background image

9

Fig. 6-7

Mode number

Setting number

Refrigerant address

Unit number

1

2

3

4

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

A

B

D

C

G

E

F

4

1

2

1

3 4

1

2

6. Electrical work

6.4. Remote controller (Wired remote controller)

1) Installing procedures

(1) Select an installing position for the remote controller. (Fig. 6-4)
The temperature sensors are located on both remote controller and indoor unit.

s

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

A

Remote controller profile

B

Required clearances surrounding the remote controller

C

Installation pitch

(2) Seal the service entrance for the remote controller cord with putty to prevent pos-

sible invasion of dew drops, water, cockroaches or worms. (Fig. 6-5)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run

the remote controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cut-out upper case, then seal the cut-

out notch with putty similarly as above.

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion

:

(3) For direct installation on the wall

C

Wall

D

Conduit

E

Lock nut

F

Bushing

G

Switch box

H

Remote controller cord

I

Seal with putty

J

Wood screw

2) Connecting procedures (Fig. 6-6)

1

Connect the remote controller cord to the terminal block.

A

To TB5 on the indoor unit

B

TB6 (No polarity)

3) Two remote controllers setting

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

6.5. Function settings (Wired remote controller) (Fig. 6-7)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function setting mode.

Switch OFF the remote controller.
Press the 

A

 and 

B

 buttons simultaneously and hold them for at least 2

seconds. FUNCTION will start to flash.

2

Use the 

C

 button to set the refrigerant address (

3

) to 00.

3

Press 

D

 and [--] will start to flash in the unit number (

4

) display.

4

Use the 

C

 button to set the unit number (

4

) to 00.

5

Press the 

E

 MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number (

1

) display momentarily.

6

Press the 

F

 buttons to set the mode number (

1

) to 04.

7

Press the 

G

 button and the current set setting number (

2

) will flash.

Use the 

F

 button to switch the setting number in response to the power supply

voltage to be used.
Power supply voltage

240 V

: setting number = 1

220 V, 230 V : setting number = 2

8

Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

30

46

30

30

120

83.5

A

B

C

F

A

H

C

D

E

G

I

I

I

H

B

B-1.

B-2.

Fig. 6-5

Fig. 6-4

J

H

A

AB

TB6

B

Fig. 6-6

Function table

Select unit number 00

Mode
Power failure automatic recovery

Indoor temperature detecting

LOSSNAY connectivity

Power voltage

Auto mode (only for PUHZ)

Settings
Not available
Available

*1

Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled

Mode no.

Setting no. Initial setting

setting

01

1

*2

2

*2

1

02

2
3
1

03

2
3

04

1
2

05

1
2

Summary of Contents for Mr.Slim PEA-RP100EA

Page 1: ...glish INSTALLATION MANUAL For safe and correct use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PEA RP EA FOR INSTALLER ...

Page 2: ...o charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or f...

Page 3: ...ed dust may accumulate and breakdown may result Do not touch any switch with wet hands Electric shock may result Do not touch the refrigerant pipes with bare hands during operation The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn...

Page 4: ...3 The ceiling work differs according to the construction of the building Building con structors and interior decorators should be consulted for details 1 Wooden structures Use tie beams single storied houses or second floor beams two story houses as reinforcing members Wooden beams for suspending air conditioners must be sturdy and their sides must be at least 6 cm long if the beams are separated ...

Page 5: ...nd other hazards RP71 140 Liquid pipe ø9 52 thickness 0 8 mm Gas pipe ø15 88 thickness 1 0 mm Do not use pipes thinner than those specified above A Die B Copper pipe A A B Fig 4 2 Copper pipe O D A mm mm Flare tool for R 22 R407C Flare tool for R410A Clutch type ø6 35 1 4 0 0 5 1 0 1 5 ø9 52 3 8 0 0 5 1 0 1 5 ø12 7 1 2 0 0 5 1 0 1 5 ø15 88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 2 Indoor unit...

Page 6: ...r Outdoor connecting cable Use buffer bushing to prevent tensile force to the terminal bed F The Indoor Outdoor connecting cables G Tensile force H Knockout hole for the remote controller cables Use ordinary bushing I The remote controller cables s s s s s Selecting non fuse breaker NF or earth leakage breaker NV 4 Installing the refrigerant piping E F D C B 4 3 Refrigerant and drainage piping loc...

Page 7: ...owever between S3 and S1 these terminals are not electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Install an earth longer than other cables Indoor unit model Indo...

Page 8: ...ircuit rating Wiring Wire No size mm 2 There are three types of labels labels A B and C Affix the appropriate labels to the units according to the wiring method Electric heater For models with heater Connectors connections when shipped from the factory are for indoor unit power supplied from outdoor unit Indoor unit power supplied from outdoor unit when shipped from factory If the indoor and outdo...

Page 9: ... indoor unit 6 5 Function settings Wired remote controller Fig 6 7 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Go to the function setting mode Switch OFF the remote controller Press the A and B buttons simultaneously and hold them for at least 2 seconds FUNCTION will start to flash 2 Use the C button to set the refrigerant address ...

Page 10: ...sting pipes that carried R22 refrigerant replacement op eration must be performed before performing a test run If new pipes are used these procedures are not necessary If existing pipes that carried R22 refrigerant are used for the RP3 model these procedures are not necessary The replacement operation cannot be performed Replacement operation procedures 1 Supply power 2 Set DIP switch SW8 2 on the...

Page 11: ...E Check code F Unit address Fig 8 2 ERROR CODE ERROR CODE B F E PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF ERROR CODE C B A E D 8 Test run Output pattern A Errors detected by indoor unit Beeper sounds OPERATION Symptom Remark INDICATOR lamp flashes Check code Number of times 1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor erro...

Page 12: ...outdoor units Make sure that this LED is always blinking 8 4 Check of drainage During the trial run ensure the water is being properly drained out and that no water is leaking from joints Always check this during installation even if the unit is not required to provide cooling drying at that time 8 Test run Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Beeper sou...

Page 13: ... press the ON OFF button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use the following proce dure to start this operation COOL STABLE MODE HEAT STABLE MODE STABLE MODE CANCEL Stable cooling operation Stable heating operation Stable operation cancellation Di...

Page 14: ......

Page 15: ......

Page 16: ...sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Thailand BG79U642H01 ...

Reviews: