33
MUZ-GC50NA-
C2
No.
Symptom
LED indication
Abnormal point/
Condition
Condition
Correspondence
1
Outdoor unit
does not oper-
ate.
1-time
fl
ash every
2.5 seconds
Outdoor power sys-
tem
Overcurrent protection stop is continuously performed 3 times
within 1 minute after the compressor gets started, or failure of
restart of compressor has repeated 24 times.
Reconnect connector of compres-
sor.
Refer to 9-5. "How to check in-
verter/compressor".
Check stop valve.
•
•
•
2
Outdoor thermistors Discharge temperature thermistor,
fi
n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor or ambi-
ent temperature thermistor shorts or opens during compressor
running.
Refer to 9-5. "Check of outdoor
thermistors".
•
3
Outdoor control sys-
tem
Nonvolatile memory data cannot be read properly.
(The left lamp of OPERATION INDICATOR lamp of the indoor
unit lights up or
fl
ashes 7-time.)
Replace inverter P.C. board.
•
4
6-time
fl
ash
2.5 seconds OFF
Serial signal
The communication fails between the indoor and outdoor unit
for 3 minutes.
Refer to 9-5. "How to check mis-
wiring and serial signal error.
•
5
11-time
fl
ash
2.5 seconds OFF
Stop valve/
Closed valve
Closed valve is detected by compressor current.
Check stop valve.
•
6
14-time
fl
ash
2.5 seconds OFF
Outdoor unit
(Other abnormality)
Outdoor unit is defective.
Refer to 9-2.2. "Flow chart of the
detailed outdoor unit failure mode
recall function".
•
7
'Outdoor unit
stops and
restarts 3 min-
utes later' is
repeated.
2-time
fl
ash
2.5 seconds OFF
Overcurrent protec-
tion
Large current
fl
ows into intelligent power module.
Reconnect connector of compres-
sor.
Refer to 9-5. "How to check in-
verter/compressor".
Check stop valve.
•
•
•
8
3-time
fl
ash
2.5 seconds OFF
Discharge tempera-
ture overheat protec-
tion
Temperature of discharge temperature thermistor exceeds 116
°C, compressor stops. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig-
erant amount.
Refer to 9-5. "Check of LEV".
•
•
9
4-time
fl
ash
2.5 seconds OFF
Fin temperature /P.C.
board temperature
thermistor overheat
protection
Temperature of
fi
n temperature thermistor on the heat sink
exceeds 75 ~ 88°C or temperature of P.C. board temperature
thermistor on the inverter P.C.board exceeds 72 ~ 82°C.
Check around outdoor unit.
Check outdoor unit air passage.
Refer to 9-5. "Check of outdoor
fan motor".
•
•
•
10
5-time
fl
ash
2.5 seconds OFF
High pressure pro-
tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost
thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig-
erant amount.
Check stop valve.
•
•
11
8-time
fl
ash
2.5 seconds OFF
Compressor syn-
chronous abnormal-
ity
The waveform of compressor current is distorted.
Reconnect connector of compres-
sor.
Refer to 9-5. "How to check in-
verter/compressor".
•
•
12
10-time
fl
ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 9-5. "Check of outdoor
fan motor.
Refer to 9-5. "Check of inverter
P.C. board.
•
•
13
12-time
fl
ash
2.5 seconds OFF
Each phase current
of compressor
Each phase current of compressor cannot be detected nor-
mally
Refer to 9-5. "How to check in-
verter/compressor".
•
14
13-time
fl
ash
2.5 seconds OFF
DC voltage
DC voltage of inverter cannot be detected normally.
Refer to 9-5. "How to check in-
verter/compressor".
•
15 Outdoor unit
operates.
1-time
fl
ash
2.5 seconds OFF
Frequency drop by
current protection
Current from power outlet reaches the protection current, and
compressor frequency lowers.
The unit is normal, but check the
following.
Check if indoor
fi
lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air cir-
culation is short cycled.
•
•
•
16
3-time
fl
ash
2.5 seconds OFF
Frequency drop by
high pressure pro-
tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT
mode, compressor frequency lowers.
Frequency drop by
defrosting in COOL
mode
Indoor coil thermistor reads 8°C or less in COOL mode, com-
pressor frequency lowers.
17
4-time
fl
ash
2.5 seconds OFF
Frequency drop by
discharge tempera-
ture protection
Temperature of discharge temperature thermistor exceeds 111
°C, compressor frequency lowers.
Check refrigerant circuit and refrig-
erant amount.
Refer to 9-5. "Check of LEV".
Refer to 9-5. "Check of outdoor
thermistors".
•
•
•
18
Outdoor unit
operates.
7-time
fl
ash
2.5 seconds OFF
Low discharge tem-
perature protection
Temperature of discharge temperature thermistor has been 50
°C or less for 20 minutes.
Refer to 9-5. "Check of LEV".
Check refrigerant circuit and refrig-
erant amount.
•
•
19
8-time
fl
ash
2.5 seconds OFF
PAM protection PAM
: Pulse Amplitude
Modulation
The overcurrent
fl
ows into IGBT (Insulated Gate Bipolar tran-
sistor : TR821) or when the bus-bar voltage reaches 320 V or
more, PAM stops and restarts.
This is not malfunction. PAM protec-
tion will be activated in the following
cases;
1 Instantaneous power voltage drop.
(Short time power failure)
2 When the power supply voltage is
high.
20
9-time
fl
ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com-
pressor is correctly connected.
Refer to 9-5. "How to check in-
verter/compressor".
•
NOTE
: 1. The location of LED is illustrated at the right
fi
gure. Refer to 9-6.1.
2. LED is lighted during normal operation.
The
fl
ashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the
fl
ashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Flashing
→
Inverter P.C. board(Parts side)
Summary of Contents for Mr.Slim MUZ-GC25NA - C1
Page 9: ...9 MUZ GC25NA MUZ GC35NA 4 WIRING DIAGRAM ...
Page 10: ...10 MUZ GC50NA C1 MUZ GC60NA C1 ...
Page 11: ...11 MUZ GC50NA C2 ...
Page 12: ...12 MUZ GC60NA C2 ...
Page 13: ...13 MUZ GC71NA ...
Page 61: ...61 ...
Page 62: ...62 ...
Page 63: ...63 ...