 9 E4 Remote controller signal receiving error 10 11 12 Fb Indoor unit control system error memory err...

Page 12: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this LED is always blinking 7 Test run On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit Blink of operation lamp On wired remote controller Check code displaye...

Page 13: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Display A Press the ...

Page 14: ...s manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U874H02 BG79U874H02 A ...