9
2) HEATING CAPACITY
Note CA :Capacity (W)
P.C. :Power consumption (kW)
Heating capacity correction factors
P.C.
CA
4,588
4,393
4,222
5,684
5,443
5,230
7,122
6,820
6,554
8,903
8,524
8,192
1.79
1.93
2.04
2.27
2.45
2.60
2.48
2.67
2.83
3.28
3.54
3.75
15
20
25
15
20
25
15
20
25
15
20
25
-10
P.C.
CA
5,259
5,052
4,847
6,514
6,259
6,004
8,163
7,842
7,524
10,203
9,803
9,404
1.98
2.13
2.27
2.51
2.71
2.88
2.74
2.95
3.14
3.63
3.91
4.17
-5
P.C.
CA
5,994
5,768
5,539
7,425
7,145
6,861
9,303
8,953
8,597
11,629
11,191
10,747
2.18
2.34
2.51
2.76
2.98
3.19
3.01
3.25
3.47
3.99
4.30
4.60
0
P.C.
CA
6,792
6,539
6,297
8,414
8,101
7,801
10,543
10,150
9,774
13,179
12,688
12,218
2.39
2.57
2.75
3.03
3.27
3.50
3.31
3.56
3.82
4.38
4.72
5.06
5
P.C.
CA
7,653
7,366
7,121
9,481
9,125
8,822
11,880
11,434
11,054
14,850
14,292
13,817
2.61
2.81
3.02
3.32
3.58
3.83
3.62
3.90
4.18
4.80
5.16
5.54
10
P.C.
CA
8,576
8,247
8,011
10,624
10,217
9,924
13,312
12,802
12,435
16,640
16,002
15,544
2.85
3.07
3.29
3.62
3.90
4.18
3.95
4.25
4.56
5.23
5.63
6.04
15
Outdoor intake air D.B.
°
C
Indoor
Intake
air
W.B.
°
C
Service Ref.
PEH-2.5EKHA
2
.TH
PEH-3EKHA
2
.TH
PEH-4EKHSA
2
.TH
PEH-5EKHSA
2
.TH
Service Ref.
PEH-2.5EKHA
2
.TH
PEH-3EKHA
2
.TH
PEH-4EKHSA
2
.TH
PEH-5EKHSA
2
.TH
5m
1.00
1.00
1.00
1.00
10m
1.00
1.00
1.00
1.00
15m
1.00
1.00
1.00
1.00
20m
1.00
1.00
1.00
1.00
25m
1.00
1.00
1.00
1.00
30m
1.00
1.00
1.00
1.00
Refrigerant piping length (one way)
35m
0.998
0.998
0.998
0.998
40m
0.995
0.995
0.995
0.995
45m
0.993
0.993
0.993
0.993
50m
0.990
0.990
0.990
0.990