background image

18

8.1. Power supply

8.1.1. Indoor unit power supplied from outdoor unit

The following connection patterns are available.
The outdoor unit power supply patterns vary on models.

1:1 System

[Fig. 8-1] (P.5)

A

Outdoor unit power supply

B

Earth leakage breaker

C

Wiring circuit breaker or isolating switch

D

Outdoor unit

E

Indoor unit/outdoor unit connecting cords

F

Remote controller

G

Indoor unit

* Affix a label A that is included with the manuals near each wiring diagram for the

indoor and outdoor units.

Simultaneous twin/triple/four system

[Fig. 8-2] (P.5)

A

Outdoor unit power supply

B

Earth leakage breaker

C

Wiring circuit breaker or isolating switch

D

Outdoor unit

E

Indoor unit/outdoor unit connecting cords

F

Remote controller

G

Indoor unit

* Affix a label A that is included with the manuals near each wiring diagram for the

indoor and outdoor units.

Field electrical wiring

*1. The 10 m [32 ft] wire is attached in the remote controller accessory. Max. 500 m [1640 ft]
*2. The figures are NOT always against the ground.

S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals
are not electrically insulataed by the transformer or other device.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Power supply cords and indoor unit/outdoor unit connecting cords

shall  not  be  lighter  than  polychloroprene  sheathed  flexible  cord.
(Design 245 IEC57)

3. Install an earth longer than other cables.

 Caution:

Do not use anything other than the correct capacity breaker and fuse. Using fuse,
wire or copper wire with too large capacity may cause a risk of malfunction or fire.

8.2. Indoor wire connection

Work procedure
1.Remove 2 screws to detach the electric component cover.
2.Route each cable through the wiring intake into the electric component box. (Pro-

cure power cable and in-out connecting cable locally and use remote control cable
supplied with the unit.)

3.Securely connect the power cable and the in-out connecting cable and the remote

control cable to the terminal blocks.

4.Secure the cables with clamps inside the electric component box.
5.Attach the electric component cover as it was.
• Fix  power  supply  cable  and  indoor/outdoor  cable  to  control  box  by  using  buffer

bushing for tensile force. (PG connection or the like.)

 Warning:

• Attach the electrical part cover securely. If it is attached incorrectly, it could

result in a fire, electric shock due to dust, water, etc.

• Use the specified indoor/outdoor unit connecting wire to connect the indoor

and outdoor units and fix the wire to the terminal block securely so that no
stress is applied to the connecting section of the terminal block.  Incomplete
connection or fixing of the wire could result in a fire.

[Fig. 8-2-1] (P.6)

A

Screw holding cover (1pc)

B

Cover

[Fig. 8-2-2] (P.6)

C

Terminal box

D

Knockout hole

E

Remove

8. Electrical work

[Fig. 8-2-3] (P.6)

F

Use PG bushing to keep the weight of the cable and external force from being applied to the
power supply terminal connector. Use a cable tie to secure the cable.

G

Power source wiring

H

Use ordinary bushing

I

Transmission wiring

J

Conduit

K

Side frame

L

Knockout hole (for power source wiring)

M

Washer (accessory)

[Fig. 8-2-4] (P.6)

N

Terminal block for power source and indoor transmission

O

Terminal block for remote controller

• Perform wiring as shown in the diagram to the lower left. (Procure the cable locally.)

Make sure to use cables of the correct polarity only.

[Fig. 8-3] (P.7)

A

Indoor terminal block

B

Earth wire (green/yellow)

C

Indoor/outdoor unit connecting wire 3-core 1.5 mm

2

 [AWG 16] or more

D

Outdoor terminal block

1

Connecting cable

Cable 3-core 1.5 mm

2

 [AWG 16], in conformity with Design 245 IEC 57.

2

Indoor terminal block

3

Outdoor terminal block

4

Always install an earth wire (1-core 1.5 mm

2

 [AWG 16]) longer than other cables

5

Remote controller cable

Wire No 

×

 size (mm

2

) : Cable 2C 

×

 0.3

This wire accessory of remote controller

(wire length : 10 m [32 ft], non-polar. Max. 500 m [1640 ft])

6

Wired remote controller

• Connect the terminal blocks as shown in the diagram below.

 Caution:

• Use care not to make mis-wiring.
• Firmly tighten the terminal screws to prevent them from loosening.
• After tightening, pull the wires lightly to confirm that they do not move.

8.3. Remote controller (wired remote controller)

8.3.1. For wired remote controller

1) Installing procedures

(1) Select an installing position for the remote controller.
The temperature sensors are located on both remote controller and indoor unit.

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

[Fig. 8-4] (P.7)

A

Remote controller profile

B

Required clearances surrounding the remote controller

C

Installation pitch

(2) Seal the service entrance for the remote controller cord with putty to prevent pos-

sible invasion of dew drops, water, cockroaches or worms.

[Fig. 8-5] (P.7)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run the remote

controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cut-out upper case, then seal the cut-out notch

with putty similarly as above.

