Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.
• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
instruction manual.
• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller.
.
3. The horizontal vanes on the unit cannot be operated using the louver switch.
4. The range of room temperature indication is between 10
:
and 38
:
.
CN560
TB580
2
1
2
A
B
Indoor unit
Remote control cord that came with
the MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set.
SW501:
SW501- No. 1-4: Refrigerant address
Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.
Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
1
Outdoor unit
2
Outdoor unit
3
Indoor unit
4
Interface
5
MA remote controller
Refrigerant
address
0
1
2
15
SW501- No. 5–6
ON
5
6
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller.
* This can be switched when an accurate room temperature cannot be detected by the air conditioner unit.
PE-EAK series do not have a room temperature sensor on their MA remote controllers.
No. 5 should normally be set to OFF.
Under the following conditions, No.6 should normally be set to ON.
Interface unit
Refrigerant
address "0"
Refrigerant
address "1"
Refrigerant
address "2"
MA remote controller
(PAR-21MAA)
* PAR-20MAA cannot be used
with this interface.
1
1
2
3
3
3
3
4
5
4
4
OC394--2.qxp 06.5.23 5:45 PM Page 47