background image

8

5. Operation

6.1. For Wired Remote-controller (option)

You can use Function Selection of remote controller to select which of
three types of timer to use: 

1

 Weekly timer, 

2

 Simple timer, or 

3

 Auto Off

timer.

6.1.1. Weekly Timer

The weekly timer can be used to set up to eight operations for each day
of the week.
• Each operation may consist of any of the following: ON/OFF time

together with a temperature setting, or ON/OFF time only, or tempera-
ture setting only.

• When the current time reaches a time set at this timer, the air

conditioner carries out the action set by the timer.

Time setting resolution for this timer is 1 minute.

Note:
*1. Weekly Timer/Simple Timer/Auto Off Timer cannot be used at the same time.
*2. The weekly timer will not operate when any of the following conditions is in

effect.
The timer feature is off; the system is in an malfunction state; a test run is
in progress; the remote controller is undergoing self-check or remote con-
troller check; the user is in the process of setting a function; the user is in
the process of setting the timer; the user is in the process of setting the
current day of the week or time; the system is under central control. (Spe-
cifically, the system will not carry out operations (unit on, unit off, or tem-
perature setting) that are prohibited during these conditions.)

˚C

SUN

ON

WEEKLY

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

2

4

2

3

A

9

78

0

4

1

3

B

1

Operation No.

Day Setting

<How to Set the Weekly Timer>

1. Be sure that you are at a standard control screen, and that the weekly

timer indicator 

1

 is shown in the display.

6. Timer

5.5. Ventillation

s

s

s

s

s

For LOSSNAY combination

5.5.1. For Wired Remote-controller

To run the ventilator together with the indoor unit:

Press the ON/OFF button 

1

.

• The Vent indication appears on the screen (at 

8

). The ventilator will

now automatically operate whenever the indoor unit is running.

To run the ventilator independently:

Press the Mode button 

2

 until 

 appears on the display. This will

cause the ventilator to start.

To change the ventilator force:

Press the Ventilation button 

8

 as necessary.

• Each press toggles the setting, as shown below.

5.5.2. For Wireless Remote-controller

The ventilator will automatically operate when the indoor unit turns on.

No indication on the wireless remote controller.

Note:
By setting the day to “Sun Mon Tues Wed Thurs Fri Sat”, you can set the same
operation to be carried out at the same time every day.
(Example: Operation 2 above, which is the same for all days of the week.)

<Setting the Weekly Timer>

5. Press the appropriate Set Time button 

A

 as necessary to set the de-

sired time (at 

5

).

* As you hold the button down, the time first increments in minute inter-

vals, then in ten-minute intervals, and then in one-hour intervals.

6. Press the ON/OFF button 

1

  to select the desired operation (ON or

OFF), at 

6

.

* Each press changes the next setting, in the following sequence: No

display (no setting) 

 “ON” 

 “OFF”

˚C

SUN

ON

WEEKLY

6

7

5

Shows the selected operation (ON or OFF)
* Does not appear if operation is not set.

Shows the temperature setting
* Does not appear if temperature is not

set.

Shows the time
setting

The display and the fan speed of the unit will differ in the following situa-
tions:
• When STAND BY and DEFROST are displayed.
• Just after the heating mode (while waiting to change to another mode).
• When the temperature of the room is higher than the temperature set-

ting of the unit operating in the heating mode.

• In the dry operation, the indoor fan automatically turns to low-speed

operation. Switching of fan speed is impossible.

• When the temperature of the heat exchanger is low in the heating mode

(e.g., immediately after heating operation starts).

Note:

In the following cases, the actual fan speed generated by the unit will differ
from the speed shown the remote controller display.
1. While the display is showing “STAND BY” or “DEFROST”.
2. When the temperature of the heat exchanger is low in the heating mode.

(e.g. immediately after heating operation starts)

3. In HEAT mode, when room temperature is higher than the temperature

setting.

4. When the unit is in DRY mode.

Low

High

Op No.

Sunday

Monday

Saturday

No. 1

No. 2

No. 8

• 8:30
• ON
• 23 °C

• 10:00
• OFF

• 10:00
• OFF

• 10:00
• OFF

• 10:00
• OFF

Setup Matrix

<Operation 1 settings for Sunday>

Start the air conditioner at 8:30, with
the temperature set to 23 °C.

<Operation 2 settings for every day>

Turn off the air conditioner at 10:00.

2. Press the Timer Menu button 

B

, so that the “Set Up” appears on the

screen (at 

2

). (Note that each press of the button toggles the display

between “Set Up” and “Monitor”.)

3. Press the Timer On/Off (Set Day) button 

9

 to set the day. Each press

advances the display at 

3

 to the next setting, in the following sequence:

“Sun Mon Tues Wed Thurs Fri Sat” 

 “Sun” 

 ... 

 “Fri” 

 “Sat” 

 “Sun

Mon Tues Wed Thurs Fri Sat”...

4. Press the 

 or 

 Operation button (

7

 or 

8

) as necessary to select the

appropriate operation number (1 to 8) 

4

.

* Your inputs at Steps 3 and 4 will select one of the cells from the matrix

illustrated below.
(The remote-controller display at left shows how the display would
appear when setting Operation 1 for Sunday to the values indicated
below.)

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...Air Conditioners PEA RP100 125 140GAA English OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit FOR USER English ORIGINAL ...

Page 2: ...e unit and on the nameplate Doing so may cause the unit or pipes to burst or result in explosion or fire during use during repair or at the time of disposal of the unit It may also be in violation of applicable laws MITSUBISHI ELECTRIC CORPORATION cannot be held responsi ble for malfunctions or accidents resulting from the use of the wrong type of refrigerant Never repair the unit or transfer it t...

Page 3: ...le inside temperature is one that is within 5 C of the outside temperature Do not leave handicapped people or infants sitting or standing in the path of the airflow from the air conditioner This could cause health problems Caution Do not direct the airflow at plants or caged pets Ventilate the room frequently If the unit is operated continu ously in a closed room for a long period of time the air ...

Page 4: ... after one hour at which time the airflow di rection also changes Room Temperature display Showstheroomtemperature Theroom temperature display range is 8 39 C The display flashes if the temperature is less than 8 C or 39 C or more Louver display Indicates the action of the swing louver Does not appear if the louver is station ary Power On indicator Indicates that the power is on Fan Speed indicato...

Page 5: ...acing the remote controller install the holder included with the remote con troller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert two AAA batter ies and then install the top cover Top cover 2 Press the Reset button CLOCK CHECK RESET SET TESTRUN MODE FAN VANE LOUVER min h AUTOSTART AUTOSTOP ON OFF T...

Page 6: ... Selection of remote controller Set Day Time Standard Control Screens OFF ON Timer Monitor Timer Setup A D C B C B 1 Press the or Set Time button A to show display 2 2 Press the Timer On Off Set Day button 9 to set the day Each press advances the day shown at 3 Sun Mon Fri Sat 3 Press the appropriate Set Time button A as necessary to set the time As you hold the button down the time at 4 will incr...

Page 7: ...oller as shown below 5 Operation To Stop Operation Press the ON OFF button 1 again The ON lamp 1 and the display area go dark Note Even if you press the ON OFF button immediately after shutting down the op eration is progress the air conditioner will not start for about three minutes This is to prevent the internal components from being damaged 5 2 Mode select Press the operation mode button 2 and...

Page 8: ...ry day Example Operation 2 above which is the same for all days of the week Setting the Weekly Timer 5 Press the appropriate Set Time button A as necessary to set the de sired time at 5 As you hold the button down the time first increments in minute inter vals then in ten minute intervals and then in one hour intervals 6 Press the ON OFF button 1 to select the desired operation ON or OFF at 6 Each...

Page 9: ...o that the time setting clears to at 4 If you want to use only an ON setting or only an OFF setting be sure that the setting you do not wish to use is shown as C C TIME SUN WEEKLY 0 C C TIME SUN WEEKLY 0 7 Press the appropriate Set Temperature button 3 to set the desired temperature at 7 Each press changes the setting in the following sequence No display no setting 24 25 29 30 12 23 No display Ava...

Page 10: ...d is ON setting 5 hours OFF setting 2 hours 3 hours At Timer Start Display shows the timer s OFF setting hours remaining to OFF At 5 hours after timer start The air conditioner comes on and will continue to run until someone turns it off 6 1 3 Auto Off Timer This timer begins countdown when the air conditioner starts and shuts the air conditioner off when the set time has elapsed Available setting...

Page 11: ...the Filter button4 press and hold down the ON OFF button 1 for 2 seconds so that the Locked indication disappears from the screen at 1 7 Other Functions C C TIME SUN FUNCTION PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF 4 1 1 Lock Indicator 7 1 Locking the Remote Controller Buttons Operation function limit controller If you wish you can lock the re...

Page 12: ...can be changed using the remote controller function selection mode Change the setting when needed Item 1 1 Change Language CHANGE LANGUAGE 2 Function limit FUNCTION SELECTION 3 Mode selection MODE SELEC TION 4 Display change DISP MODE SETTING Item 2 Language setting to display 1 Operation function limit setting operation lock LOCKING FUNCTION 2 Use of automatic mode setting SELECT AUTO MODE 3 Temp...

Page 13: ...ection Display mode setting Operation lock setting is not used Initial setting value Operation lock setting is except On Off button Operation lock setting is All buttons The automatic mode is displayed when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The ...

Page 14: ...it setting and the lower limit setting press the button H The selected setting will flash and the temperature can be set Settable range Cooling Dry mode Lower limit 19 C 30 C Upper limit 30 C 19 C Heating mode Lower limit 17 C 28 C Upper limit 28 C 17 C Automatic mode Lower limit 19 C 28 C Upper limit 28 C 19 C 4 3 Mode selection setting 1 Remote controller main sub setting To switch the setting p...

Page 15: ...matic mode setting Temperature range limit setting Use of automatic filter elevation panel up down operation mode setting Use of fixed airflow direction mode setting Limit temperature cooling day mode Limit temperature heating mode Limit temperature auto mode Mode selection Remote controller setting MAIN Remote controller setting SUB Use of clock setting Setting the day of the week and time Timer ...

Page 16: ... lit when unit is operating unlit when unit is not operat ing 2 Emergency operation In cases where the remote control unit does not operate properly use either the COOL or HEAT button on the wireless remote control signal receiver to toggle the unit on or off On cooler only units pushing the HEAT button toggles the fan on and off Pressing the COOL or HEAT button selects the following settings Oper...

Page 17: ...nit draws in air that contains gases produced from the walls carpeting and furniture as well as odors trapped in clothing and then blows this air back into the room If the indoor temperature and the humidity are high this condition may occur when operation starts During defrosting mode cool airflow may blow down and appear like a mist During cooling mode water may form and drip from the cool pipes...

Page 18: ...higher than the noise specification which was measured in an echo free room The batteries are low Replace the batteries and press the Reset button If nothing appears even after the batteries are replaced make sure that the batteries are installed in the correct directions The self diagnosis function has operated to protect the air conditioner Do not attempt to repair this equipment by yourself Tur...

Page 19: ...19 ...

Page 20: ...KD79M110H02 Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: