7-4. ADDITION OF REFRIGERANT
• Additional charging is not necessary if the pipe length does not exceed 30 m (100 ft).
• If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the
permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe
extensions and indoor unit have been vacuumized.
* When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant
directly to the check valve.
* After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit).
• Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have
a serious effect on operation performance.
Model
Max. height
difference
Additional refrigerant charging amount
Max. pipe
length
30 m
33 m
37 m
40 m
43 m
46 m
49 m
52 m
55 m
58 m
61 m
64 m
67 m
70 m
73 m
75 m
100 ft
110 ft
120 ft
130 ft
140 ft
150 ft
160 ft
170 ft
180 ft
190 ft
200 ft 210 ft
220 ft
230 ft
240 ft
245 ft
0 oz
6 oz
12 oz
18 oz
24 oz
30 oz
36 oz
42 oz
48 oz
54 oz
60 oz
66 oz
72 oz
78 oz
84 oz
86 oz
0 kg
0.2 kg 0.4 kg 0.5 kg 0.7 kg 0.9 kg 1.0 kg 1.2 kg 1.4 kg 1.5 kg 1.7 kg 1.9 kg 2.0 kg 2.2 kg 2.3 kg 2.4 kg
HA30,36
75 m
245 ft
30 m
100 ft