C

Wall

G

Switch box

D

Conduit

H

Remote controller cord

E

Lock nut

I

Seal with putty

F

Bushing

J

Wood screw

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:

(3) For direct installation on the wall

2) Connecting procedures

1

Connect the remote controller cord to the terminal block.

[Fig. 8-6] (P.7)

A

To the terminal block on the indoor unit

B

TB6 (No polarity)

2

Set the dip switch No.1 shown below when using two remote controller’s for the
same group.

3) Function selection of remote controller

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

Indoor unit model

Wiring 

Wire 

No.

×

 size 

(mm

2

)

C

ir

c

u

it

rating

Indoor unit power supply (Heater)

Indoor unit power supply (Heater) earth

Indoor unit-Outdoor unit

Indoor unit-Outdoor unit earth

Remote controller-Indoor unit

*1

Indoor unit (Heater) L-N

*2

Indoor unit-Outdoor unit S1-S2

*2

Indoor unit-Outdoor unit S2-S3

*2

Remote controller-Indoor unit

*2

PEAD

×

 1.5 (polar)

×

 Min. 1.5

×

 0.3 (Non-polar)

230 V AC

24 V DC

14 V DC

Summary of Contents for Mr.SLIM PEAD-A24AA

Page 1: ...ead this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER English MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte POUR L INSTALLATEUR Français ...

Page 2: ... in or more 2 100 mm 3 15 16 in or more 3 10 mm 7 16 in or more 4 300 mm 11 13 16 in or more Y X L W A Z C Nuts field supply D Washers accessory E M10 hanging bolt field supply B C D A F G 3 4 E A C B A D C E 1 2 50 150 2 5 15 16 450 17 3 4 450 17 3 4 49 1 15 16 625 24 5 8 777 30 5 8 20 13 16 100 3 15 16 23 15 16 250 9 7 8 B A Model PEAD A24 30AA PEAD A36 42AA A 1100 43 5 16 1400 55 1 8 B 1154 45 ...

Page 3: ...ation field supply I Pull J Flare nut K Return to original position A B C D F G E H H K L J I J O O N N 20 25 32 20 25 32 20 25 32 20 25 32 Fig 6 3 Fig 6 6 Fig 6 4 Fig 6 5 a Flare nut b Copper tube a Burr b Copper tube pipe c Spare reamer d Pipe cutter Fig 6 7 Fig 6 8 a Flaring tool b Die c Copper tube d Flare nut e Yoke a Smooth all around b Inside is shining without any scratches c Even length a...

Page 4: ... N Drain hose accessory O Horizontal or slightly upgradient Fig 6 11 C B A L D D D E K M B H I Max 20m 65ft 1 5 2m 5 7ft G F F F A Indoor unit B Tie band accessory C Visible part D Insertion margin E Drain hose accessory F Drain pipe O D ø32 mm 1 1 4 in PVC TUBE field supply G Insulating material field supply H Tie band accessory I To be gap free The joint section of the insulation material meet m...

Page 5: ...utdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply S1 S2 1 2 S1 S2 S3 S3 A C B D J E B C F G H L1 L2 G L1 L2 G A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit p...

Page 6: ...ce wiring H Use ordinary bushing I Transmission wiring J Conduit K Side frame L Knockout hole for power source wiring M Washer accessory N Terminal block for power source and indoor transmission O Terminal block for remote controller Fig 8 2 3 Fig 8 2 4 C Terminal box D Knockout hole E Remove A Screw holding cover 1pc B Cover Fig 8 2 1 Fig 8 2 2 8 A B D E C H I J G F O N L K J M ...

Page 7: ... 5 16 A B C 30 1 3 16 30 1 3 16 A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch Fig 8 4 Fig 8 3 A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit connecting wire 3 core 1 5 mm2 AWG 16 or more D Outdoor terminal block 1 Connecting cable Cable 3 core 1 5 mm2 AWG 16 in con formity with Design 245 IEC 57 2 Indoor terminal b...

Page 8: ...B C A Fix tightly with tape B Remote controller wire C Order wire Indoor unit Fig 8 8 Fig 8 11 H J I When using the switch box When installing directly on the wall A 150 mm 5 15 16 inch B Remote controller wire Accessory C Wiring pipe D Locknut H Seal around here with putty I Remote controller wire J Seal around here with putty E Bushing F Switch box G Seal around here with putty C D B F E G A Wal...

Page 9: ...r case directly on the wall or the ceiling use wood screws Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover A flat screwdriver whose width of blade is between 4 and 7mm 5 32 9 32inch must be used Fig 8 15 1 1 2 A 1 Hang the cover to the upper hooks 2 places 2 Mount the cover to the lower case A Cross section of upper hooks ...

Page 10: ...air number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 1 Pair number 2 Pair number 3 Pair number 0 Pair number 0 Pair number 0 Pair number 0 A CN2A CN3C SW2 SW1 JP1 JP2 JP3 JP41 JP42 CN22 CN2L CNXA2 CN32 SWE CN20 CN90 CN105 CN41 CN4F CN51 CNXB2 CNXC2 CN44 ON OFF Indoor controller board ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHECK 2 4 ...

Page 11: ...lection button F Set temperature button G Timer Menu button Monitor Set button Mode number Setting number Refrigerant address Unit number 1 2 3 4 3 1 2 CHECK CHECK CHECK CHECK 4 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK CHECK E F D C A B A Hour button B Minute button C TEMP button D TEMP button E ON OFF button F CHECK button Fig 8 22 Fig 9 3 A TEST ...

Page 12: ...pe D Gas pipe E Stop valve F Outdoor unit G Refrigerant gas cylinder operating valve H Refrigerant gas cylinder for R410A with siphon I Refrigerant liquid J Electronic scale for refrigerant charging K Charge hose for R410A L Gauge manifold valve for R410A M Service port 10 1 ...

Page 13: ...mplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the service panel in the outdoor unit are not attached securely it could result in a fire or an electric shock due to dust water etc Be sure to use the part provided or sp...

Page 14: ... connected at the bottom and side surfaces and the maintenance is made at the same surfaces allow a proper space properly For the efficient suspension work and safety provide a space as much as possible 3 3 Indoor unit accessories The unit is provided with the following accessories No Name Quantity 1 Pipe cover for refrigerant piping joint Small diameter 1 2 Pipe cover for refrigerant piping joint...

Page 15: ...e c Copper tube d Flare nut e Yoke Carry out flaring work using flaring tool as shown below Dimension Pipe diameter A mm in mm in When the tool for R410A is used B mm in Clutch type 6 35 1 4 0 to 0 5 0 to 1 32 9 1 3 8 9 52 3 8 0 to 0 5 0 to 1 32 13 2 17 32 12 7 1 2 0 to 0 5 0 to 1 32 16 6 21 32 15 88 5 8 0 to 0 5 0 to 1 32 19 7 25 32 Firmly hold copper tube in a die in the dimension shown in the t...

Page 16: ... to support the refrigerant pipe so that no load is imparted to the indoor unit end pipe This metal brace should be provided 50 cm 19 11 16 in away from the indoor unit s flare connection Close Open Hexagonal wrench Stop valve 4 to 5 turns Stop valve or the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R41...

Page 17: ... In case of bottom inlet A Duct B Air inlet C Access door D Canvas duct E Ceiling surface F Air outlet G Leave distance enough to prevent short cycle Procedure for changing the rear inlet to the bottom inlet Fig 7 2 P 5 A Filter B Bottom plate 1 Remove air filter First remove filter lock screw 2 Remove the bottom plate 3 Fit the bottom plate to the rear of the body Fig 7 3 P 5 Position of lug hole...

Page 18: ...e frame L Knockout hole for power source wiring M Washer accessory Fig 8 2 4 P 6 N Terminal block for power source and indoor transmission O Terminal block for remote controller Perform wiring as shown in the diagram to the lower left Procure the cable locally Make sure to use cables of the correct polarity only Fig 8 3 P 7 A Indoor terminal block B Earth wire green yellow C Indoor outdoor unit co...

Page 19: ...cting the installation site lf the Signal Receiving Unit is installed near a fluorescent lamp specially inverter type signal interception may occur Be careful for installing the Signal Receiving Unit or replacing the lamp 2 Use the remote controller wire to connect it to the connector CN90 on the controller circuit board on the indoor unit Refer to the 2 Setting the Pair Number Switch for details ...

Page 20: ...ote controller Remote controller s internal sensor Not Supported Supported indoor unit is not equipped with outdoor air intake Supported indoor unit is equipped with outdoor air intake 240V 220V 230V Energy saving cycle automatically enabled Energy saving cycle automatically disabled Mode no Setting no Initial setting Check 1 1 01 2 1 02 2 3 1 03 2 3 1 04 2 1 05 2 Mode Power failure automatic reco...

Page 21: ... to the cooling or heating mode Make sure that cold or warm wind is blown out 5 Press the Fan speed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote contro...

Page 22: ...it Remark For details check the LED display of the outdoor controller board Output pattern A Errors detected by indoor unit Wireless remote controller Beeper sounds OPERATION INDICATOR lamp flashes Number of times 1 2 3 4 5 6 7 8 9 10 11 12 No sound Wired remote controller Check code P1 P2 P9 E6 E7 P4 P5 P6 EE P8 E4 Fb Symptom Intake sensor error Pipe Liquid or 2 phase pipe sensor error Indoor out...

Page 23: ...maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C 104 F during cold season But never use naked fire or steam 9 Test run Indicates whether control power is supplied Make sure that this LED is always lit Indicates whether power is supplied to the remote controller This LED lights only in the case of the indoor unit which is connected to the outdoor unit ...

Reviews: