background image

15

6. Refrigerant piping work

6.1. Refrigerant pipe

[Fig. 6-1] (P.3)

a

Indoor unit

b

Outdoor unit

 Refer to the Instruction Manual that came with the outdoor unit for the restrictions on
 the height difference between units and for the amount of additional refrigerant
 charge.

Avoid  the  following  places  for  installation  where  air  conditioner  trouble  is  liable  to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides. 

[Fig. 6-1]

• Refrigerant pipes are used to connect the indoor and outdoor units as shown in the

figure below.

• Insulate both refrigerant and drainage piping completely to prevent condensation.

Piping preparation

• Refrigerant pipes of 3, 5, 7, 10 and 15 m [9-13/16, 16-3/8, 22-15/16, 32-1/4 and 49-

3/16 ft] are available as optional items.

(1) Table below shows the specifications of pipes commercially available.

(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.

(3) Refrigerant pipe bending radius must be 10 cm [3-15/16 in] or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.

6.2. Flaring work

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

6.2.1. Pipe cutting

[Fig. 6-3] (P.3)

a

Copper tubes

b

Good

c

No good

d

Tilted

e

Uneven

f

Burred

• Using a pipe cutter cut the copper tube correctly.

6.2.2. Burrs removal

[Fig. 6-4] (P.3)

a

Burr

b

Copper tube/pipe

c

Spare reamer

d

Pipe cutter

• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in

order to avoid burrs drop in the tubing.

6.2.3. Putting nut on

[Fig. 6-5] (P.3)

a

Flare nut

b

Copper tube

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube

having completed burr removal.
(not possible to put them on after flaring work)

6.2.4. Flaring work

[Fig. 6-6] (P.3)

a

Flaring tool

b

Die

c

Copper tube

d

Flare nut

e

Yoke

• Carry out flaring work using flaring tool as shown below.

Dimension

Pipe diameter

A (mm [in])

(mm [in])

When the tool for R410A is used

B              (mm [in])

Clutch type

6.35 [1/4]

0 to 0.5 [0 to 1/32]

9.1 [3/8]

9.52 [3/8]

0 to 0.5 [0 to 1/32]

13.2 [17/32]

12.7 [1/2]

0 to 0.5 [0 to 1/32]

16.6 [21/32]

15.88 [5/8]

0 to 0.5 [0 to 1/32]

19.7 [25/32]

Firmly hold copper tube in a die in the dimension shown in the table at above.

6.2.5. Check

[Fig. 6-7] (P.3)

a

Smooth all around

f

Scratch on flared plane

b

Inside is shining without any scratches

g

Cracked

c

Even length all around

h

Uneven

d

Too much

i

Bad examples

e

Tilted

• Compare the flared work with a figure in right side hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

6.3. Pipe connection

[Fig. 6-8] (P.3)

• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table below as a guideline for indoor unit side union joint section,

and tighten using two wrenches. Excessive tightening damages the flare section.

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm [in])

(mm [in])

 (N·m)

ø6.35 [1/4]

17 [11/16]

14 - 18

ø9.52 [3/8]

22 [7/8]

34 - 42

ø12.7 [1/2]

26 [1-1/32]

49 - 61

ø15.88 [5/8]

29 [1-5/32]

68 - 82

 Warning:

Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., hiss-

ing noise stops).

3. Check that the gas has been completely released, and then remove the nut.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque

applied for indoor unit.

Pipe

For liquid

For gas

For liquid

For gas

For liquid

For gas

For liquid

For gas

Outside diameter

mm

inch

9.52

3/8

15.88

5/8

9.52

3/8

15.88

5/8

9.52

3/8

15.88

5/8

9.52

3/8

15.88

5/8

Model

PEAD-
A24AA
PEAD-
A30AA
PEAD-
A36AA
PEAD-
A42AA

Insulation

material

Heat resisting

foam plastic

0.045 specific

gravity

Insulation thickness

mm

inch

8

5/16

8

5/16

8

5/16

8

5/16

8

5/16

8

5/16

8

5/16

8

5/16

Min wall thickness

mm

inch

0.8

1/32

1.0

1/32

0.8

1/32

1.0

1/32

0.8

1/32

1.0

1/32

0.8

1/32

1.0

1/32

+0

-0.4 [-1/32]

Summary of Contents for Mr.SLIM PEAD-A24AA

Page 1: ...ead this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR Français ...

Page 2: ... in or more 2 100 mm 3 15 16 in or more 3 10 mm 7 16 in or more 4 300 mm 11 13 16 in or more Y X L W A Z C Nuts field supply D Washers accessory E M10 hanging bolt field supply B C D A F G 3 4 E A C B A D C E 1 2 50 150 2 5 15 16 450 17 3 4 450 17 3 4 49 1 15 16 625 24 5 8 777 30 5 8 20 13 16 100 3 15 16 23 15 16 250 9 7 8 B A Model PEAD A24 30AA PEAD A36 42AA A 1100 43 5 16 1400 55 1 8 B 1154 45 ...

Page 3: ...ation field supply I Pull J Flare nut K Return to original position A B C D F G E H H K L J I J O O N N 20 25 32 20 25 32 20 25 32 20 25 32 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth all around b Inside is shining without any scratches c Even length a...

Page 4: ... N Drain hose accessory O Horizontal or slightly upgradient Fig 6 11 C B A L D D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F A Indoor unit B Tie band accessory C Visible part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply G Insulating material field supply H Tie band accessory I To be gap free The joint section of the insulation material meet m...

Page 5: ...utdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply S1 S2 1 2 S1 S2 S3 S3 A C B D J E B C F G H L1 L2 G L1 L2 G A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit p...

Page 6: ...ce wiring H Use ordinary bushing I Transmission wiring J Conduit K Side frame L Knockout hole for power source wiring M Washer accessory N Terminal block for power source and indoor transmission O Terminal block for remote controller Fig 8 2 3 Fig 8 2 4 C Terminal box D Knockout hole E Remove A Screw holding cover 1pc B Cover Fig 8 2 1 Fig 8 2 2 8 A B D E C H I J G F O N L K J M ...

Page 7: ... 5 16 A B C 30 1 3 16 30 1 3 16 A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch Fig 8 4 Fig 8 3 A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 AWG 16 or more D Outdoor terminal block 1 Connecting cable Cable 3 core 1 5 mm2 AWG 16 in con formity with Design 245 IEC 57 2 Indoor terminal b...

Page 8: ...B C A Fix tightly with tape B Remote controller wire C Order wire Indoor unit Fig 8 8 Fig 8 11 H J I When using the switch box When installing directly on the wall A 150 mm 5 15 16 inch B Remote controller wire Accessory C Wiring pipe D Locknut H Seal around here with putty I Remote controller wire J Seal around here with putty E Bushing F Switch box G Seal around here with putty C D B F E G A Wal...

Page 9: ...r case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 15 1 1 2 A 1 Hang the cover to the upper hooks 2 places 2 Mount the cover to the lower case A Cross section of upper hooks ...

Page 10: ...air number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 A CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHECK 2 4 ...

Page 11: ...lection button F Set temperature button G Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number 1 2 3 4 3 1 2 CHECK CHECK CHECK CHECK 4 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHECK E F D C A B A Hour button B Minute button C TEMP button D TEMP button E ON OFF button F CHECK button Fig 8 22 Fig 9 3 A TEST ...

Page 12: ...pe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 10 1 ...

Page 13: ...mplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or sp...

Page 14: ... connected at the bottom and side surfaces and the maintenance is made at the same surfaces allow a proper space properly For the efficient suspension work and safety provide a space as much as possible 3 3 Indoor unit accessories The unit is provided with the following accessories No Name Quantity 1 Pipe cover for refrigerant piping joint Small diameter 1 2 Pipe cover for refrigerant piping joint...

Page 15: ...e c Copper tube d Flare nut e Yoke Carry out flaring work using flaring tool as shown below Dimension Pipe diameter A mm in mm in When the tool for R410A is used B mm in Clutch type 6 35 1 4 0 to 0 5 0 to 1 32 9 1 3 8 9 52 3 8 0 to 0 5 0 to 1 32 13 2 17 32 12 7 1 2 0 to 0 5 0 to 1 32 16 6 21 32 15 88 5 8 0 to 0 5 0 to 1 32 19 7 25 32 Firmly hold copper tube in a die in the dimension shown in the t...

Page 16: ... to support the refrigerant pipe so that no load is imparted to the indoor unit end pipe This metal brace should be provided 50 cm 19 11 16 in away from the indoor unit s flare connection Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R41...

Page 17: ... In case of bottom inlet A Duct B Air inlet C Access door D Canvas duct E Ceiling surface F Air outlet G Leave distance enough to prevent short cycle Procedure for changing the rear inlet to the bottom inlet Fig 7 2 P 5 A Filter B Bottom plate 1 Remove air filter First remove filter lock screw 2 Remove the bottom plate 3 Fit the bottom plate to the rear of the body Fig 7 3 P 5 Position of lug hole...

Page 18: ...e frame L Knockout hole for power source wiring M Washer accessory Fig 8 2 4 P 6 N Terminal block for power source and indoor transmission O Terminal block for remote controller Perform wiring as shown in the diagram to the lower left Procure the cable locally Make sure to use cables of the correct polarity only Fig 8 3 P 7 A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit co...

Page 19: ...cting the installation site lf the Signal Receiving Unit is installed near a fluorescent lamp specially inverter type signal interception may occur Be careful for installing the Signal Receiving Unit or replacing the lamp 2 Use the remote controller wire to connect it to the connector CN90 on the controller circuit board on the indoor unit Refer to the 2 Setting the Pair Number Switch for details ...

Page 20: ...ote controller Remote controller s internal sensor Not Supported Supported indoor unit is not equipped with outdoor air intake Supported indoor unit is equipped with outdoor air intake 240V 220V 230V Energy saving cycle automatically enabled Energy saving cycle automatically disabled Mode no Setting no Initial setting Check 1 1 01 2 1 02 2 3 1 03 2 3 1 04 2 1 05 2 Mode Power failure automatic reco...

Page 21: ... to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote contro...

Page 22: ...it Remark For details check the LED display of the outdoor controller board Output pattern A Errors detected by indoor unit Wireless remote controller Beeper sounds OPERATION INDICATOR lamp flashes Number of times 1 2 3 4 5 6 7 8 9 10 11 12 No sound Wired remote controller Check code P1 P2 P9 E6 E7 P4 P5 P6 EE P8 E4 Fb Symptom Intake sensor error Pipe Liquid or 2 phase pipe sensor error Indoor out...

Page 23: ...maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C 104 F during cold season But never use naked fire or steam 9 Test run Indicates whether control power is supplied Make sure that this LED is always lit Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit ...

Reviews: