8. Function Selection

[Detailed setting]

[4]–1. CHANGE LANGUAGE setting

The language that appears on the dot display can be selected.

• Press the [[

MENU] button 

G

 to change the language.

1

 English (GB), 

2

 German (D), 

3

 Spanish (E), 

4

 Russian (RU),

5

 Italian (I), 

6

 Chinese (CH), 

7

 French (F), 

8

 Japanese (JP)

Refer to the dot display table.

[4]–2. Function limit

(1) Operation function limit setting (operation lock)

• To switch the setting, press the [

ON/OFF] button 

D

.

1

  no1: Operation lock setting is made on all buttons other than the

[

ON/OFF] button.

2

 no2: Operation lock setting is made on all buttons.

3

 OFF (Initial setting value): Operation lock setting is not made.

* To make the operation lock setting valid on the normal screen, it is

necessary to press buttons (Press and hold down the [FILTER] and
[

ON/OFF] buttons at the same time for two seconds.) on the

normal screen after the above setting is made.

(2) Use of automatic mode setting

When the remote controller is connected to the unit that has automatic
operation mode, the following settings can be made.
• To switch the setting, press the [

ON/OFF] button 

D

.

1

ON (Initial setting value):
The automatic mode is displayed when the operation mode is
selected.

2

OFF:
The automatic mode is not displayed when the operation mode
is selected.

(3) Temperature range limit setting

After this setting is made, the temperature can be changed within the
set range.
• To switch the setting, press the [

ON/OFF] button 

D

.

1

LIMIT TEMP COOL MODE:
The temperature range can be changed on cooling/dry mode.

2

LIMIT TEMP HEAT MODE:
The temperature range can be changed on heating mode.

3

LIMIT TEMP AUTO MODE:
The temperature range can be changed on automatic mode.

4

OFF (initial setting): The temperature range limit is not active.

* When the setting, other than OFF, is made, the temperature range

limit setting on cooling, heating and automatic mode is made at the
same time. However, the range cannot be limited when the set
temperature range has not changed.

• To increase or decrease the temperature, press the [

TEMP. (

)

or (

)] button 

F

.

• To switch the upper limit setting and the lower limit setting, press the

[

] button 

H

. The selected setting will flash and the temperature

can be set.

• Settable range

Cooling/Dry mode:

Lower limit:19°C ~ 30°C

Upper limit:30°C ~ 19°C

Heating mode:

Lower limit:17°C ~ 28°C

Upper limit:28°C ~ 17°C

Automatic mode:

Lower limit:19°C ~ 28°C

Upper limit:28°C ~ 19°C

[4]–3. Mode selection setting

(1) Remote controller main/sub setting

• To switch the setting, press the [

ON/OFF] button 

D

.

1

Main:

The controller will be the main controller.

2

Sub:

The controller will be the sub controller.

(2) Use of clock setting

• To switch the setting, press the [

ON/OFF] button 

D

.

1

ON:

The clock function can be used.

2

OFF:

The clock function cannot be used.

(3) Timer function setting

• To switch the setting, press the [

ON/OFF] button 

D

 (Choose one

of the followings.).

1

WEEKLY TIMER (initial setting value):
The weekly timer can be used.

2

AUTO OFF TIMER:
The auto off timer can be used.

3

SIMPLE TIMER:
The simple timer can be used.

4

TIMER MODE OFF:
The timer mode cannot be used.

* When the use of clock setting is OFF, the “WEEKLY TIMER” cannot

be used.

(4) Contact number setting for error situation

• To switch the setting, press the [

ON/OFF] button 

D

.

1

CALL OFF:
The set contact numbers are not displayed in case of error.

2

CALL **** *** ****:
The set contact numbers are displayed in case of error.
CALL_:
The contact number can be set when the display is as shown on
the left.

• Setting the contact numbers

To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [

TEMP.

(

) and (

)] button 

F

 to move the cursor to the right (left). Press

the [

CLOCK (

) and (

)] button 

C

 to set the numbers.

[4]–4. Display change setting

(1) Temperature display °C/°F setting

• To switch the setting, press the [

 ON/OFF] button 

D

.

1

°C:

The temperature unit °C is used.

2

°F:

The temperature unit °F is used.

(2) Suction air temperature display setting

• To switch the setting, press the [

ON/OFF] button 

D

.

1

ON:

The suction air temperature is displayed.

2

OFF:

The suction air temperature is not displayed.

(3) Automatic cooling/heating display setting

• To switch the setting, press the [

ON/OFF] button 

D

.

1

ON:
One of “Automatic cooling” and “Automatic heating” is displayed
under the automatic mode is running.

2

OFF:
Only “Automatic” is displayed under the automatic mode.

Summary of Contents for Mr.Slim PEA-RP100

Page 1: ...Air Conditioners PEA RP100 125 140GAA English OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit FOR USER English ORIGINAL ...

Page 2: ...e unit and on the nameplate Doing so may cause the unit or pipes to burst or result in explosion or fire during use during repair or at the time of disposal of the unit It may also be in violation of applicable laws MITSUBISHI ELECTRIC CORPORATION cannot be held responsi ble for malfunctions or accidents resulting from the use of the wrong type of refrigerant Never repair the unit or transfer it t...

Page 3: ...le inside temperature is one that is within 5 C of the outside temperature Do not leave handicapped people or infants sitting or standing in the path of the airflow from the air conditioner This could cause health problems Caution Do not direct the airflow at plants or caged pets Ventilate the room frequently If the unit is operated continu ously in a closed room for a long period of time the air ...

Page 4: ... after one hour at which time the airflow di rection also changes Room Temperature display Showstheroomtemperature Theroom temperature display range is 8 39 C The display flashes if the temperature is less than 8 C or 39 C or more Louver display Indicates the action of the swing louver Does not appear if the louver is station ary Power On indicator Indicates that the power is on Fan Speed indicato...

Page 5: ...acing the remote controller install the holder included with the remote con troller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert two AAA batter ies and then install the top cover Top cover 2 Press the Reset button CLOCK CHECK RESET SET TESTRUN MODE FAN VANE LOUVER min h AUTOSTART AUTOSTOP ON OFF T...

Page 6: ... Selection of remote controller Set Day Time Standard Control Screens OFF ON Timer Monitor Timer Setup A D C B C B 1 Press the or Set Time button A to show display 2 2 Press the Timer On Off Set Day button 9 to set the day Each press advances the day shown at 3 Sun Mon Fri Sat 3 Press the appropriate Set Time button A as necessary to set the time As you hold the button down the time at 4 will incr...

Page 7: ...oller as shown below 5 Operation To Stop Operation Press the ON OFF button 1 again The ON lamp 1 and the display area go dark Note Even if you press the ON OFF button immediately after shutting down the op eration is progress the air conditioner will not start for about three minutes This is to prevent the internal components from being damaged 5 2 Mode select Press the operation mode button 2 and...

Page 8: ...ry day Example Operation 2 above which is the same for all days of the week Setting the Weekly Timer 5 Press the appropriate Set Time button A as necessary to set the de sired time at 5 As you hold the button down the time first increments in minute inter vals then in ten minute intervals and then in one hour intervals 6 Press the ON OFF button 1 to select the desired operation ON or OFF at 6 Each...

Page 9: ...o that the time setting clears to at 4 If you want to use only an ON setting or only an OFF setting be sure that the setting you do not wish to use is shown as C C TIME SUN WEEKLY 0 C C TIME SUN WEEKLY 0 7 Press the appropriate Set Temperature button 3 to set the desired temperature at 7 Each press changes the setting in the following sequence No display no setting 24 25 29 30 12 23 No display Ava...

Page 10: ...d is ON setting 5 hours OFF setting 2 hours 3 hours At Timer Start Display shows the timer s OFF setting hours remaining to OFF At 5 hours after timer start The air conditioner comes on and will continue to run until someone turns it off 6 1 3 Auto Off Timer This timer begins countdown when the air conditioner starts and shuts the air conditioner off when the set time has elapsed Available setting...

Page 11: ...the Filter button4 press and hold down the ON OFF button 1 for 2 seconds so that the Locked indication disappears from the screen at 1 7 Other Functions C C TIME SUN FUNCTION PAR 21MAA ON OFF FILTER CHECK OPERATION CLEAR TEST TEMP MENU BACK DAY MONITOR SET CLOCK ON OFF 4 1 1 Lock Indicator 7 1 Locking the Remote Controller Buttons Operation function limit controller If you wish you can lock the re...

Page 12: ...can be changed using the remote controller function selection mode Change the setting when needed Item 1 1 Change Language CHANGE LANGUAGE 2 Function limit FUNCTION SELECTION 3 Mode selection MODE SELEC TION 4 Display change DISP MODE SETTING Item 2 Language setting to display 1 Operation function limit setting operation lock LOCKING FUNCTION 2 Use of automatic mode setting SELECT AUTO MODE 3 Temp...

Page 13: ...ection Display mode setting Operation lock setting is not used Initial setting value Operation lock setting is except On Off button Operation lock setting is All buttons The automatic mode is displayed when the operation mode is selected Initial setting value The automatic mode is not displayed when the operation mode is selected The temperature range limit is not active Initial setting value The ...

Page 14: ...it setting and the lower limit setting press the button H The selected setting will flash and the temperature can be set Settable range Cooling Dry mode Lower limit 19 C 30 C Upper limit 30 C 19 C Heating mode Lower limit 17 C 28 C Upper limit 28 C 17 C Automatic mode Lower limit 19 C 28 C Upper limit 28 C 19 C 4 3 Mode selection setting 1 Remote controller main sub setting To switch the setting p...

Page 15: ...matic mode setting Temperature range limit setting Use of automatic filter elevation panel up down operation mode setting Use of fixed airflow direction mode setting Limit temperature cooling day mode Limit temperature heating mode Limit temperature auto mode Mode selection Remote controller setting MAIN Remote controller setting SUB Use of clock setting Setting the day of the week and time Timer ...

Page 16: ... lit when unit is operating unlit when unit is not operat ing 2 Emergency operation In cases where the remote control unit does not operate properly use either the COOL or HEAT button on the wireless remote control signal receiver to toggle the unit on or off On cooler only units pushing the HEAT button toggles the fan on and off Pressing the COOL or HEAT button selects the following settings Oper...

Page 17: ...nit draws in air that contains gases produced from the walls carpeting and furniture as well as odors trapped in clothing and then blows this air back into the room If the indoor temperature and the humidity are high this condition may occur when operation starts During defrosting mode cool airflow may blow down and appear like a mist During cooling mode water may form and drip from the cool pipes...

Page 18: ...higher than the noise specification which was measured in an echo free room The batteries are low Replace the batteries and press the Reset button If nothing appears even after the batteries are replaced make sure that the batteries are installed in the correct directions The self diagnosis function has operated to protect the air conditioner Do not attempt to repair this equipment by yourself Tur...

Page 19: ...19 ...

Page 20: ...KD79M110H02 Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: