13
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge
pressure
Suction
pressure
Discharge
temperature
Condensing
temperature
Suction
temperature
Ref. pipe
length
Discharge air
temperature
Service Ref.
Mode
W
kW
V
A
V
A
MPa
MPa
:
:
:
m
:
:
:
:
:
(kgf/
F
)
(kgf/
F
)
(20.2)
(4.4)
(19.9)
(4.5)
(19.0)
(4.9)
(20.5 )
(4.1)
Cooling
13,500
6.06
1, 60
220
1.99
PU-5TJSA.TH
3, 60
220
16.83
1.98
0.43
78.3
51.9
1.6
5
27
19
14.9
35
24
Cooling
14,000
5.65
1, 50
220
2.50
PU-6YJSA
1
.TH
3, 50
380
8.63
1.95
0.44
77.8
50.8
1.7
5
27
19
14.5
35
24
Cooling
12,100
5.10
1, 50
220
2.50
PU-5YJSA
1
.TH
3, 50
380
8.15
1.86
0.48
72.2
49.3
- 0.9
5
27
19
15.5
35
24
Cooling
15,200
6.58
1, 60
220
1.99
PU-6TJSA.TH
3, 60
220
18.70
2.01
0.40
81
52.1
- 0.5
5
27
19
14.1
35
24
PE-5EAK.TH(-U)
PE-6EAK.TH(-U)
PE-5EAK.TH(-U)
PE-6EAK.TH(-U)
T
otal
Electrical Circuit
Refrigerant Circuit
Indoor side
Outdoor side
Intake air
temperature
Intake air
temperature
D.B.
W.B.
D.B.
D.B.
W.B.
The unit of pressure has been changed to Mpa based on SI (International System of Units) in accordance with I.S.O.
(International Organization for Standardization).
The conversion factor is : 1(Mpa) =10.2 (
O
O
f/
F
F
)
OC394--1.qxp 06.5.23 5:44 PM Page 13